ClimateMaster TRC09 Series Скачать руководство пользователя страница 33

T H E   S M A R T   S O L U T I O N   F O R   E N E R G Y   E F F I C I E N C Y

Consoles

R e v. :   0 8 / 2 4 / 1 5

33

c l i m a t e m a s t e r. c o m

Unit Start-Up Procedure

Unit Start-up Procedure

1.  Turn the thermostat fan position to “ON”. Blower 

should start.

2.  Balance air fl ow at registers.
3.  Adjust all valves to their full open positions. Turn on 

the line power to all heat pumps.

4.  Room temperature should be within the minimum-

maximum ranges of table 8. During start-up checks, 
loop water temperature entering the heat pump 
should be between 60°F [16°C] and 95°F [35°C].

5.  Two factors determine the operating limits of 

ClimateMaster heat pumps, (a) return air temperature, 
and (b) water temperature. When any one of these 
factors is at a minimum or maximum level, the other 
factor must be at normal level to insure proper unit 
operation.

a. 

 Adjust the unit thermostat to the warmest 
setting. Place the thermostat mode switch in the 
“COOL” position.  Slowly reduce thermostat 
setting until the compressor activates.

b. 

Check for cool air delivery at the unit grille 
within a few minutes after the unit has begun to 
operate.

  Note: Units have a fi ve minute time delay in the 

control circuit that can be eliminated on the CXM/
DXM control board as shown below in Figure 8. See 
controls description for details.

c. 

Check the elevation and cleanliness of the 
condensate lines. Dripping may be a sign of a 
blocked line. Check that the condensate trap is 
fi lled to provide a water seal.

d. 

Refer to Table 9. Check the temperature of 
both entering and leaving water. If temperature 
is within range, proceed with the test. If 
temperature is outside of the operating range, 
check refrigerant pressures.

e. 

Check air temperature drop across the air coil 
when compressor is operating. Air temperature 
drop should be between 15°F and 25°F [8°C 
and 14°C].

f. 

 Turn thermostat to “OFF” position. A hissing 
noise indicates proper functioning of the 
reversing valve.

6. Allow fi ve (5) minutes between tests for pressure to 

equalize before beginning heating test.

a. 

 Adjust the thermostat to the lowest setting. 
Place the thermostat mode switch in the 
“HEAT” position.

b. 

Slowly raise the thermostat to a higher 
temperature until the compressor activates.

c. 

Check for warm air delivery within a few minutes 
after the unit has begun to operate.

d. 

 Refer to Table 9. Check the temperature of 
both entering and leaving water. If temperature 
is within range, proceed with the test. If 
temperature is outside of the operating range, 
check refrigerant pressures.

e. 

Check air temperature rise across the air coil 
when compressor is operating. Air temperature 
rise should be between 20°F and 30°F [11°C 
and 17°C]. 

f. 

Check for vibration, noise, and water leaks.

7.  If unit fails to operate, perform troubleshooting 

analysis (see troubleshooting section). If the check 
described fails to reveal the problem and the unit 
still does not operate, contact a trained service 
technician to insure proper diagnosis and repair of the 
equipment.

8.  When testing is complete, set system to maintain 

desired comfort level.

9.  BE CERTAIN TO FILL OUT AND FORWARD 

ALL WARRANTY REGISTRATION PAPERS TO 
CLIMATEMASTER.

Note: If performance during any mode appears 
abnormal, refer to the CXM/DXM section or 
troubleshooting section of this manual. To obtain 
maximum performance, the air coil should be cleaned 
before start-up. A 10% solution of dishwasher 
detergent and water is recommended.

WARNING!  

When the disconnect switch is closed, high 

voltage is present in some areas of the electrical panel. 
Exercise caution when working with energized equipment.

CAUTION! 

Verify that ALL water control valves are open and 

allow water fl ow prior to engaging the compressor. Freezing 
of the coax or water lines can permanently damage the heat 
pump.

Short test pins together to enter 
Test Mode and speed-up timing 
and delays for 20 minutes.

Figure 8: Test Mode Pins

LT1
LT2

 

WARNING

 

 

CAUTION!

 

Содержание TRC09 Series

Страница 1: ...pplications 14 Ground Loop Heat Pump Applications 15 Ground Water Heat Pump Applications 16 Water Quality Standards 18 Electrical Line Voltage 19 Electrical Low Voltage 22 TRC Series Wiring Diagram Ma...

Страница 2: ...CLIMATEMA STE R WATE R S OURCE H E A T P UMP S Consoles Rev 08 24 15 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...oil w Extended Range Insulation 1 2 3 S Standard None S F M Motorized Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valv...

Страница 4: ...RCUIT OPTIONS 09 12 15 18 SERIES UNIT SIZE Size TRC06 TRC09 TRC12 TRC15 TRC18 1 5 2 0 2 5 3 0 3 5 0 095 0 126 0 158 0 189 0 221 2 0 2 5 3 0 3 5 4 0 0 126 0 158 0 189 0 221 0 252 US GPM LPS US GPM LPS...

Страница 5: ...and notices appear throughout this manual Read these items carefully before attempting any installation service or troubleshooting of the equipment DANGER Indicates an immediate hazardous situation w...

Страница 6: ...tem components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is design...

Страница 7: ...6 203 x 660 10 x 26 254 x 660 10 x 32 254 x 812 Filter Size Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 36 x 1 254 x 914 x 25 Front Return In mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5...

Страница 8: ...mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5 x 1 8 178 x 902 x 3 2 Cabinet Size Bottom Return Std 5 127 Base W x H x D In mm 48 x 26 x 12 1219 x 660 x 305 54 x 26 x 12 1372 x 660 x 305 Front Return...

Страница 9: ...e for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted with swivel joint fittings at one end...

Страница 10: ...correctly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause block...

Страница 11: ...DWHU RQQHFWLRQV 2 RSSHU 37 RU 037 8 00 Min 203 11 25 286 1 62 41 2 00 51 2 25 57 HIW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 RQGHQVDWH FWLRQV 2 25 57 Q 2...

Страница 12: ...UDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 5LJKW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW RPSUHVVRU FFHVV 3DQHO RQWURO R 1 84 47 RQGHQVDWH RQGHQVDWH 9LQ O RVH 2SWLRQD 0RWRUL D...

Страница 13: ...freeze is used in the loop insure that it is compatible with the Teflon tape or pipe joint compound that is applied Maximum allowable torque for brass fittings is 30 ft lbs 41 N m If a torque wrench i...

Страница 14: ...rop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to op...

Страница 15: ...le free ground loops These instructions are recommendations only State provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes It is the responsibility of the...

Страница 16: ...or return water piping with water source heat pump products containing HFC 410A as system failures and property damage may result WARNING Use the appropriate scaling surface temperature for the appli...

Страница 17: ...t pumps from the ground water and confine heat exchanger cleanings to one location and lessen maintenance Direct use of ground water may increase the frequency of heat pump maintenance and may shorten...

Страница 18: ...NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maxim...

Страница 19: ...wer supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed to accept ot...

Страница 20: ...5 10 0 12 4 20 11 5 13 8 20 G 208 230 60 1 197 254 1 4 7 25 0 0 6 5 3 6 5 15 5 7 7 3 15 E 265 60 1 239 292 1 4 2 22 0 0 4 4 6 5 7 15 5 4 6 5 15 TRC15 G 208 230 60 1 197 254 1 5 6 30 0 0 8 6 4 7 8 15 7...

Страница 21: ...ield installed B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the powe...

Страница 22: ...flash U1 press up arrow and screen will change to U2 flashing Press and release mode button and on will flash To turn off push down arrow push up arrow to get back to on Press fan button to escape Fig...

Страница 23: ...ed it has the correct number of heating and cooling stages Zone integrity must be maintained to efficiently control units or groups of units Unless zones of control are considered and accounted for ad...

Страница 24: ...R410A 96B0292N03 LON ETL R410A 96B0292N04 MPC ETL R410A 96B0293N01 115 60 1 208 230 60 1 265 60 1 DXM ACO MCO ETL R410A 96B0293N02 REM ETL R410A 96B0293N03 LON ETL R410A 96B0293N04 MPC ETL R410A 96B0...

Страница 25: ...onnection DIP Switches Note In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable p...

Страница 26: ...rying Field Configuration Options Note In the following field configuration options jumper wires should be clipped ONLY when power is removed from the DXM control Water coil low temperature limit sett...

Страница 27: ...tings On Stage 1 Off Stage 2 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is th...

Страница 28: ...se 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the l...

Страница 29: ...ill flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM CONTROLS Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM con...

Страница 30: ...IT ENTERING WATER MIN MAX 40 120 4 5 49 60 90 16 43 EXTENDED RANGE UNIT ENTERING WATER MIN MAX 30 120 1 49 20 90 6 7 32 Requires optional insulation package when operating below the dew point Requires...

Страница 31: ...ther equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period shut off the circul...

Страница 32: ...oper pH promotes longevity of hoses and fittings see Table 3 System flushing Verify that all hoses are connected end to end when flushing to insure that debris bypasses the unit heat exchanger water v...

Страница 33: ...noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to the lowest setting Plac...

Страница 34: ...10 6 12 6 6 9 8 9 17 23 17 23 17 23 TRC12 Full Load Cooling Full Load Heating Entering Water Temp F Water Flow GPM Ton Suction Pressure PSIG Discharge Pressure PSIG Super heat Sub cooling Water Temp...

Страница 35: ...36 90 2 1 3 15 4 2 138 148 138 148 138 148 366 386 353 373 340 360 9 14 9 14 9 14 11 16 9 14 6 11 15 8 17 8 14 9 16 9 14 16 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 18 2...

Страница 36: ...g checks and data entries before the system is put into full operation Temperatures F or C Antifreeze __________________ Pressures PSIG or kPa Type __________________ Cooling Mode Heating Mode Return...

Страница 37: ...nditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan moto...

Страница 38: ...lope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flow Find a...

Страница 39: ...strictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjust to proper flow rate X...

Страница 40: ...5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 2...

Страница 41: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or repla...

Страница 42: ...nce as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or unrealized savings in sam...

Страница 43: ...TH E SMA RT SO LUT I ON FOR E NE RG Y E FFI CIENCY Consoles Rev 0 8 24 1 5 43 climatemaster com Notes...

Страница 44: ...ing Conditions 12 02 08 TRC CCE Wiring Diagrams Consolidated 12 02 08 TRC Piping Connection Diagrams Added 09 09 08 Pressure Testing Note Updated 06 30 08 Shut Off Valve Note Added to Piping Connectio...

Отзывы: