AT C 3 2 U 0 1   C o m m u n i c a t i n g ,   P r o g r a m m a b l e   T h e r m o s t a t   -   I O M

R e v. :   4   F e b . ,   2 0 1 3

8

G e o t h e r m a l   H e a t   P u m p   S y s t e m s

UNIT CONFIGURATION

CURRENT CONFIG                                    TE026

HEAT PUMP FAMILY                                     TE

HEAT PUMP SIZE                                         026

BLOWER TYPE                                           ECM

LOOP CONFIG                                      VS PUMP

PARALLEL

SELECT OPTION   

 PREVIOUS                                          SAVE 

VARIABLE SPD INTERNAL

PUMP CONFIGURATION

PUMP CONTROL                                   DELTA T

HEATING DELTA T                                             7

COOLING DELTA T                                          10

MAXIMUM HEAT LWT                                      80

MINIMUM COOL LWT                                      40

 PREVIOUS                                        SELECT 

•  Compressor ASCD (Anti-Short Cycle Delay 

(default stored in control)

 – valid range:  5 to 8 

(in 1 minute increments)

NOTE 1: 

 The Compressor Anti-Short Cycle Delay setting 

provides equipment protection by forcing the compressor to 
wait a few minutes before restarting.

NOTE 2: 

 If multiple units are connected to one thermostat, 

refer to section 3.6 for unit selection.

3.4 PUMP 

CONFIGURATION

vFlow™ vs internal flow control pump can be controlled either 
through temperature differential (Delta T) or can be set to 
specific speed (fixed; % of full speed for each heat and cool 
stage).

Configure temperature differentials at the thermostat for 
vFlow™ units with an internal flow control pump.

Adjust the Pump Configuration settings using the up/down 
arrow buttons.  Press the center button to select each item.

 

•  Heating Delta T (default stored in control) – 

 

 

valid range:  4 to 12ºF (in 1ºF increments)

 

•  Cooling Delta T (default stored in control) – 

 

 

valid range:  9 to 20ºF (in 1ºF increments)

Maximum Heat LWT (valid range based on specifi c model; 
refer to model IOM). Minimum Cool LWT (valid range based 
on specifi c model; refer to model IOM).

NOTE:

 Refer to section 3.6.3 for multi-unit confi guration 

instructions.

To control vs pump by fi xed speed, select ‘Pump Control’, 
press  , use down arrow to select ‘Fixed’, and press   to 
save.

Default stored in control. Valid range: 15% - 90% (in 1% 
increments)
Heating Stage 1   

Cooling Stage 1

Heating Stage 2   

Cooling Stage 2

If Pump Confi guration is set to ‘VS PUMP PARALLEL’, valid 
range changes to 50-90% (in 1% increments).

OPTION SELECTION

MOTORIZED VALVE                                      OFF

COMPRESSOR ASCD                                        5

 PREVIOUS                                             NEXT 

3.3 UNIT 

CONFIGURATION

Adjust the Unit Confi guration settings including Heat 
Pump Family, Heat Pump Size, Blower Type, and Loop 
Confi guration using the up/down arrow buttons.  Press the 
center button to select each item.

•  Heat Pump Family (default stored in control) – 

valid range:  TE, TY, TES, TEP, TRT, TSM

•  Heat Pump Size (default stored in control) 

– valid 

range:  depends on Heat Pump Family setting

•  Blower Type (default stored in control)

 – valid 

 

range:  NONE, PSC–2SPD, ECM, PSC–1SPD

• Loop 

Confi g (default stored in control)

 – valid 

range:  Other, VS PUMP SINGLE, VS PUMP 

 

PARALLEL, MOD VALVE, MOD VALVE MIN POS

Airfl ow, pump and valves can be confi gured from ‘System 
Confi guration’ screen.

Select ‘VS PUMP PARALLEL’ when applying an internal 
variable speed fl ow controller with other fl ow controllers on a 
single loop in parallel.

NOTE: 

Refer to section 3.6.3 for multi-unit confi guration 

instructions.

 

CAUTION! 

CAUTION! 

This is a Commercial option only and does not 

alter Residential unit operation.

Содержание ATC32U01 iGate

Страница 1: ...10 4 3 UV Lamp 10 Caution These instructions are intended to be used by the installer or service personnel End users are NOT advised to change or modify any of these settings Doing so may cause the e...

Страница 2: ...This page was intentionally left blank...

Страница 3: ...ct airflow from supply registers In areas with poor air circulation such as behind a door or in an alcove II THERMOSTAT INSTALLATION 1 Turn off all power to unit 2 If an existing thermostat is being r...

Страница 4: ...f 70 F your thermostat will not call for heating until the temperature is 69 F Adjust the Differential setting using the up down arrow buttons Navigate between Differentials using the left right arrow...

Страница 5: ...mation then press and hold the right arrow for 5 seconds 1 4 2 DEMO MODE OPERATION Control Demo Mode operation parameters from the Demo Operation screen shown below DEMO OPERATION OUTDOOR FAN AUTO 78...

Страница 6: ...multi stage compressor applications 2 0 Installer Menu Settings 2 1 INSTALLER MENU SETTINGS ACCESS The Installer Settings can be accessed at any time from the Main Operating screen by holding the up d...

Страница 7: ...be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating mode using the up down arro...

Страница 8: ...mum Heat LWT valid range based on specific model refer to model IOM Minimum Cool LWT valid range based on specific model refer to model IOM NOTE Refer to section 3 6 3 for multi unit configuration ins...

Страница 9: ...3 for multi unit configuration instructions VARIABLE SPD INTERNAL PUMP CONFIGURATION PUMP CONTROL FIXED HEATING STAGE 1 60 COOLING STAGE 2 75 COOLING STAGE 1 50 COOLING STAGE 2 70 PREVIOUS SELECT 3 5...

Страница 10: ...to remind the user to change the air filter after the selected time has passed Adjust the Air Filter Reminder settings using the up down arrow buttons Press the center button to save changes Cumulativ...

Страница 11: ...nergized until the demand is fully satisfied see NOTE 1 Differential This logic will only use temperature differential to determine the appropriate heating or cooling stages for operation This logic w...

Страница 12: ...COMM OUTPUT OFF O COMM OUTPUT OFF G COMM OUTPUT OFF H COMM OUTPUT OFF DH COMM OUTPUT OFF ECM AIRFLOW 0 PUMP SPEED 0 TEST MODE OFF SELECT OPTION PREVIOUS SELECT 9 2 CONTROL DIAGNOSTICS Control Diagnos...

Страница 13: ...T OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SETTING WELL PREVIOUS 9 4 FAULT HISTORY Fault History mode displays the five most recent stored fault codes for the connected communicating control DX...

Страница 14: ...CC Y2 Y2 CO RV W W ACC1 O O OUTPT ACC2 G G FAN AL1 H H HWG EH1 OVR DH PUMP EH2 PREVIOUS FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 O...

Страница 15: ...its are connected to one thermostat UNLIKE Mult Unit Diagnostics the service personnel views each units fault information by selecting the next option 10 0 Restore Defaults The thermostat will reset a...

Страница 16: ...contained herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products The management system...

Отзывы: