FieldSmart
®
FxMP Panel & Standard Frame
Installation Manual
_________________________________________________________
Manual 019807 REV A - June 2018
FxMP Panel Mounting
The FieldSmart FxMP Panel will arrive with reversible mounting brackets unattached. Depending on the size of the frame,
you will attach the mounting brackets in a 19 inch or 23 inch configuration.
The exception to this will be the 1RU panel, which has mounting brackets that are not reversible. These mounting brackets
will attach to a 19 inch frame. Extender brackets will be supplied with the panel, which can be attached to the mounting
brackets in order to mount the panel to a 23 inch frame.
Installing Mounting Brackets for 19 Inch Frame
If installing reversible mounting brackets for a 19 inch frame
configuration, the large side of the bracket will be mounted to the
panel. The smaller side will be used to mount the panel to the
frame.
Note:
Mounting brackets for the left and right sides of the panel
are identical, interchangeable parts.
1.
Align the reversible mounting bracket so that the holes in the bracket and the panel body match up. Using the
provided screws (three per bracket) secure the bracket into place. Repeat for the other side.
Note:
There are four bracket-to-panel screw holes on each side of the bracket and panel. One of the holes will be a
smaller size, used for a bonding screw with the NEBS panel.
2.