C0240111-04-05-GB
Dig.Out. slave exp3
12345 67890 12345
AAAAA AAAAA AAAAA
AAAAA AAAAA AAAA
Displays the state of the digital outputs of expansion 3 (if present) and specifies
their state.
C: Contact closed
O: Contact open
An. In. slave exp3
N° Value
1 06.0 °C
2 00.0 °C
Displays analogue inputs 1 and 2 of expansion 3 (if present).
An. In. slave exp3
N° Value
3 00.0 °C
4 00.0 °C
Displays analogue inputs 3 and 4 of expansion 3 (if present).
An. Out. slave exp3
N° Value
1 00.0 V
Voltage applied to analogue output 1 of expansion 3 (if present).
Dig.In. slave exp4
12345 67890 12345
CCCCC CCCCC CCCCC
CCC
Displays the state of the digital inputs of expansion 4 (if present) and specifies
their state.
C: Contact closed
O: Contact open
Dig.Out. slave exp4
12345 67890 12345
AAAAA AAAAA AAAAA
AAAAA AAAAA AAAA
Displays the state of the digital outputs of expansion 4 (if present) and specifies
their state.
C: Contact closed
O: Contact open
An. In. slave exp4
N° Value
1 A
2 A
Displays analogue inputs 1 and 2 of expansion 4 (if present).
An. In. slave exp4
N° Value
3 A
4 A
Displays analogue inputs 3 and 4 of expansion 4 (if present).
Dig.In. slave exp5
12345 67890 12345
CCCCC CCCCC CCCCC
CCC
Displays the state of the digital inputs of expansion 5 (if present) and specifies
their state.
C: Contact closed
O: Contact open
Dig.Out. slave exp5
12345 67890 12345
AAAAA AAAAA AAAAA
AAAAA AAAAA AAAA
Displays the state of the digital outputs of expansion 5 (if present) and specifies
their state.
C: Contact closed
O: Contact open
An. In. slave exp5
N° Value
1 00.0 °C
2 00.0 °C
Displays analogue inputs 1 and 2 of expansion 5 (if present).
An. In. slave exp5
N° Value
3 00.0 °C
4 00.0 °C
Displays analogue inputs 3 and 4 of expansion 5 (if present).
Setpoint
m
p
Access mask to setpoint menu. Press "Up" or "Down" to scroll the other masks
and "Esc" to return to the submenu.
Unit type:
chiller
Operating mode:
chiller
Mask for displaying the unit type and setting the operating mode.
409
Active Setpoint:
Main 07.0 °C
Recovery 42.5 °C
Displays the current setpoint. If the letter R appears in the top right-hand corner,
the active setpoint is the secondary one.
Chiller setpoint
07.0 °C
Heatpump setpoint
42.5 °C
Sets the chiller and heat pump setpoint for inlet adjustment.
410
411
412
Chiller setpoint
11.0 °C
Heatpump setpoint
45.0 °C
Sets the chiller and heat pump setpoint for outlet adjustment.
413
414
Secondary chiller
setpoint 07.0 °C
Secondary heatpump
setpoint 45.0 °C
Sets the secondary setpoint (only displayed if the secondary setpoint is enabled).
415
416
Recovery setpoint
42.5 °C
Sets the recovery setpoint (only displayed if recovery is enabled).
417
59