Page 13
HEAT PUMP
MODIFY THE OUTDOOR TEMPERATURE:
5 - select
6 - Set the required values:
Max 35°C
Min.
22°C
MODIFICATION OF 4 POINTS
7 - Modify the correction
5
6
7
Confirm the modification
8 - Modify the correction
example: + 2°C
8
The correction can be used to modify the climatic curve rapidly,
without modifying the 4 set points.
Example:
Outdoor air = 35°C supply water set point = 7°C
Outdoor air = 22°C supply water set point = 15°C
Corr 2°C in Summer
Values after the correction:
Outdoor air = 35°C supply water set point = 7+2 = 9°C
Outdoor air = 22°C supply water set point = 15+2 = 17°C
When correction is active the symbol (9) is displayed
For the
winter
correction, follow the same procedure.
select
5
select
7