FieldSmart
®
FxMP Panel & Standard Frame
Installation Manual
_________________________________________________________
Manual 019807 REV A - June 2018
Splicing/Buffer Tube Storage
Proceed to splicing the buffer tubes into the cassettes for the first half of the panel.
Note:
Consult the Clearview Blue Cassette Installation Manual for splicing instructions. Viewable in the Installation
Manual section, under the Resources tab, of the Clearfield website. Link here:
https://www.seeclearfield.com/assets/documents/installation-manuals/clearview-blue-cassette-install-manual.pdf
Note: Panels shown in images may not match product received. Splicing in cassettes and buffer tube storage will
remain functionally the same.
4.
1.
Before splicing, remove the patch and
splice cassettes.
Note:
In a 144 port panel, ports 1-72
will be located in the cassettes held
on the left side of the panel. The latter
half, ports 73-144, will be located in the
cassettes on the right side of the panel.
This is true for all panel sizes.
Open the slack basket by pulling on the push/pull plungers and gently swinging the basket down.
Feed the buffer tubes for all cassettes on the right side of the panel (when looking from the rear of the panel), through
the front of the panel, to the right side of the bulkhead divider.
2.
3.