INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

TM-2

 and TM-4

™  

Gasket Seal and Gel Seal Ducted, Disposable Ceiling Filter Modules

Gasket Seal Installation – TM-2 and TM-4

The TM Series Disposable Ceiling Filter Modules are unique 

factory-assembled and tested units, incorporating a HEPA 

or ULPA filter media pack, damper-diffuser, an optional  

faceguard, and integral round duct connection. They are 

made with an anodized aluminum housing that is  

 compatible with gasketed T-Bar ceiling grids.

1. 

Before beginning installation of any HEPA or ULPA filter 

module, the system should be cleaned and blown down 

with both roughing filters and prefilters in place. This is 

essential to minimize the initial quantity of particulate that 

might be drawn into the filter modules.

2. 

Carefully remove each bagged module from its shipping 

carton just before installation. Remove the poly bag at the 

point of installation and inspect the filter face for shipping 

damage. Carefully scrutinize each unit before installation. 

Avoid accidentally damaging the delicate filter media while 

handling the filter. (Gloves are recommended to comply 

with some protocol requirements.)

3. 

The TM-2 and TM-4 units are equipped with four hanger 

support points for independently suspending the  

modules. Local codes, rigidity of the ceiling system,  

or owner preference will determine the use of hangers. 

These hangers are available only on the gasket version.

4. 

AAF Flanders recommends that the modules be sealed 

airtight against the ceiling grid. This may be accomplished 

by using pressure-sensitive gasketing, caulking, or 

non-hardening tape sealant. This is a design decision, 

dependent upon room performance requirements.

5.

 When connecting the flexible round duct to the module 

collar, avoid excessive slack in the duct. Where practical, 

set the housing in place, then connect the round duct to 

the collar. Drawbands must be positioned below the  

dimples in the collar to prevent slippage or blowoff of  

the duct connection. Stainless steel, wormgear-type 

drawbands are recommended.

Gel Seal Installation – TM-2 and TM-4

TM-4 Disposable Ceiling Filter Modules are unique  

factory-assembled and tested units, incorporating a  

HEPA or ULPA filter media pack, damper-diffuser, optional 

faceguard, and integral round duct connection. They are 

made with an anodized aluminum housing that is  

compatible with gel seal grid systems.

1. 

Before beginning installation of any HEPA or ULPA filter 

module, the system should be cleaned and blown down 

with both roughing filters and prefilters in place. This is 

essential to minimize the initial quantity of particulate that 

might be drawn into the filter modules.

2. 

Carefully remove each bagged module from its shipping 

carton just before installation. Remove the poly bag at 

the point of installation and inspect the filter face for 

shipping damage. Carefully scrutinize each unit before 

installation. Avoid accidentally damaging the delicate filter 

media while handling the filter. (Gloves are recommended 

to comply with some protocol requirements.)

3.

 Inspect the knife edge seal around the perimeter of the 

module for damage.

4.

 Set the module down into the gel seal grid. Check to be 

sure the knife edge on the module penetrates into the gel 

in the channel on all four sides to form an airtight seal. No 

latches are required. The weight of the module sets the 

unit into the gel seal grid.

5. 

When connecting the flexible round duct to the module  

collar, avoid excessive slack in the duct. Where practical, 

set the housing in place, then connect the round duct 

to the collar. Drawbands must be positioned below the 

dimples in the collar to prevent slippage or blowoff of  

the duct connection. Stainless steel, wormgear-type 

drawbands are recommended.