Operator's Manual: Model CB-1400
7-1
SECTION 7: RESETTING THE OIL PRIMARY CONTROL
Understanding the Oil Primary Control
NOTE:
The CB-1400 primary controller (CB Part #33400) is a recycle type control, which features
interrupted ignition operation.
The oil primary control will go into safety lockout and shut the burner off when it detects flame-out
during burner operation. The oil primary control will then wait approximately one to two minutes and
attempt to re-ignite the burner (recycle mode). If the burner does not re-ignite, the control will shut the
burner off on safety. The following procedure explains what should be done when this occurs.
It is very
important that you follow these instructions precisely when resetting the safety on the primary control
and restarting the burner.
Using the Reset Button
DANGER!
DO NOT push the reset button more than once! DO NOT push the reset button if
oil mist is present in the combustion chamber or when the combustion chamber is hot! DO NOT
operate your furnace if excess oil, oil vapor or fumes have accumulated in or near your furnace. As with
any oil burning furnace, improper operation may result in a fire or explosion hazard.
1.
Refer to Figure 7A.
2.
Check the combustion chamber for fuel mist by shining a flashlight through the observation port.
If you see fog (fuel mist) in the chamber, DO NOT push the reset button.
3.
If the combustion chamber is hot, allow the furnace to cool for at least 30 minutes. DO NOT
push the reset button.
4.
When you are sure all mist has been cleared from the chamber and the combustion chamber is
cool, depress the red button on the primary control for a minimum of three (3) seconds, then
release. Reset the control ONCE ONLY.
5.
If the burner will not restart, call your Clean Burn dealer immediately.
FIGURE 7A - Oil Primary Control
ATTENTION: Never touch a jumper wire
from an "F" terminal to a "T" terminal on
the oil primary control. This will severely
damage your primary control. Make sure
the plastic barrier strip is in place between
the "F" and "T" terminals as shown in
Figure 7A.
RESET BUTTON
THERMOSTAT WIRES
I88787−C
CAD CELL WIRES
PLASTIC BARRIER STIP
Содержание CB-1400
Страница 2: ......
Страница 8: ......
Страница 15: ...Operator sManual ModelCB 1400 1 7 For Your Safety continued CB 1400 Furnace Cabinet Safety Labels ...
Страница 18: ...Operator sManual ModelCB 1400 1 10 ...
Страница 62: ...Operator sManual ModelCB 1400 5 8 ...
Страница 68: ...Operator sManual ModelCB 1400 7 2 ...
Страница 84: ...Operator sManual ModelCB 1400 9 10 ...
Страница 92: ...Operator sManual ModelCB 1400 10 8 ...
Страница 106: ...Operator sManual ModelCB 1400 B 4 Wiring Diagrams continued FigureB4 MeteringPumpWiringSchematic H44040 ...
Страница 108: ...Operator sManual ModelCB 1400 C 2 ...