DIP Package #2 (S2) -

 DIP Package #2 has 8 switches and 

provides the following setup selections:

2.1 -

 Accessory1 relay personality: DIP 2.1 provides 

selection of ACC1 relay personality (relay operation/
characteristics). See table 5c for description of 
functionality. 

2.2 - 

Accessory1 relay personality: DIP 2.2 provides 

selection of ACC 1 relay personality (relay operation/
characteristics). See table 5c for description of 
functionality.

2.3 -

 Accessory1 relay personality: DIP 2.3 provides 

selection of ACC 1 relay options. See table 5c for 
description of functionality.

2.4 

- Accessory2 relay personality: DIP 2.4 provides 

selection of ACC 2 relay personality (relay operation/
characteristics). See table5c for description of functionality. 

2.5 -

 Accessory2 relay personality: DIP 2.5 provides 

selection of ACC 2 relay personality (relay operation/
characteristics). See table 5c for description of 
functionality.

2.6 -

 Accessory2 relay personality: DIP 2.6 provides 

selection of ACC 2 relay options. See table 5c for 
description of functionality.

2.7 -

 Auto dehumidifi cation fan mode or high fan mode: 

DIP 2.7 provides selection of auto dehumidifi cation fan 
mode or high fan mode. In auto dehumidifi cation mode, 
the fan speed relay will remain off during cooling stage 2 
IF the H input is active. In high fan mode, the fan enable 
and fan speed relays will turn on when the H input is 
active.
On = Auto dehumidifi cation mode. Off = High fan mode.

2.8 -

 Special factory selection: DIP 2.8 provides special 

factory selection. Normal position is “On”. Do not change 
selection unless instructed to do so by the factory.

DIP 2.1

DIP 2.2

DIP 2.3

ACC1 Relay Option

On

On

On

Cycle with fan

Off

On

On

Digital NSB

On

Off

On

Water Valve - slow opening

On

On

Off

OAD

Off

Off

Off

Reheat Option - Humidistat

Off

On

Off

Reheat Option - Dehumidistat

DIP 2.4

DIP 2.5

DIP 2.6

ACC2 Relay Option

On

On

On

Cycle with compressor

Off

On

On

Digital NSB

On

Off

On

Water Valve - slow opening

On

On

Off

OAD

All other DIP combinations are invalid

Table 7c: Accessory DIP Switch Settings

On = Stage 1. Off = Stage 2.

1.3 - 

Thermostat type (heat pump or heat/cool): DIP 1.3 

provides selection of thermostat type. Heat pump or 
heat/cool thermostats can be selected. When in heat/
cool mode, Y1 is the input call for cooling stage 1; Y2 is 
the input call for cooling stage 2; W1 is the input call for 
heating stage 1; and O/W2 is the input call for heating 
stage 2. In heat pump mode, Y1 is the input call for 
compressor stage 1; Y2 is the input call for compressor 
stage 2; W1 is the input call for heating stage 3 or 
emergency heat; and O/W2 is the input call for reversing 
valve (heating or cooling, depending upon DIP 1.4).
On = Heat Pump. Off = Heat/Cool.

1.4 -

 Thermostat type (O/B): DIP 1.4 provides selection of 

thermostat type for reversing valve activation. Heat pump 
thermostats with “O” output (reversing valve energized 
for cooling) or “B” output (reversing valve energized for 
heating) can be selected with DIP 1.4. 
On = HP stat with “O” output for cooling. Off = HP stat 
with “B” output for heating.

1.5 -

 Dehumidifi cation mode: DIP 1.5 provides 

selection of normal or dehumidifi cation fan mode. In 
dehumidifi cation mode, the fan speed relay will remain 
off during cooling stage 2. In normal mode, the fan 
speed relay will turn on during cooling stage 2.
On = Normal fan mode. Off = Dehumidifi cation mode.

1.6 -

 DDC output at EH2: DIP 1.6 provides selection for 

DDC operation. If set to “DDC Output at EH2,” the EH2 
terminal will continuously output the last fault code of 
the controller. If set to “EH2 normal,” EH2 will operate as 
standard electric heat output.
On = EH2 Normal. Off = DDC Output at EH2.

1.7 -

 Boilerless operation: DIP 1.7 provides selection of 

boilerless operation. In boilerless mode, the compressor 
is only used for heating when LT1 is above the 
temperature specifi ed by the setting of DIP 1.8. Below 
DIP 1.8 setting, the compressor is not used and the 
control goes into emergency heat mode, staging on EH1 
and EH2 to provide heating. 
On = normal. Off = Boilerless operation.

1.8 -

 Boilerless changeover temperature: DIP 1.8 

provides selection of boilerless changeover temperature 
setpoint. Note that the LT1 thermistor is sensing 
refrigerant temperature between the coaxial heat 
exchanger and the expansion device (TXV). Therefore, 
the 50°F [10°C] setting is not 50°F [10°C] water, but 
approximately 60°F [16°C] EWT.
On = 50°F [10°C]. Off = 40°F [16°C].

Содержание TRC09 Series

Страница 1: ...pplications 14 Ground Loop Heat Pump Applications 15 Ground Water Heat Pump Applications 16 Water Quality Standards 18 Electrical Line Voltage 19 Electrical Low Voltage 22 TRC Series Wiring Diagram Ma...

Страница 2: ...CLIMATEMA STE R WATE R S OURCE H E A T P UMP S Consoles Rev 08 24 15 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...oil w Extended Range Insulation 1 2 3 S Standard None S F M Motorized Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valv...

Страница 4: ...RCUIT OPTIONS 09 12 15 18 SERIES UNIT SIZE Size TRC06 TRC09 TRC12 TRC15 TRC18 1 5 2 0 2 5 3 0 3 5 0 095 0 126 0 158 0 189 0 221 2 0 2 5 3 0 3 5 4 0 0 126 0 158 0 189 0 221 0 252 US GPM LPS US GPM LPS...

Страница 5: ...and notices appear throughout this manual Read these items carefully before attempting any installation service or troubleshooting of the equipment DANGER Indicates an immediate hazardous situation w...

Страница 6: ...tem components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is design...

Страница 7: ...6 203 x 660 10 x 26 254 x 660 10 x 32 254 x 812 Filter Size Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 36 x 1 254 x 914 x 25 Front Return In mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5...

Страница 8: ...mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5 x 1 8 178 x 902 x 3 2 Cabinet Size Bottom Return Std 5 127 Base W x H x D In mm 48 x 26 x 12 1219 x 660 x 305 54 x 26 x 12 1372 x 660 x 305 Front Return...

Страница 9: ...e for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted with swivel joint fittings at one end...

Страница 10: ...correctly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause block...

Страница 11: ...DWHU RQQHFWLRQV 2 RSSHU 37 RU 037 8 00 Min 203 11 25 286 1 62 41 2 00 51 2 25 57 HIW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 RQGHQVDWH FWLRQV 2 25 57 Q 2...

Страница 12: ...UDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 5LJKW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW RPSUHVVRU FFHVV 3DQHO RQWURO R 1 84 47 RQGHQVDWH RQGHQVDWH 9LQ O RVH 2SWLRQD 0RWRUL D...

Страница 13: ...freeze is used in the loop insure that it is compatible with the Teflon tape or pipe joint compound that is applied Maximum allowable torque for brass fittings is 30 ft lbs 41 N m If a torque wrench i...

Страница 14: ...rop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to op...

Страница 15: ...le free ground loops These instructions are recommendations only State provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes It is the responsibility of the...

Страница 16: ...or return water piping with water source heat pump products containing HFC 410A as system failures and property damage may result WARNING Use the appropriate scaling surface temperature for the appli...

Страница 17: ...t pumps from the ground water and confine heat exchanger cleanings to one location and lessen maintenance Direct use of ground water may increase the frequency of heat pump maintenance and may shorten...

Страница 18: ...NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maxim...

Страница 19: ...wer supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed to accept ot...

Страница 20: ...5 10 0 12 4 20 11 5 13 8 20 G 208 230 60 1 197 254 1 4 7 25 0 0 6 5 3 6 5 15 5 7 7 3 15 E 265 60 1 239 292 1 4 2 22 0 0 4 4 6 5 7 15 5 4 6 5 15 TRC15 G 208 230 60 1 197 254 1 5 6 30 0 0 8 6 4 7 8 15 7...

Страница 21: ...ield installed B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the powe...

Страница 22: ...flash U1 press up arrow and screen will change to U2 flashing Press and release mode button and on will flash To turn off push down arrow push up arrow to get back to on Press fan button to escape Fig...

Страница 23: ...ed it has the correct number of heating and cooling stages Zone integrity must be maintained to efficiently control units or groups of units Unless zones of control are considered and accounted for ad...

Страница 24: ...R410A 96B0292N03 LON ETL R410A 96B0292N04 MPC ETL R410A 96B0293N01 115 60 1 208 230 60 1 265 60 1 DXM ACO MCO ETL R410A 96B0293N02 REM ETL R410A 96B0293N03 LON ETL R410A 96B0293N04 MPC ETL R410A 96B0...

Страница 25: ...onnection DIP Switches Note In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable p...

Страница 26: ...rying Field Configuration Options Note In the following field configuration options jumper wires should be clipped ONLY when power is removed from the DXM control Water coil low temperature limit sett...

Страница 27: ...tings On Stage 1 Off Stage 2 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is th...

Страница 28: ...se 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the l...

Страница 29: ...ill flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM CONTROLS Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM con...

Страница 30: ...IT ENTERING WATER MIN MAX 40 120 4 5 49 60 90 16 43 EXTENDED RANGE UNIT ENTERING WATER MIN MAX 30 120 1 49 20 90 6 7 32 Requires optional insulation package when operating below the dew point Requires...

Страница 31: ...ther equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period shut off the circul...

Страница 32: ...oper pH promotes longevity of hoses and fittings see Table 3 System flushing Verify that all hoses are connected end to end when flushing to insure that debris bypasses the unit heat exchanger water v...

Страница 33: ...noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to the lowest setting Plac...

Страница 34: ...10 6 12 6 6 9 8 9 17 23 17 23 17 23 TRC12 Full Load Cooling Full Load Heating Entering Water Temp F Water Flow GPM Ton Suction Pressure PSIG Discharge Pressure PSIG Super heat Sub cooling Water Temp...

Страница 35: ...36 90 2 1 3 15 4 2 138 148 138 148 138 148 366 386 353 373 340 360 9 14 9 14 9 14 11 16 9 14 6 11 15 8 17 8 14 9 16 9 14 16 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 18 2...

Страница 36: ...g checks and data entries before the system is put into full operation Temperatures F or C Antifreeze __________________ Pressures PSIG or kPa Type __________________ Cooling Mode Heating Mode Return...

Страница 37: ...nditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan moto...

Страница 38: ...lope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flow Find a...

Страница 39: ...strictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjust to proper flow rate X...

Страница 40: ...5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 2...

Страница 41: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or repla...

Страница 42: ...nce as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or unrealized savings in sam...

Страница 43: ...TH E SMA RT SO LUT I ON FOR E NE RG Y E FFI CIENCY Consoles Rev 0 8 24 1 5 43 climatemaster com Notes...

Страница 44: ...ing Conditions 12 02 08 TRC CCE Wiring Diagrams Consolidated 12 02 08 TRC Piping Connection Diagrams Added 09 09 08 Pressure Testing Note Updated 06 30 08 Shut Off Valve Note Added to Piping Connectio...

Отзывы: