background image

3

AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

ClimateMaster’s ATC32U** Communicating, Programmable 
Thermostat is the perfect compliment to a ClimateMaster 
Geothermal Heat Pump System and represents a signifi cant 
advancement in thermostat communicating technology.  For 
homeowners, the ATC32U** provides highly customizable cli-
mate control features designed to maximize comfort and re-
duce the amount of energy consumed by the ClimateMaster 
Geothermal Heat Pump System.  For dealers, it represents 
a signifi cant, industry leading advancement in confi guration, 
monitoring and diagnostics from the thermostat. Please read 
the following instructions carefully to maximize the comfort 
and cost-saving potential of your ClimateMaster Geothermal 
Heat Pump System.

SAFETY CONSIDERATIONS

Improper wiring or installation may damage thermostat. Wir-
ing must conform to local and national electrical codes

 

WARNING! 

WARNING!  Before installing thermostat, turn off all 
power to unit.  There may be more than one power 
disconnect.  Electrical shock can cause personal 
injury or death.

INSTALLATION CONSIDERATIONS

The thermostat requires no batteries.  The thermostat is not 
a power stealing device and MUST have both R and C termi-
nals connected. See Diagram 1.

INSTALLATION
I. THERMOSTAT 

LOCATION

Thermostat should be mounted:

 • 

Approximately 5 ft. (1.5m) above fl oor.

 • 

Close to or in a frequently used room, preferably on an 
inside partitioning wall.

 • 

On a section of wall without pipes or duct work.

Thermostat should NOT be mounted:

 • 

Close to a window, on an outside wall, or next to a 
door leading to the outside.

 • 

Exposed to direct light and heat from a lamp, sun, 
fi replace, or other temperature-radiating object which 
may cause a false reading.

 • 

Close to or in direct airfl ow from supply registers.

 • 

In areas with poor air circulation, such as behind a 
door or in an alcove.

II. THERMOSTAT INSTALLATION

 1.  Turn off all power to unit. 
 2.  If an existing thermostat is being replaced: 
 A.  Remove existing thermostat from wall.

B.  Disconnect wires from existing thermostat, one at 

a time.  Be careful not to allow wires to fall back 
into the wall.

C.  As each wire is disconnected, record wire color 

and terminal marking.

D.  Discard or recycle old thermostat.

 

NOTE

:  Mercury is a hazardous waste and MUST be dis-

posed of properly.

 

 3.  Separate the thermostat from base.
 4.  Route thermostat wires through hole in base.  Level 

base against wall (for aesthetic value only - thermo-
stat need not be leveled for proper operation) and 
mark wall through 2 mounting holes.

 5.  Drill two 3/16-in. mounting holes in wall where 

marked.  (Note: Mounting holes on thermostat are 
designed to fi t on a horizontal J-box).

 6.  Secure base to wall with 2 anchors and screws 

provided making sure all wires extend through hole in 
base.

 7.  Connect wires to proper terminal of the connector 

block in the thermostat.

 8.  Push any excess wire back into wall.  Excess wire 

inside the thermostat case can interfere with proper 
air fl ow across the temperature sensor.  Seal hole in 
wall to prevent air leaks.  Leaks can affect operation.

 9.  Install thermostat on base.
 10. Turn on power to the unit.

 

 

III. WIRING DIAGRAMS

All excess wire should be pushed back into the wall as far as 
possible.  Excess wire inside the thermostat plastic case may 
interfere with the air fl ow across the temperature sensor. 

ATC32U** Thermostat

24Vac Hot

DXM2

Control

24V

Comm +

A+

A+

Comm -

B-

B-

OD

ID

GND

Outdoor

Sensor

(Optional)

Remote Indoor

Sensor

(Optional)

24Vac Common

Gnd

R

C

Diagram 1: Thermostat Connections

Thermostat Connections

24V Common for Control Circuit

24V Supply for Control Circuit

A+ Communications 

(Positive)

B – 

Communications (Negative)

GND Ground
OD Outdoor 

Temperature 

Sensor 

ID Indoor 

Temperature 

Sensor

Содержание ATC32U01 iGate

Страница 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...ct airflow from supply registers In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being r...

Страница 4: ...f 70 F your thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow...

Страница 5: ...mation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO 78...

Страница 6: ...multi stage compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up d...

Страница 7: ...be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating mode using the up down arro...

Страница 8: ...mum Heat LWT valid range based on specific model refer to model IOM Minimum Cool LWT valid range based on specific model refer to model IOM NOTE Refer to section 3 6 3 for multi unit configuration ins...

Страница 9: ...3 for multi unit configuration instructions VARIABLE SPD INTERNAL PUMP CONFIGURATION PUMP CONTROL FIXED HEATING STAGE 1 60 COOLING STAGE 2 75 COOLING STAGE 1 50 COOLING STAGE 2 70 PREVIOUS SELECT 3 5...

Страница 10: ...to remind the user to change the air filter after the selected time has passed Adjust the Air Filter Reminder settings using the up down arrow buttons Press the center button to save changes Cumulativ...

Страница 11: ...nergized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation This logic w...

Страница 12: ...COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0 PUMP SPEED 0 TEST MODE OFF SELECT OPTION PREVIOUS SELECT 9 2 CONTROL DIAGNOSTICS Control Diagnos...

Страница 13: ...T OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating control DX...

Страница 14: ...CC Y2 Y2 CO RV W W ACC1 O O OUTPT ACC2 G G FAN AL1 H H HWG EH1 OVR DH PUMP EH2 PREVIOUS FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 O...

Страница 15: ...its are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The thermostat will reset a...

Страница 16: ...contained herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system...

Отзывы: