Installation, configuration and use manual 

 

 

 

  

 

 

ELFOControl

2

 

 

M0CZ40B12-10 

16-12-2013 

Содержание ELFOControl2

Страница 1: ...Installation configuration and use manual ELFOControl2 M0CZ40B12 10 16 12 2013 ...

Страница 2: ...time with high reliability efficiency quality and sa fety The target of the company is to offer advanced systems that assure the best comfort reduce the energy consumption the installation and main tenance costs for all the life cycle of the system With this manual we want to give you information that are useful in all the phases from the reception to the installation and use until the disposal so...

Страница 3: ...ing pag 26 INSTRUCTIONS FOR THE INSTALLER Elfocontrol2 pag 28 Bus RS485 pag 30 System diagrams pag 31 Electrical connections Unit for the production of thermal energy pag 33 Unit for fresh air pag 37 Terminali ambiente pag 39 Ambient terminals pag 41 Module of radiant areas pag 42 Addressing Keyboard unit pag 47 Thermostats pag 51 Modules pag 54 Configuration System component configuration pag 61 ...

Страница 4: ......

Страница 5: ...omic or off for comfort and eco modes temperature and humidity set points can be configured together with the type of ventilation an area can be forced in the required operation mode for a certain period stopping temporarily the ongoing program Setpoint each area has a comfort setpoint optimal comfort greater consumption and an economic set medium comfort minimum consumption the economic set is ca...

Страница 6: ...ure 4 solar status active inactive System areas schedule Switching on and off the system Away function Return to the main display without saving modifications displayed in the subsequent menus Return to the previous display without saving modifications displayed in the subsequent menus Help Alarms System settings Only qualified personnel is allowed to access Save modifications return to the previo...

Страница 7: ...p the system 4 Switch off the system 5 Switch off the system until day hour at the due time the system returns to the status previously set 6 Set the SYSTEM START UP date go to display n 8 7 Set the SYSTEM START UP date go to display n 9 Confirm the modification 2 3 4 5 6 7 8 9 select 2 select 6 1 select 7 ...

Страница 8: ...g only 4 Automatic switches from heating to cooling automatically depending on the outdoor and indoor temperature detected mode enabled only if ELFOFresh2 is present CHANGE MODE 1 Operation of the system Confirm the modification 1 2 3 4 select 1 ...

Страница 9: ...t date and hour to synchronise the system operation Settings Automatic do not activate this setting Set date Select time zone Set hour Use H24 format Select date format To exit drag area 3 downwards 1 2 select 1 select 2 select 3 3 select 4 4 ...

Страница 10: ...mp is used to produce both air conditioning system water and domestic hot water 3 For domestic hot water only The heat pump is used only to produce domestic hot water 4 Deactivate the heat pump The heat pump is switched off 5 Distribution Displays the components in the system and the water temperature The operation of single components of the system can be enabled or excluded select 6 7 or 8 to Ex...

Страница 11: ... set point Fixed no compensation is set on the outdoor temperature the value can be set dew compensation remains active in the Summer Compensated varies according to the outdoor temperature 5 Current set point fix temperature to be set 6 Circuits combined with the system components Not mixed high temperature Mixed circuit 1 or 2 or 3 Confirm the modification 5 3 2 4 6 7 HEAT PUMP CLIMATE SETTINGS ...

Страница 12: ...x 2 3 select 2 select 3 Example Outdoor air 32 C supply water set point 7 C Outdoor air 22 C supply water set point 12 C The curve of the compensated set point can be modified in two ways modify 4 points the curve is modified in detail 2 supply set point sections 2 outdoor temperature sections rapid modification raises or lowers the entire curve CORRECTION MODIFICATION OF 4 POINTS MODIFICATION OF ...

Страница 13: ...ed to modify the climatic curve rapidly without modifying the 4 set points Example Outdoor air 35 C supply water set point 7 C Outdoor air 22 C supply water set point 15 C Correction 2 C in Summer Values after the correction Outdoor air 35 C supply water set point 7 2 9 C Outdoor air 22 C supply water set point 15 2 17 C When correction is active the symbol 9 is displayed For the winter correction...

Страница 14: ... controlled Confirm the modification 1 2 3 4 5 6 7 8 9 10 11 select 1 select 6 DOMESTIC HOT WATER PROGRAMMING Elfocontrol2 is equipped with 3 preset time schedules Up to 7 programs can be saved in the memory All programs can be modified 12 select 12 DOMESTIC HOT WATER SETTINGS 7 Water set point with heat pump is indicated as RELOAD in the programming 8 Water set point with heat pump is indicated a...

Страница 15: ...can be created modify the program using buttons Programming example Day Friday Program Circulation program 1 Operation Profile Confirm the modification start time end time mode set point previous page 01 05 Maintenance ref 8 06 08 Recharge and recirculation ref 7 ref 11 09 11 Maintenance ref 8 12 14 Maintenance and recirculation ref 8 ref 11 15 17 Maintenance ref 8 18 20 Recharge and recirculation...

Страница 16: ...y Compressor status 3 Continuous automatic operation the fresh air unit operates without interruptions 4 Ventilation only forces the ventilation only mode 5 Scheduled automatic operation operation according to the programming 6 Exclude ELFOFresh2 off If four units are installed inside the system settings must be performed on all units 14 select unit and repeat the procedure CONFIGURE THE SET POINT...

Страница 17: ...witched Off the unit is switched off Select 1 2 appears Select 2 3 appears Confirm the modification 1 2 3 A different program can be combined to each day of the week select the day of the week to be programmed the selected day is highlighted in grey select a program among the 14 available the saved program can be removed a new program can be created modify the program using buttons Programming exa...

Страница 18: ...eduled programming Economic follows the scheduled programming but it is forced in Eco Off 3 Fresh air unit Fresh air units can be set in the following modes Normal automatic ventilation Reduced reduced ventilation Off ventilation off 4 Domestic hot water DHW can be set in the following modes Normal follows the scheduled programming Reduced is maintained at a lower temperature for an higher energy ...

Страница 19: ...OGRAMMED MODE Comfort Ideal temperature to use when we are at home Economic Holding temperature to use when the zone is not used PROGRAM ZONE A different program can be combined to each day of the week 5 Select winter or summer season select the day of the week to be programmed the selected day is highlighted in grey summer or winter program among those available the saved program can be removed a...

Страница 20: ...r 21 C for Winter A different temperature can be set for each area To modify the temperature 8 Press Comfort for 2 seconds 9 Set area temperature humidity automatic manual silenced off ventilation fancoil off The temperature of the Economic profile depends on the temperature of the Comfort profile it is higher in summer lower in winter To modify the temperature difference press Economic for 2 sec ...

Страница 21: ...r Comfort difference Economical Temperature 25 C 2 C 27 C Winter Comfort difference Economical Temperature 21 C 2 C 19 C 11 Set the Zone manually in one of the following operation modes 3 Comfort for ever it does not return to the programming for 1 2 3 hours 4 Economic for ever it does not return to the programming for 1 2 3 hours 5 Off for ever it does not return to the programming for 1 2 3 hour...

Страница 22: ...e Living room 2 4 5 C 29 5 C Main entrance 2 0 C 23 0 C Bathroom entrance 25 0 C 2 set temperature living room 25 C 3 temperatures detected by thermostats 4 correction setting cursors Modification of a single component temperature Example Confirm the modification 1 2 select 1 3 4 4 4 ...

Страница 23: ... description of the alarm and date hour of the event Attention Before resetting an alarm identify and remove the cause generating that Repeated resets can cause system malfunctions or irreversible damage In case of doubt contact the After Sales Centre 2 1 3 select 1 select 2 select 3 4 select 3 1 For contact the After Sales Centre ...

Страница 24: ...Page 24 MODIFICATION OF THE PROGRAM NAME Names of the following programs can be customised Domestic hot water Elfofresh2 Zone 4 1 2 3 select 1 select 2 select 3 press for 2 sec 4 ...

Страница 25: ...Page 25 Capital or small letters MODIFICATION OF THE PROGRAM NAME Use the keyboard to type the name of the program Key functions Numbers Space Delete Confirm 5 select 5 ...

Страница 26: ...Page 26 SYSTEM SETTINGS Access to the System settings is reserved only to the After sales Centre It allows setting 2 Parameters 3 System layout 4 Elfocontrol 1 2 3 4 select 1 ...

Страница 27: ...ld be performed by trained personnel having the necessary requirements by the regulations in force and being informed about the risks relevant to these activities Maintenance Only qualified personnel can operate on the system as required by the regulation in force Modification Any type the modifications will end the warranty coverage and the manufacturer responsibility Breakdown Malfuction Using t...

Страница 28: ...Page 28 ELFOCONTROL2 CIECX Uncased box optional 222 38 43 168 3 1 2 micro SD system configuration data 1 ...

Страница 29: ...ication Ethernet side in progress C Power presence Led ON device OK Convertitore Ethernet 485 A ELFOControl2 B Bus RS 485 Customer option CBSX 50 mt spool C converter Ethernet 485 supplied with ELFOControl2 D converter 485 TCP IP 12 24 Vdc o 12 Vac E domotic system Customer F ETHERNET modbus TCP IP Customer G Ethernet UTP cat 5 cable 5 m supplied with ELFOControl2 H power supply max 90 mt I feeder...

Страница 30: ...y single serial line 1000 m Difference in potential between the earth of the two RS485 devices lower than 7 v Provide guards to protect against electrostatic discharges of atmospheric origin Complete last network component INSTALLATION OF THE SERIAL LINE Performed by trained and qualified personnel in data communication networks Performed up to standard Separated from other cables especially from ...

Страница 31: ... be specified by both the Designer and Installer e g expansion tanks vents cocks calibration safety valves etc SYSTEM TYPICAL DIAGRAMS NEW BUILDING WITH RADIANT PANELS AND RADIATORS SYSTEM TYPICAL DIAGRAMS NEW BUILDING WITH RADIANT PANELS FAN COILS AND RADIATORS Ethernet 485 Converter Ethernet 485 Converter ...

Страница 32: ...TORS SYSTEM TYPICAL DIAGRAMS REQUALIFICATION OF EXISTING BUILDING WITH RADIATORS Indicative diagram The components of the system are not indicated because they must be specified by both the Designer and Installer e g expansion tanks vents cocks calibration safety valves etc Ethernet 485 Converter Ethernet 485 Converter ...

Страница 33: ...D COOLING ENERGY GAIA ARIA MSER XEE 31 61 R 410A GAIA ACQUA WSHR XEE 31 61 R 410A GAIA MAXI ARIA MSER XIN 61 R 410A TERMINATION JUMPER Ethernet 485 Converter ELFOENERGY GROUND MEDIUM WSHN XEE 82 802 Termination No Yes Version AC GAIA MAXI ACQUA WSHR XIN 61 R 410A Version AC ...

Страница 34: ...1 81 R 407C HORUS WSAR MT E 21 81 R 407C HORUS WSAR HT E 31 81 R 407C HORUS WSAR HT E 31 81 R 407C UNIT FOR PRODUCING THERMAL AND COOLING ENERGY Ethernet 485 Converter TERMINATION JUMPER For outdoor installation For indoor installation For indoor installation J 3 S 3 S 4 ON S 5 ON S1 S2 J 1 ON RS485 1 LR LV Terminazione No Si ...

Страница 35: ... CMSC2X Serial communication module with RS485 serial converter kit optional ELFOENERGY EXTENDED INVERTER WSAN XIN 21 71 R 410A UNIT FOR PRODUCING THERMAL AND COOLING ENERGY Ethernet 485 Converter TERMINATION JUMPER Terminazione No Si ...

Страница 36: ...l communication module with supervisor MODBUS optional UNIT FOR PRODUCING THERMAL AND COOLING ENERGY Ethernet 485 Converter TERMINATION JUMPER Terminazione No Si VULCAN WBAN 41 81 R 407C GROUND WSH N EE17 121 R 410A MEDIUM WSAN T XEE 82 302 R 410A ...

Страница 37: ...dc FRESH AIR UNIT ELFOFRESH2 CPAN U 200 650 R410a ELFOFRSH LARGE CPAN U 17 51 R410a SP1X RS485 serial port for remote communication optional Ethernet 485 Converter TERMINATION JUMPER Terminazione No Si ELFOFRESH2 CPAN U 70 120 R134a ...

Страница 38: ...38 AMBIENT TERMINALS ELFOROOM2 OUTVOT 3 15 ELFOROOM2 INVOT 3 15 ELFOROOM2 OUTVOT 3 15 ELFOROOM2 INVOT 3 15 Set as shown in the figure SERIAL CARD Ethernet 485 Converter TERMINATION JUMPER Terminazione No Si ...

Страница 39: ...3 31 ELFOSPACE OUT H 3 31 SP1X RS485 serial port for remote communication optional page 29 ELFOSPACE IN V 3 31 CF V 31 242 ELFOSPACE IN H 3 31 BT1 BT2 V3 V2 V1 N 10 11 12 S L 6 7 8 9 CLIVET TALK TERMINAL SPACE CTS CTS CLIVET TALK TERMINAL SPACE Electronic for HID T2 or HID T3 thermostats ELFOControl2 optional Ethernet 485 Converter TERMINATION JUMPER Terminazione No Si J 3 S3 S 4 ON S5 ON S1 S2 J ...

Страница 40: ... 25 71 CF 25 71 CF 91 242 ELFOSPACE BOX2 7 41 SP1X RS485 serial port for remote communication optional page 29 BT1 BT2 V3 V2 V1 N 10 11 12 S L 6 7 8 9 CLIVET TALK TERMINAL SPACE CTS CTS CLIVET TALK TERMINAL SPACE Electronic for HID T2 or HID T3 thermostats ELFOControl2 optional Ethernet 48 5 Converter TERMINATION JUMPER Terminazione No Si J 3 S 3 S 4 ON S5 ON S1 S 2 J 1 ON RS485 1 LR LV ELFOSPACEW...

Страница 41: ...estic hot water Antilegionella cycle scheduling Elfocontrol2 222x43x168 LxHxP 230 1 50 feeder 12Vdc 4 DIN modules Ethernet 485 converter 3 DIN modules Elfocontrol2 CACSX Domestic hot water control kit 290x410x140 LxHxP ACS300X 300 litres DWH tank 600x1615 ØxH ACS500X 500 litres DWH tank 750x1690 ØxH ACS3SX 300 litres DHW tank with solar coil 600x1615 ØxH ACS5SX 500 litres DHW tank with solar coil ...

Страница 42: ...4 G5 G6 AUX ID1 ID2 CH5 CH6 CH4 CH3 CH2 CH1 PWR ZONE X 10 X 1 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6 7 8 9 ADDRESS 1 2 3 4 5 6 230V L N G G0 PWR 230Vac THE MODULE CAN CONTROL 24ac valve on off transformer provided by the client 230v valve on off 230V L N BT1 BT2 RS 485 CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 COM ID1 ID2 COM GND GND GND GND GND GND GND G G0 G1 G0 G2 G0 G3 G0 G4 G0 G5 G0 G6 G0 ...

Страница 43: ...he figure 230V L N G G0 PWR 230Vac THE MODULE CAN CONTROL 24ac valve on off transformer provided by the client 230v valve on off 230V L N BT1 BT2 RS 485 CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 COM ID1 ID2 COM GND GND GND GND GND GND GND G G0 G1 G0 G2 G0 G3 G0 G4 G0 G5 G0 G6 G0 C1 NO1 G1 G2 G3 G4 G5 G6 AUX ID1 ID2 CH5 CH6 CH4 CH3 CH2 CH1 PWR ZONE X 10 X 1 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6...

Страница 44: ... 4 GND 230V L N BT1 BT2 RS 485 CH 1 CH 2 CH 3 CH 4 CH 5 CH 6 COM ID1 ID2 COM GND GND GND GND GND GND GND G G0 G1 G0 G2 G0 G3 G0 G4 G0 G5 G0 G6 G0 C1 NO1 G1 G2 G3 G4 G5 G6 AUX ID1 ID2 CH5 CH6 CH4 CH3 CH2 CH1 PWR ZONE X 10 X 1 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6 7 8 9 1 0 2 3 4 5 6 7 8 9 ADDRESS 1 2 3 4 6 5 GND In the example the bathroom is unique and is managed by the scheduler through 2 zones one f...

Страница 45: ...der channel 6 connectors in position ON 4 switch on the module the word OFF is displayed on the thermostat 5 configure the parameters corresponding to the used channels 6 follow the instruction at page 51 or 52 7 once the addressing is complete move the dip switch placed under channel 6 connectors in position OFF Channel Parameters Description 1 P02 2 Thermoregulation 2 Steps 2 P03 0 Disabled 3 P0...

Страница 46: ...f the compressor once the set has been reached 1031 32 A 0 0 It is an offset on the dew point normally it is set at 2C considering that between the temperature of both the panels and surface there is a difference and on the latter condensation is not formed on the panels This allows working with lower water temperatures at the dew point enhancing the cooling capacities 1069 870 A 20C Dew point lim...

Страница 47: ...he addresses with the lowest value must be assigned to single zone modules Example First zone module address 17 Second zone module address 18 First terminal address 19 Second terminal address 20 GAIA ARIA and ACQUA version AC GAIA MAXI GROUND MEDIUM Parameters to be modified Parameter Mnemonic Name Description Value 315 Index ModBus supervision serial address 2 316 Baud Rate Baud Rate 0 4800 1 960...

Страница 48: ...tate to select the Scheduling menu Press Rotate to select the Configuration menu Press Rotate to select the Machine menu Press Rotate to select the unit Press Select the parameter to be modified Press Enter the value Press Press to return to the main screen Main Menu Stata Alarms Date and hour Configuration Configuration Menu Keypad Unit System s variables Unit configuration All Configuration Setp...

Страница 49: ...ocol Baud Rate 2 4800 3 9600 4 19200 3 CF32 Parity modbus 1 EVEN 2 NONE 3 ODD 2 CL43 DI4 Digital input Configuration remote OFF 2 CL44 DI5 Digital input Configuration remote Summer Winter 0 Press PAr Press CL Press CF01 Select CF30 CF30 Press 0 Set the value 2 Confirm 2 Back to the previous menu Select CF menu CF Repeat the sequence for the other parameters ...

Страница 50: ...dress 3 4 5 or 6 166 Baud Rate Baud Rate 0 4800 1 9600 1 167 Parity Parity 0 NO 1 YES 0 1 Press S E T Parameter Value 1 0 3 2 Enter the PASSWORD 0 3 2 1 3 Access parameter 164 1 6 4 X Y 4 Edit value as indicated in the table 1 6 4 2 5 Repeat the sequence for the other parameters indicated in the table 6 Save in the memory Exit S E T 1 0 3 Units can be CPAN U 70 650 Elfofresh2 and or CPAN U 17 51 E...

Страница 51: ...hin 5 seconds press the keys until P00 is displayed S w i n g P00 3 Press E c o 4 Enter password 321 321 5 Confirm password E c o 6 Access parameter 33 P33 7 Access the value range E c o XY 8 Edit value as indicated in the table 17 9 Confirm the value entered E c o 10 Repeat the sequence for the other parameters indicated in the table 11 Press the keys until the word OFF is displayed on the thermo...

Страница 52: ...icated in the table 17 9 Confirm the value entered OK 10 Repeat the sequence for the other parameters indicated in the table 11 Press until P appears flashing and wait until the word OFF is displayed OK OFF TERMINALS AREA MODULES WITH HID TI2 THERMOSTATS Parameters to be modified Parameter Mnemonic Name Description Value 33 Index Device address 17 18 34 Baud Rate Baud Rate 0 4800 1 9600 2 19200 1 ...

Страница 53: ...w flashings up to the address to be assigned and release the button 3 A fast flashing at the end confirms the procedure 1 Supply and keep the addressing key pressed until the red led starts flashing quickly 2 After a few seconds count the slow flashings up to the address to be assigned and release the button 3 A fast flashing at the end confirms the procedure Addressing key Diagnostics With fixed ...

Страница 54: ...he module the word OFF is displayed on the thermostat 5 follow the instruction at page 48 or 49 6 if several radiant area modules are available max 5 the first will have P33 11 the second will have P33 12 etc 7 once the addressing is complete move the dip switch placed under channel 6 connectors in position OFF Parameters to be modified Parameter Mnemonic Name Description Value 33 Index Device add...

Страница 55: ...2 Temperature HID T3 Temp humidity HID TI2 Temperature uncased For module RS485 see below RS485 MODULE The addressing can be performed from thermostat via selectors on RS485 module From thermostat 1 set selector switches S5 ON 100 hundreds S4 9 unit S3 8 tens 2 set parameters 33 34 35 From selector switches 1 set the address using selector switches S4 unit S3 tens example 17 S4 1 S3 7 2 set using ...

Страница 56: ...re detected by the thermostat in the cooling mode the module closes the valve The module can be used also to control 1 radiant circuit The area module must be powered at 230 Vac 50 Hz Assembly on DIN guide Type of cable used 2x0 35 mm2 with screen on gnd Maximum distance 15 m 1 switch off the module 2 connect a HID T2 HID T3 or HID TI2 thermostat 3 switch on the module the word OFF is displayed on...

Страница 57: ...on the real requirement of energy by the components of that hydraulic circuit Management of the cooling only unit If the boiler is used in conjunction with a unit to produce cooling energy only the MIOX module will also switch circuits depending on the system s operating mode heating or cooling Stand by normally open contacts towards chiller Powered contact towards boiler L N ACS ON OFF RS485 230V...

Страница 58: ...e activated ACS ON OFF RS485 230V 1 2 3 4 13 14 15 16 17 18 19 20 21 22 23 24 8 9 1 2 3 4 5 6 7 11 12 Remote On off from telephone dial Telephone dial Termination jumper Example system in ON 1 1 2 1 System ON System OFF 1 2 System ON Par 49 CLOSE OPEN 0 Not used 1 NC System OFF DHW ON System ON OFF from Elfocontrol2 keypad 2 NA System ON OFF from Elfocontrol2 keypad System OFF DHW ON Set the param...

Страница 59: ...ication with all devices 2 Disconnect bus C of module A 3 Access to the parameter scripture mask via modbus see sideway 4 Point the IO module provisionally addressed at 7 B 5 At parameter 788 of module write 8 6 Point the IO module just addressed at 8 B 7 At parameter 788 check with a reading test if the answer is 8 8 Connect the bus C of the module A If the module is the last element of the netwo...

Страница 60: ...ss 1 34 Baud Rate Baud Rate 0 4800 1 9600 2 19200 1 35 Parity Parity 0 NO 1 Odd 2 Even supervision serial 0 Return to main menu Scroll up Scroll down Confirm How to modify the parameters of PARAMETER LIST menu 2 Select Log User 1 initial screen 3 Confirm 4 Enter password 5 Confirm password 6 Select menu 7 Confirm 8 Select parameter 9 Confirm 10 Modify parameter 11 Confirm 12 Main menu twice X For ...

Страница 61: ...pe of system name of the climatic areas kitchen living room etc mixed and not mixed circuits units installed which and how many heat pumps terminals etc modules installed input output modules single modules etc number of hydraulic circuits booster pumps area valve combining components with the areas 1 2 select 1 select 2 3 select 3 4 select 4 ...

Страница 62: ...EM COMPONENT CONFIGURATION Create modify areas new modify remove select 5 5 Capital or small letters Use the keyboard to type the name of the area Key functions Numbers Space Delete 6 select 6 7 select 7 8 select 8 ...

Страница 63: ...ible combinations with boosters STD booster area 1 high temperature only optional boosters 2 areas high temperature only 2 areas one high temperature one low temperature 3 areas high temperature only 3 areas two high temperature one low temperature 3 areas one high temperature two low temperature 4 areas high temperature only 4 areas three high temperature one low temperature 4 areas two high temp...

Страница 64: ...nfigure the outputs to control the following functions activation of the circulator it activates when the hydraulic circuit combined with the circulator is requested area valve control it activates when the hydraulic circuit combined with area valve is requested seasonal control it closes the system when it is in heating mode whilst when in cooling mode it opens it If the system is provided with a...

Страница 65: ...ilable define the type of controlled component for each channel single step radiant panel double step radiant panel triple step radiant panel radiator fan coil with electro mechanical thermostat radiator with electro mechanical thermostat radiant panel with electro mechanical thermostat not used Belonging area kitchen living room etc Type of circuit assigned mixed non mixed Number of circuit mixed...

Страница 66: ...terminal of reference NONE Component 2 DAY area thermostat YES terminal of reference 1 Component 3 DAY area thermostat YES terminal of reference 1 Component 4 NIGHT area thermostat YES terminal of reference NONE Component 5 DAY area thermostat NO terminal of reference 4 21 end of the configuration DAY NIGHT select 22 end of the configuration 22 Select mix module controlled by the thermostat assign...

Страница 67: ...TOCONFIGURATION select 2 select 3 2 21 1 select 1 3 Check of the auto configuration procedure end Autoconfiguration completed For make the autoconfiguration changes effective turn off and on the power TO MODULES ...

Страница 68: ...Page 68 AUTOCONFIGURATION If you do not see Autoconfiguration completed 1 check the element is in ON 2 check the network ...

Страница 69: ...st restart this period can vary depending on the composition of the system select 2 select 3 Communication OK 1 select 1 2 A Belonging to area 4 B Terminal number 2 The unit does not communicate with ELFOControl2 an alarm is notified communication with interrupted device If ELFOControl2 does not communicate with Ethernet 485 converter an alarm communication interrupted with all the devices is noti...

Страница 70: ...d mixing circulators Drag area 2 upwards ZONE ELEMENTS STATUS Check of the installed radiant fancoil zone modules operation status For reference only A Status on off B Heating cooling C Ambient setpoint C D Air temperature C E Ambient humidity F Water temperature C G Remote control H Configuration I Zone J Dew temperature C To see all the components drag area 1 to the left ...

Страница 71: ...er temperature C E Return water temperature C F Air temperature C G Ambient humidity H Valve opening I Dew temperature C J Configuration H I j A B C D E F G select 8 6 Access to the parameters is reserved only to After Sales Centre 7 8 Version firmware vx xxx FIRMWARE It is possible to Check the firmware version Update the firmware operation exclusively reserved ATC ...

Страница 72: ...Page 72 SYSTEM COMPONENT STATUS 1 select 1 2 select 2 Company Confirm Company Confirm the modification You can insert the contact references ...

Страница 73: ...T ALWAYS BE DELIVERED TO AUTHORISED CENTRES All materials must be recovered or disposed or in compliance with the relative national standards in force For further information on the dismissal of the unit contact the manufacturing company The units falling within the standard in question are marked with the symbol at the side With a view of respecting the environment our units are manufactured in a...

Страница 74: ...ameter Value Description 1129 130 2 Enablement of the modbus ambient probe always set to 2 1160 161 0 Select the supervision mode 1137 138 2 Enablement of UR ambient probe from Elfocontrol 2 Mixing module Modbus Parameter Value Description 1077 78 Enables compensation for dew in cooling mode 0 deactivate 1 activate 1084 85 90 sec Time required to position VRad from closed to fully open 1085 86 400...

Страница 75: ...on between EC2 and Sten The DHCP client is not active do not enable it Currently Sten only accepts commands modbus 03 in reading and 16 in writing Address Description Notes 1 Plant status 1 off 2 on 2 Plant mode 1 cooling 2 heating 3 Heat pump mode 1 PDC disabled 2 only dmestic hot water DHW 3 auto mode 4 DHW mode 1 ACS disabled 2 solar only 3 auxiliary heater only 4 auto mode 5 Away function 1 aw...

Страница 76: ...s Description Notes Limits 110 Setpoint reload DHW 25 C 55 C 111 Setpoint maintenance DHW 25 C 55 C 112 DHW profile 1 Maintenance recirculation 2 Maintenance 3 recirculation recharge 4 recharge ElfoFresh commands For each ElfoFresh EF areas you can set the commands listed in the table below There are 5 records for each ElfoFresh first record EF 1 115 EF 2 120 EF 3 125 EF 4 130 Address Description ...

Страница 77: ...ntenance 3 recirculation recharge 4 recharge 203 Solar temperature 204 Solar status 0 disable 1 active 205 Heat pump DHW pump Recirculation 0 disable 1 active 206 RHeater DHW boiler 0 disable 1 active 207 Antilegionella 0 not in progress 1 in progress ElfoFresh EF stata For each ElfoFresh EF you can read the data listed in the table below There are 9 records for each ElfoFresh First record EF 1 21...

Страница 78: ......

Страница 79: ......

Страница 80: ... 0 1489 572238 Fax 44 0 1489 573033 info clivet uk co uk CLIVET NEDERLAND B V Siliciumweg 20a 3812 SX Amersfoort Netherlands Tel 31 0 33 7503420 Fax 31 0 33 7503424 info clivet nl CLIVET GmbH Hummelsbütteler Steindamm 84 22851 Norderstedt Germany Tel 49 0 40 32 59 57 0 Fax 49 0 40 32 59 57 194 info de clivet com CLIVET RUSSIA Elektrozavodskaya st 24 office 509 107023 Moscow Russia Tel 74956462009 ...