Page 51
SYSTEM COMPONENT ADDRESSING
TERMINALS, AREAS MODULES WITH HID-T2, HID-T3 THERMOSTATS
Parameters to be modified
Parameter
Mnemonic
Name
Description
Value
33 Index
Device
address
17,18....
34 Baud
Rate
Baud Rate 0=4800 1 :9600
2 :19200
1
35 Parity
Parity 0=NO / 1=Odd 2=Even
supervision serial
0
HID-T2 Temperature / HID-T3 Temp. + humidity
1
Switch off and on the thermostat using the ON/OFF key and wait for the set point
2
Within 5 seconds, press the keys until P00 is displayed
S
w
in
g
P00
3
Press
E
co
4
Enter password 321
321
5
Confirm password
E
co
6
Access parameter 33
P33
7
Access the value range
E
co
XY
8
Edit value as indicated in the table
17
9
Confirm the value entered
E
co
10
Repeat the sequence for the other parameters indicated in the table
11
Press the keys until the word OFF is displayed on the thermostat
S
w
in
g
OFF
First address the area modules combining them with the lowest addresses (example area module 17 - terminals 18 ............)
If the number of fa area modules in the system is greater than 33, use addresses 60, 61, etc.