![CLIVET R513A Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/clivet/r513a/r513a_manual-for-installation-use-and-maintenance_2625610012.webp)
12
4 WATER CONNECTIONS
The unit must always be protected
from freeze.
Otherwise irreversible damage may
occur.
Risk of freeze
If the unit or the relative water connections can be subject to
temperatures close to 0°C:
Mix water with ethylene glycol, or
Safeguard the pipes with heating cables placed under the
insulation, or
Empty the system in cases of long non-use
Anti-freeze solutions
Consider that the use of anti-freeze solution determines an
increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the hydraulic circuit components.
Do not use different glicol mixture (i.e. ethylic with propylene).
% ETHYLENE GLYCOL BY WEIGHT
5% 10% 15% 20% 25% 30% 35% 40% 45% 50%
Freezing temperature
°C -2 -3.9 -6.5 -8.9 -11.8 -15.6 -19.0 -23.4 -27.8 -32.7
Safety temperature
°C 3 1 -1 -4 -6 -10 -14 -19
-23.8
-29.4
Содержание R513A
Страница 1: ...R513A MANUAL FOR INSTALLATION USE AND MAINTENANCE WDAT ik4 120 1 580 2 MF500002 00 11 20...
Страница 20: ...20 5 ELECTRICAL CONNECTIONS...
Страница 34: ...34 7 CONTROL...
Страница 35: ...35 7 CONTROL...
Страница 36: ...36 7 CONTROL...
Страница 37: ...37 7 CONTROL...
Страница 51: ...51 9 ANTIVIBRATION MOUNTS Anti vibration mount support Anti seismic spring antivibration mounts...
Страница 52: ...52 9 ANTIVIBRATION MOUNTS...
Страница 53: ...53 9 ANTIVIBRATION MOUNTS...
Страница 73: ......