6 START-UP
Start-up sequence
Unit power supply ON
Yes / No
1 compressor carter resistances operating at least since 8 hours
2 off-load voltage measure
3 phase sequence check
4 pump manual start-up and flow check
5 refrigeration circuit shut-off valves opening (if applicable)
6 unit ON
7 load voltage measure
8 verify the lack of bubbles in the liquid light (if applicable)
9 check of all fan operating
10 measure of return and supply water temperature
11 super-heating and sub-cooling measure
12 check no anomalous vibrations are present
13 set-point personalization
14 scheduling customisation
15 complete and available unit documentation