C0240111-04-05-GB
6)
Configure keyboard 21 (previously set) as Pr=private (usually
the one on the unit), Sp=printer or Sh=shared
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 None --
Trm3 None -- Ok?No
7)
The remote keyboard must also be configured. Simply define
the keyboard addressed with 32 (even if not present) as Sh.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?No
8)
To save the settings and exit the configuration procedure,
move the cursor to “No”, change it to “Yes” and press [ENTER].
To exit without saving the settings, wait 30 seconds without
touching the keyboard.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?Yes
9)
The following mask may appear. If no expansions are
connected, simply press [ESC] to show the main display menu.
#####################
expansion
connection ……
#####################
To connect several units together and remote control them, thereby forming a plan network (global),
connect a remote keyboard controlling all the plans (local).
The remove keyboard cannot be used with a W3000 base keyboard. If a W3000 keyboard is fitted to the
unit, change it with a W3000 or W3000 compact.
x
CONFIGURING THE PLAN NETWORK (global):
It is easy to install a PLAN network (global). Just a few but essential operations are required. If just one
of these is not performed correctly, the entire system will not work.
The remote keyboard will work problem-free if the following operations are performed one after the
other.
1 ) Set the on-board machine card and
keyboard addresses (see configuring the
local plan network)
Leaving the network cable disconnected.
configure the terminals on each card and
keyboard (then connect the remote keyboard).
2 ) Check the chillers work correctly without
being connected to the network.
3 ) Disconnect the power supply from the
chillers
4 ) Connect all the chillers to the network
except for the remote keyboard.
Connect connectors J11 together.
Do not connect
the remote keyboard
!!!
5 ) Power the chillers.
6 ) Check that all the networked devices work
correctly
If any faults occur, check the configuration of the
terminals to make sure that no two devices have
the same address.
7 ) Connect the remote keyboard to one of the
units (see below: connecting the remote
keyboard)
If the converter is fitted (see below: remove
keyboard from 200 to 500 metres away), make
sure the remote keyboard is powered.
8 ) Make sure the remote keyboard address is
set to 32.
Follow the procedure for addressing the remote
keyboard.
9 ) Make sure that the devices outside the
chillers are correctly configured.
Make sure that no two components of the
network share the same address (to avoid
conflicts)
10) Wait a few seconds until network
communication has stabilised.
17