background image

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

4

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

1.0  User Menu Settings

 

1.1  OFFSETS

 If 

you 

fi nd that the temperature displayed on the 

thermostat does not accurately represent the room 
temperature where the thermostat is located, this 
offset function compensates for the difference.  
The thermostat will apply an offset between what 
temperature the thermostat is measuring versus the 
temperature that is displayed.

 1.1.1 

TEMPERATURE 

OFFSET

 

The Temperature Offset function allows for 
calibration of the temperature sensor.

 

Adjust the Temperature Offset settings using the 
up/down arrow buttons.  Press the center button to 
save changes.

• 

Indoor Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)

• 

Remote Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)  

• 

Outdoor Temperature (default 0°F):  options:  
-5°F to +5°F (in 1°F increments)

 1.1.2 

ANTICPATOR

 If 

you 

fi nd that the thermostat is overshooting or 

undershooting the temperature setpoint value, the 
Anticipator setting allows for adjustment to correct 
the temperature algorithm.  When the Anticipator 
value is set to a lower number, the thermostat 
becomes more sensitive and when the Anticipator 
value is raised, the thermostat becomes less 
sensitive.  If the thermostat is overshooting the 
temperature setpoint, adjust the Anticipator 
value up to reduce thermostat sensitivity.  If the 
thermostat is undershooting the temperature 
setpoint, adjust the Anticipator value down to 
increase thermostat sensitivity.

 

Adjust the Anticipator setting using the up/down 
arrow buttons.  Press the center button to save 
changes.

• 

Anticipator (default 3):  valid range:  1 to 9

 1.1.3 

DIFFERENTIAL

 

The Differential adjustment will vary the number of 
degrees from the setpoint before a call for heating 
or cooling is made.  Use this function if you fi nd 
that the thermostat is starting a call too soon/late 
or staging equipment up/down too quickly/slowly.  
For example, with a 1 ˚F 1st stage differential and 
a heating setpoint of 70˚F, your thermostat will not 
call for heating until the temperature is 69˚F.

 
 

Adjust the Differential setting using the up/down 
arrow buttons.  Navigate between Differentials 
using the left/right arrow buttons.  Press the center 
button to save changes.

• 

1st  Stage (default 1°F): 

 options:  1°F to 4°F 

(in 1°F increments)

• 

2nd Stage (default 1°F):

  options:  1°F to 4°F 

(in 1°F increments)

• 

Aux Heat (default 1°F)

:  options:  1°F to 4°F 

(in 1°F increments)

 

NOTE 1:  

The thermostat must be confi gured for 

Multistage by installer to access the 2nd Stage 
Differential setting.  The thermostat must be 
confi gured for Auxiliary Heat by installer to access 
the Auxiliary Heat Differential setting.

 

 NOTE 

2:

  The temperature control algorithm must 

be confi gured for Differential control to access the 
Differential settings by installer.

 1.1.4 

HUMIDITY 

OFFSET

 If 

you 

fi nd that the Humidity level displayed on 

the thermostat does not accurately represent the 
Humidity level of the room in which the thermostat 
is located, use the Humidity Offset function to 
calibrate the humidity sensor.

 

Adjust the Humidity Offset setting using the up/
down arrow buttons.  Press the center button to 
save changes.

 

• 

Indoor Humidity (default 0%): 

 options:  

 

 

-10% to +10% (in 1% increments)

 

1.2  CYCLES PER HOUR

 

The thermostat allows the user to adjust the maximum 

number of on/off cycles per hour to maintain the 
desired indoor temperature.

 

Adjust the Cycles per Hour setting using the up/

down arrow buttons.  Press the center button to save 
changes.

•  4 (default):  

operation will start no sooner than 15 

minutes after the previous call was initiated

• 6: 

 

operation will start no sooner than 10 minutes 

after the previous call was initiated (can provide 
tighter temperature control)

 

1.3  AUTO CHANGEOVER TIME

 

When the thermostat is confi gured for AUTO mode, 

the thermostat automatically selects heating or 
cooling mode depending on the indoor temperature.  
The Auto Changeover Time is the amount of time that 
elapses before operation switches from heating to 
cooling mode or from cooling to heating mode.

 

Adjust the Auto Changeover Time using the up/

down arrow buttons.  Press the center button to save 
changes.

•  Auto Change Over Time (default 15 minutes):  

options:  0 to 120 minutes (in 15 minute 
increments)

Содержание ATC32U01 iGate

Страница 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...ct airflow from supply registers In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being r...

Страница 4: ...f 70 F your thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow...

Страница 5: ...mation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO 78...

Страница 6: ...multi stage compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up d...

Страница 7: ...be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating mode using the up down arro...

Страница 8: ...mum Heat LWT valid range based on specific model refer to model IOM Minimum Cool LWT valid range based on specific model refer to model IOM NOTE Refer to section 3 6 3 for multi unit configuration ins...

Страница 9: ...3 for multi unit configuration instructions VARIABLE SPD INTERNAL PUMP CONFIGURATION PUMP CONTROL FIXED HEATING STAGE 1 60 COOLING STAGE 2 75 COOLING STAGE 1 50 COOLING STAGE 2 70 PREVIOUS SELECT 3 5...

Страница 10: ...to remind the user to change the air filter after the selected time has passed Adjust the Air Filter Reminder settings using the up down arrow buttons Press the center button to save changes Cumulativ...

Страница 11: ...nergized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation This logic w...

Страница 12: ...COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0 PUMP SPEED 0 TEST MODE OFF SELECT OPTION PREVIOUS SELECT 9 2 CONTROL DIAGNOSTICS Control Diagnos...

Страница 13: ...T OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating control DX...

Страница 14: ...CC Y2 Y2 CO RV W W ACC1 O O OUTPT ACC2 G G FAN AL1 H H HWG EH1 OVR DH PUMP EH2 PREVIOUS FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 O...

Страница 15: ...its are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The thermostat will reset a...

Страница 16: ...contained herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system...

Отзывы: