Water reset
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
It is possible to limit the absorbed electric power with an external
signal 0-10 Vcc or 4-20mA.
The setpoint based on the climatic curve and the Water Reset is
displayed on the display
Only if P0051: En WaterReset = 1
Path: Main menu / Unit parameters / Options
Parameters
Short description Description
P0063
TypeWR
Inlet signal type: 0=0-10V; 1=4-20mA
Path: Main Menu / Unit parameters / Water reset
P0283
SWRMinC
Value of the WR control signal corresponding to the correction of the set COOL equal
to 0
Path: Main menu / Unit parameters / Options
P0283
SWRMaxC
Value of the WR control signal corresponding to the correction of the set COOL equal
to the parameter P0281
P0281:
MaxCWRC
Maximum correction to be applied to the setpoint