Operator's Manual: Model CB-1400
3-4
BURNER NOZZLE
NOZZLE IS STAMPED EITHER 9−5
OR −5 ON FLAT OF NOZZLE HEAD
SIDE VIEW − AA
3/16" GAP BETWEEN
ELECTRODES & NOZZLE
CRITICAL DIMENSIONS:
ELECTRODES MUST BE
FLUSH WITH NOZZLE TIP.
RETENTION HEAD DISK MUST
BE FLUSH WITH NOZZLE TIP
1/8"
SPARK
GAP
SIDE VIEW − BB
VIE
W
− A
A
VIEW
− BB
3X
I88340
Installing the Burner
Checking the Burner Nozzle and Electrodes
NOTE:
The burner nozzle, a Delavan 9-5, is factory installed. The nozzle size is indicated on the
nozzle as shown in Figure 3D. Refer also to
Appendix A
at the back of the manual for additional
specifications/instructions on the burner nozzle.
ATTENTION:
Check the electrode settings as specified in Figure 3D. The electrode settings must be
correct for your burner to operate properly.
Figure 3D - Burner Nozzle and Electrode Specifications