Pagina 76
Areas commands
For each areas you can set the commands listed in the table below. There are 7 records for each areas:
first record : area 1 => 10, area 2 => 17, area 3 => 24,…, area 12 => 87
Note: If mode area = 0, The area will follow the local programming set to EC2 (Or any area mode manual forcing)
Address
Description
Notes
Limits
10
Winter comfort Setpoint area 1
8.0°C…35.0°C
11
Summer comfort setpoint area 1
8.0°C…35.0°C
12
Delta winter setpoint eco area 1
Positive value. In Eco mode will be subtracted from the comfort Setpoint
0.1°C…15.0°C
13
Delta summer setpoint eco area 1
Positive value. In Eco mode will be added to the comfort Setpoint
0.1°C…15.0°C
14
Area 1mode
1 = area off, 2 = area Eco, 3 = area comfort
15
Winter humidity Setpoint area 1
10%...90%
16
Summer humidity Setpoint area 1
10%...90%
Domestic Hot Water commands
Address
Description
Notes
Limits
110
Setpoint reload DHW
25°C…55°C
111
Setpoint maintenance DHW
25°C…55°C
112 DHW
profile
1 = Maint recirculation, 2 = Maintenance,
3 = recirc recharge, 4 = recharge
ElfoFresh commands
For each ElfoFresh (EF) areas you can set the commands listed in the table below. There are 5 records for each ElfoFresh:
first record : EF 1 => 115, EF 2 => 120, EF 3 => 125, EF 4 => 130
Address
Description
Notes
Limits
115
Winter Setpoint room temperature
18.0°C…26.0°C
116
Summer Setpoint room temperature
22.0°C…28.0°C
117
Winter room humidity Setpoint
5%…80%
118
Summer room humidity Setpoint
45%…100%
119
Functionnning mode
1 = EF disabled, 2 = EF fan mode only, 3 = auto mode
Status record (read only)
Plant stata
Address
Description
Notes
140
Plant status
1 = off, 2 = on
141
Plant mode
1 = cooling, 2 = heating
142
Heat pump status
0 = off(or standby), 1 = plant, 2 = DHW
143 Outdoor
temperature
144
heat pump alarm
0 = not alarm, 1 = alarm
145
Heat pump supply temperature
146
Compressor heat pump power
0…100% (in decimi di %)
147
heat pump working Setpoint