ClimateMaster TRC09 Series Скачать руководство пользователя страница 16

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

Consoles

R e v. :   0 8 / 2 4 / 1 5

16

C l i m a t e M a s t e r   Wa t e r - S o u rc e   H e a t   P u m p s

Open Loop - Ground Water Systems - 

Shut off valves 

should be included for ease of servicing. Boiler drains or 
other valves should be “tee’d” into the lines to allow acid 
fl ushing of the heat exchanger. Shut off valves should be 
positioned to allow fl ow through the coax via the boiler 
drains without allowing fl ow into the piping system.  
P/T plugs should be used so that pressure drop and 
temperature can be measured. Supply and return water 
piping materials should be limited to copper, PE, or similar 
material. PVC or CPVC should never be used as they are 
incompatible with the POE oils used in HFC-410A products 
and piping system failure and property damage may result.

Water quantity should be plentiful and of good quality. 
Consult table 3 for water quality guidelines. The unit can 
be ordered with either a copper or cupro-nickel water heat 
exchanger. Consult Table 3 for recommendations. Copper 
is recommended for closed loop systems and open 
loop ground water systems that are not high in mineral 
content or corrosiveness. In conditions anticipating heavy 
scale formation or in brackish water, a cupro-nickel heat 
exchanger is recommended. In ground water situations 
where scaling could be heavy or where biological growth 
such as iron bacteria will be present, an open loop system 
is not recommended. Heat exchanger coils may over 
time lose heat exchange capabilities due to build up of 
mineral deposits. Heat exchangers must only be serviced 
by a qualifi ed technician, as acid and special pumping 
equipment is required. Desuperheater coils can likewise 
become scaled and possibly plugged. In areas with 
extremely hard water, the owner should be informed that 
the heat exchanger may require occasional acid fl ushing.  
In some cases, the desuperheater option should not be 
recommended due to hard water conditions and additional 
maintenance required.

Water Quality Standards -

 

Table 3 should be consulted 

for water quality requirements. Scaling potential should 
be assessed using the pH/Calcium hardness method. 
If the pH <7.5 and the calcium hardness is less than 
100 ppm, scaling potential is low. If this method yields 
numbers out of range of those listed, the Ryznar Stability 
and Langelier Saturation indecies should be calculated. 

Ground-Water Heat Pump Applications

WARNING! 

Polyolester Oil, commonly known as POE oil, is 

a synthetic oil used in many refrigeration systems including 
those with HFC-410A refrigerant. POE oil, if it ever comes 
in contact with PVC or CPVC piping, may cause failure of 
the PVC/CPVC. PVC/CPVC piping should never be used 
as supply or return water piping with water source heat 
pump products containing HFC-410A as system failures and 
property damage may result.

 

WARNING!

 

Use the appropriate scaling surface temperature for the 
application, 150°F [66°C] for direct use (well water/open 
loop) and DHW (desuperheater); 90°F [32°F] for indirect 
use. A monitoring plan should be implemented in these 
probable scaling situations. Other water quality issues 
such as iron fouling, corrosion prevention and erosion and 
clogging should be referenced in Table 3.

Expansion Tank and Pump 

-

 Use a closed, bladder-type 

expansion tank to minimize mineral formation due to air 
exposure. The expansion tank should be sized to provide at 
least one minute continuous run time of the pump using its 
drawdown capacity rating to prevent pump short cycling. 
Discharge water from the unit is not contaminated in any 
manner and can be disposed of in various ways, depending 
on local building codes (e.g. recharge well, storm sewer, 
drain fi eld, adjacent stream or pond, etc.). Most local codes 
forbid the use of sanitary sewer for disposal. Consult your 
local building and zoning department to assure compliance 
in your area. 

Water Control Valve - 

Always maintain water pressure in 

the heat exchanger by placing the water control valve(s) 
on the discharge line to prevent mineral precipitation 
during the off-cycle. Pilot operated slow closing valves are 
recommended to reduce water hammer. If water hammer 
persists, a mini-expansion tank can be mounted on the 
piping to help absorb the excess hammer shock. Insure 
that the total ‘VA’ draw of the valve can be supplied by 
the unit transformer. For instance, a slow closing valve 
can draw up to 35VA. This can overload smaller 40 or 
50 VA transformers depending on the other controls in 
the circuit. A typical pilot operated solenoid valve draws 
approximately 15VA..

Flow Regulation -

 

Flow regulation can be accomplished 

by two methods. One method of fl ow regulation involves 
simply adjusting the ball valve or water control valve on 
the discharge line.  Measure the pressure drop through the 
unit heat exchanger, and determine fl ow rate. Since the 
pressure is constantly varying, two pressure gauges may be 
needed. Adjust the valve until the desired fl ow of 1.5 to 2 
gpm per ton [2.0 to 2.6 l/m per kW] is achieved. A second 
method of fl ow control requires a fl ow control device 
mounted on the outlet of the water control valve. The 
device is typically a brass fi tting with an orifi ce of rubber 
or plastic material that is designed to allow a specifi ed 
fl ow rate. On occasion, fl ow control devices may produce 
velocity noise that can be reduced by applying some back 
pressure from the ball valve located on the discharge line. 
Slightly closing the valve will spread the pressure drop over 
both devices, lessening the velocity noise. 

 Note: When 

EWT is below 50°F [10°C], 2 gpm per ton (2.6 l/m per 
kW) is required.

Содержание TRC09 Series

Страница 1: ...pplications 14 Ground Loop Heat Pump Applications 15 Ground Water Heat Pump Applications 16 Water Quality Standards 18 Electrical Line Voltage 19 Electrical Low Voltage 22 TRC Series Wiring Diagram Ma...

Страница 2: ...CLIMATEMA STE R WATE R S OURCE H E A T P UMP S Consoles Rev 08 24 15 2 ClimateMaster Water Source Heat Pumps This Page Intentionally Left Blank...

Страница 3: ...oil w Extended Range Insulation 1 2 3 S Standard None S F M Motorized Water Valve A G N Autoflow 2 25 Gpm Ton B H P Autoflow 3 0 Gpm Ton C J Q Motorized Water Valve Afr 2 25 D K R Motorized Water Valv...

Страница 4: ...RCUIT OPTIONS 09 12 15 18 SERIES UNIT SIZE Size TRC06 TRC09 TRC12 TRC15 TRC18 1 5 2 0 2 5 3 0 3 5 0 095 0 126 0 158 0 189 0 221 2 0 2 5 3 0 3 5 4 0 0 126 0 158 0 189 0 221 0 252 US GPM LPS US GPM LPS...

Страница 5: ...and notices appear throughout this manual Read these items carefully before attempting any installation service or troubleshooting of the equipment DANGER Indicates an immediate hazardous situation w...

Страница 6: ...tem components Remove any dirt or debris found in or on these components Pre Installation Installation Operation and Maintenance instructions are provided with each unit Horizontal equipment is design...

Страница 7: ...6 203 x 660 10 x 26 254 x 660 10 x 32 254 x 812 Filter Size Bottom Return in mm 1 10 x 30 x 1 254 x 762 x 25 1 10 x 36 x 1 254 x 914 x 25 Front Return In mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5...

Страница 8: ...mm 1 7 x 29 5 x 1 8 178 x 749 x 3 2 1 7 x 35 5 x 1 8 178 x 902 x 3 2 Cabinet Size Bottom Return Std 5 127 Base W x H x D In mm 48 x 26 x 12 1219 x 660 x 305 54 x 26 x 12 1372 x 660 x 305 Front Return...

Страница 9: ...e for use with ClimateMaster Console Units Use the following guidelines when installing supply and return hose assemblies 1 Install supply and return hoses fitted with swivel joint fittings at one end...

Страница 10: ...correctly Horizontal runs of condensate hose should be pitched downward 1 4 inch minimum for every foot 10mm per 46cm of hose Avoid low points because dirt collects in these areas and may cause block...

Страница 11: ...DWHU RQQHFWLRQV 2 RSSHU 37 RU 037 8 00 Min 203 11 25 286 1 62 41 2 00 51 2 25 57 HIW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 RQGHQVDWH FWLRQV 2 25 57 Q 2...

Страница 12: ...UDWLRQ DWHU Q DWHU 2XW 1RWHV LPHQVLRQ UHGXFHG E ILWWLQJ LI VHOHFWHG 2 72 96 5LJKW DQG RQILJXUDWLRQ DWHU Q DWHU 2XW RPSUHVVRU FFHVV 3DQHO RQWURO R 1 84 47 RQGHQVDWH RQGHQVDWH 9LQ O RVH 2SWLRQD 0RWRUL D...

Страница 13: ...freeze is used in the loop insure that it is compatible with the Teflon tape or pipe joint compound that is applied Maximum allowable torque for brass fittings is 30 ft lbs 41 N m If a torque wrench i...

Страница 14: ...rop solenoid valve for use in variable speed pumping systems may also be included in the hose kit The piping system should be flushed to remove dirt piping chips and other foreign material prior to op...

Страница 15: ...le free ground loops These instructions are recommendations only State provincial and local codes MUST be followed and installation MUST conform to ALL applicable codes It is the responsibility of the...

Страница 16: ...or return water piping with water source heat pump products containing HFC 410A as system failures and property damage may result WARNING Use the appropriate scaling surface temperature for the appli...

Страница 17: ...t pumps from the ground water and confine heat exchanger cleanings to one location and lessen maintenance Direct use of ground water may increase the frequency of heat pump maintenance and may shorten...

Страница 18: ...NR 150 ppm NR NR 304 SS 400 ppm 250 ppm 150 ppm 316 SS 1000 ppm 550 ppm 375 ppm Titanium 1000 ppm 550 ppm 375 ppm Erosion and Clogging Particulate Size and Erosion All 10 ppm of particles and a maxim...

Страница 19: ...wer supply disconnect switch and secure it in an open position during installation CAUTION Use only copper conductors for field installed electrical wiring Unit terminals are not designed to accept ot...

Страница 20: ...5 10 0 12 4 20 11 5 13 8 20 G 208 230 60 1 197 254 1 4 7 25 0 0 6 5 3 6 5 15 5 7 7 3 15 E 265 60 1 239 292 1 4 2 22 0 0 4 4 6 5 7 15 5 4 6 5 15 TRC15 G 208 230 60 1 197 254 1 5 6 30 0 0 8 6 4 7 8 15 7...

Страница 21: ...ield installed B only required with systems employing remote mounted thermostats Figure 3 Typical Field Installed Wiring WARNING To avoid possible injury or death due to electrical shock open the powe...

Страница 22: ...flash U1 press up arrow and screen will change to U2 flashing Press and release mode button and on will flash To turn off push down arrow push up arrow to get back to on Press fan button to escape Fig...

Страница 23: ...ed it has the correct number of heating and cooling stages Zone integrity must be maintained to efficiently control units or groups of units Unless zones of control are considered and accounted for ad...

Страница 24: ...R410A 96B0292N03 LON ETL R410A 96B0292N04 MPC ETL R410A 96B0293N01 115 60 1 208 230 60 1 265 60 1 DXM ACO MCO ETL R410A 96B0293N02 REM ETL R410A 96B0293N03 LON ETL R410A 96B0293N04 MPC ETL R410A 96B0...

Страница 25: ...onnection DIP Switches Note In the following field configuration options DIP switches should only be changed when power is removed from the CXM control DIP switch 1 Unit Performance Sentinel Disable p...

Страница 26: ...rying Field Configuration Options Note In the following field configuration options jumper wires should be clipped ONLY when power is removed from the DXM control Water coil low temperature limit sett...

Страница 27: ...tings On Stage 1 Off Stage 2 1 3 Thermostat type heat pump or heat cool DIP 1 3 provides selection of thermostat type Heat pump or heat cool thermostats can be selected When in heat cool mode Y1 is th...

Страница 28: ...se 2 quick flashes 10 sec pause etc Low pressure switch The low pressure switch must be open and remain open for 30 continuous seconds during on cycle to be recognized as a low pressure fault If the l...

Страница 29: ...ill flash code 3 when the unit is in ESD mode ESD mode code 3 green status LED CXM DXM CONTROLS Diagnostic Features The LED on the CXM board advises the technician of the current status of the CXM con...

Страница 30: ...IT ENTERING WATER MIN MAX 40 120 4 5 49 60 90 16 43 EXTENDED RANGE UNIT ENTERING WATER MIN MAX 30 120 1 49 20 90 6 7 32 Requires optional insulation package when operating below the dew point Requires...

Страница 31: ...ther equivalent approved cleaning agent Reset the boiler to raise the loop temperature to 100 F 38 C Circulate the solution for a minimum of 8 to 24 hours At the end of this period shut off the circul...

Страница 32: ...oper pH promotes longevity of hoses and fittings see Table 3 System flushing Verify that all hoses are connected end to end when flushing to insure that debris bypasses the unit heat exchanger water v...

Страница 33: ...noise indicates proper functioning of the reversing valve 6 Allow five 5 minutes between tests for pressure to equalize before beginning heating test a Adjust the thermostat to the lowest setting Plac...

Страница 34: ...10 6 12 6 6 9 8 9 17 23 17 23 17 23 TRC12 Full Load Cooling Full Load Heating Entering Water Temp F Water Flow GPM Ton Suction Pressure PSIG Discharge Pressure PSIG Super heat Sub cooling Water Temp...

Страница 35: ...36 90 2 1 3 15 4 2 138 148 138 148 138 148 366 386 353 373 340 360 9 14 9 14 9 14 11 16 9 14 6 11 15 8 17 8 14 9 16 9 14 16 18 24 18 24 18 24 164 174 165 175 167 177 372 392 375 395 379 399 17 22 18 2...

Страница 36: ...g checks and data entries before the system is put into full operation Temperatures F or C Antifreeze __________________ Pressures PSIG or kPa Type __________________ Cooling Mode Heating Mode Return...

Страница 37: ...nditions and be replaced when necessary Units should never be operated without a filter Washable high efficiency electrostatic filters when dirty can exhibit a very high pressure drop for the fan moto...

Страница 38: ...lope of unit toward outlet Poor venting Check vent location X Moisture on sensor Check for moisture shorting to air coil X X Plugged air filter Replace air filter x X Restricted Return Air Flow Find a...

Страница 39: ...strictions Too high of external static Check static vs blower table X Reduced or no water flow in cooling Check pump operation or valve operation setting Check water flow Adjust to proper flow rate X...

Страница 40: ...5 68 7 21 7 1 1 6 6 36 6 7 36 6 7 5 2 3 7 1 48 1 3 16 21 9 9 5 2 36 6 7 36 6 7 7 5 1 7 5 287 36 36 7 5 1 7 5 287 36 36 8VH IRU ZDWHU IRU DQWLIUHH H 7 5 5 5 6 6 1 3 6 1625 3 16 21 9 9 7 5 5 5 3 6 6 1 2...

Страница 41: ...or incorrect system design or the improper application of CM s products CM is not responsible for 1 The costs of any uids refrigerant or other system components or associated labor to repair or repla...

Страница 42: ...nce as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any increases or unrealized savings in sam...

Страница 43: ...TH E SMA RT SO LUT I ON FOR E NE RG Y E FFI CIENCY Consoles Rev 0 8 24 1 5 43 climatemaster com Notes...

Страница 44: ...ing Conditions 12 02 08 TRC CCE Wiring Diagrams Consolidated 12 02 08 TRC Piping Connection Diagrams Added 09 09 08 Pressure Testing Note Updated 06 30 08 Shut Off Valve Note Added to Piping Connectio...

Отзывы: