SYSTEM COMPONENT ADDRESSING
RS485
230V
1 2
3 4
13 14 15 16 17 18 19 20 21 22 23 24
8 9
1 2 3 4 5
6 7
11 12
+
-
230V
1 2
3 4
13 14 15 16 17 18 19 20 21 22 23 24
8 9
1 2 3 4 5
6 7
11 12
+
-
C
*
A
Module addressing
To carry out the addressing, connect to bus only 1 module at a time.
1.
Set the system and put it into communication with all devices
2.
Disconnect bus (
C
) of module
A
3.
Access to the parameter scripture mask via modbus (see sideway)
4.
Point the IO module provisionally addressed at 7 (
B
)
5.
At parameter 788 of module write 8
6.
Point the IO module just addressed at 8 (
B
)
7.
At parameter 788 check with a reading test, if the answer is 8
8.
Connect the bus (
C
) of the module
A
*
If the module is the last element of the network connect a termination
resistance 120
Ω
1/4 W ( customer care)
B
3
select
3
4
select
4
select
2
1
select
1
2
I/O MODULE