Pagina 77
Area stata
For each areas you can read the data listed in the table below. There are 4 records for each area:
First area : area 1 => 150, area 2 => 154, area 3 => 158,…, area 12 => 194
Address
Description
Notes
150
Average temperature area 1
151
Average umidity area 1
152
Profile area 1
1 = off, 2 = area on eco mode, 3 = area on comfort mode
153
Setpoint area 1
Domestic hot water
Address
Description
Notes
200
DHW temperature
201
DHW second temperature
202 DHW
profile
1 = Maint recirculation, 2 = Maintenance,
3 = recirc recharge, 4 = recharge
203
Solar temperature
204
Solar status
0 = disable, 1 = active
205
Heat pump DHW pump/ Recirculation
0 = disable, 1 = active
206
RHeater /DHW boiler
0 = disable, 1 = active
207
Antilegionella
0 = not in progress, 1 = in progress
ElfoFresh (EF) stata
For each ElfoFresh (EF) you can read the data listed in the table below. There are 9 records for each ElfoFresh:
First record : EF 1 => 210, EF 2 => 219, EF 3 => 228, EF 4 => 237
Address
Description
Notes
210
Supply temperature
211
Return temperature
212
Room humidity
213
Outdoor temperature
214
Room Setpoint
215
Status
0 = off, 1 = on
216
Compressor
0 = off, 1 = on
217
Dehumidify
0 = not in progress, 1 = In progress
218
Alarm
0 = not on alarm, 1 = alarm