C0240111-04-05-GB
3.4 Configuring the terminals
The first operation to perform when a network is started up for the first time or an I/O card is replaced, is
to activate the procedure for terminal configuration.
This cannot be done with W3000 base. In this case, configure the terminals with a W3000 or W3000
compact terminal and then replace the display with a W3000 base.
Before starting this procedure it is advisable to check that each I/O card and each terminal has been
identified with the correct address established when the network was designed. It is important to
remember that the address set with the dip-switches or software configuration is only received if the
device is reset.
RESET
the device by disconnecting the power supply. Moreover, it is advisable to perform
global resetting of all network devices if a mistake has been made in the configuration of the addresses
(more than one card with the same address).
The configuration procedure can be activated from any terminal (keyboard), which may also be
connected temporarily only to perform configuration operations and removed upon completion. The
operations to perform are described in the following paragraphs.
3.4.1 SETTING THE KEYBOARD ADDRESS
After connecting the keyboard to the device (using two cables for W3000 and just one cable for W3000-
compact ) perform the following procedure:
1)
Press [UP], [DOWN] and [ENTER] together and hold down until
the mask shown to the side appears.
Display address
Setting..........:00
I/O Card address:
2)
Press [ENTER] to set the required keyboard address (e.g.: 21 )
using [UP] and [DOWN]
Display address
Setting..........:21
I/O Card address:--
3)
This mask means that the address of the keyboard has been
set.
Display address
changed
4)
If an empty mask appears, instead, it means that the keyboard
is not communicating with any card. Either the card must be
addressed or the plan network must be configured.
N.B.: This is a
timed procedure
; if the parameters are not set within a few seconds, the display turns off.
In this case, the operation must be repeated.
3.4.2 “S”, “M” AND “B” CARD SETTINGS
In “S”, “M” or “B” cards the card address is set by the software using the keyboard.
Proceed as follows:
1)
Make sure the keyboard address is set to 0 ( see para 3.4.1).
2)
Disconnect the card from the power supply (turn off the
general switch).
3)
Power the card and press [ALARM] and [UP]
together
; hold
the keys down until the mask shown to the side appears.
pLan address: 0
UP: increase
DOWN: decrease
ENTER: save & exit
14
Содержание W3000 compact
Страница 7: ...C0240111 04 05 GB 7 W3000 W3000 UNIT XL UNIT B...
Страница 8: ...C0240111 04 05 GB W3000 EXPANSION E 8...
Страница 12: ...C0240111 04 05 GB Figure 3 3 mixed connection 12...