159
Maximum condensation override differential in the chiller mode
3.0
bar
0.1
5.0
160
Enable maximum condensation override in the heat pump mode (0:No - 1:Yes)
0
-
161
Maximum condensation override setpoint in the heat pump mode
1.0
bar
0.5
15.0
162
Maximum condensation override differential in the heat pump mode
0.5
bar
0.1
5.0
163
Step 1 setpoint in chiller mode
15.0
bar
0.5
P253
164
Step 1 differential in chiller mode
3.0
bar
0.1
5.0
165
Step 2 setpoint in chiller mode
16.5
bar
0.5
P253
166
Step 2 differential in chiller mode
3.0
bar
0.1
5.0
Step 3 setpoint in chiller mode
18.0
bar
0.5
P253
168
Step 3 differential in chiller mode
3.0
bar
0.1
5.0
169
Step 4 setpoint in chiller mode
19.0
bar
0.5
P253
170
Step 4 differential in chiller mode
2.0
bar
0.1
5.0
171
Step 1 setpoint in heat pump mode
8.0
bar
0.5
15.0
172
Step 1 differential in heat pump mode
1.0
bar
0.1
5.0
173
Step 2 setpoint in heat pump mode
5.0
bar
0.5 15.0
174
Step 2 differential in heat pump mode
1.4
bar
0.1
5.0
175
Step 3 setpoint in heat pump mode
2.2
bar
0.5
15.0
176
Step 3 differential in heat pump mode
0.8
bar
0.1
5.0
177
Step 4 setpoint in heat pump mode
1.0
bar
0.5
15.0
178
Step 4 differential in heat pump mode
0.5
bar
0.1
5.0
179
Continuous adjustment setpoint in the chiller mode
14.0
bar
5.0
P253
180
Continuous adjustment differential in the chiller mode
5.0
bar
0.1
15.0
Continuous adjustment setpoint in the heat pump mode
6.0
bar
0.5
15.0
182
Continuous adjustment differential in the heat pump mode
1.0
bar
0.1
15.0
183
Maximum condensation limit in continuous adjustment
100
%
P184
100
184
Minimum condensation limit in continuous adjustment
30
%
0
P183
185
Adjustment under the minimum condensation limit (0:adjustment always-
1:adjustment Off)
1
-
186
Condensation adjustment off differential
1.0
bar
0.0 5.0
187
Temperature difference for activating freecooling
1.0
°C
1.0
5.0
188
Temperature offset for deactivating freecooling
-9.0
°C
-10.0
P921
189
Temperature delta for deactivating freecooling
1.0
°C
0.1
P922
190
Type of freecooling valve control (0:direct - 1:reverse)
0
-
191
Hysteresis temperature of individual fans
0.3
°C
0.0
1.0
192
Start/stop delay for each fan
20
s
1
500
193
Defrost type (0:standard - 1:Timer Tuning - 2:Timer Auto Tuning)
0
-
0
2
194
Start defrost setpoint
3.0
bar
0.0
P195
195
Stop defrost setpoint
14.0
bar
P194
P253
196
Defrost activation delay
1800
s
60
3600
197
Maximum defrost time
300
s
10
500
198
Drip time
120
0 500
s
199
Defrost delay increase differential
30
s
0 P927
200
Defrost delay decrease differential
60
s
1
P928
201
Defrost delay increase/decrease percentage
20
s
0
100
202
Maximum number of defrosts per hour
3
-
1
9
203
Calculation interval of the difference between external temperature and
evaporation temperature
300
s
600
10
204
Maximum difference between external temperature and evaporation temperature
3.0
°C
0.1
9.9
205
Temperature threshold for changing defrost delay
15.0
°C
12.0
20.0
206
Variation threshold offset
2.0
°C
0.5
9.9
207
Reduction factor in defrost delay
5
%
0
99
208
Bypass time from start of circuits for calculating the reduction in the defrost delay
120
s
0
999
209
Start variation delay
600
s
0
999
210
Minimum derived evaporation pressure
-0.1
bar/m
-10.0
10.0
211
Forced defrosting with low pressure (0:disabled - 1:enabled)
0
-
167
181
71