background image

16 

 

41000664 Iss 05 

9.1  General 

 

If  the  air  curtain  does  not  operate  after  running 

through  the  detail  provided  in  Section  6,  then  a 

suitably  competent  service  engineer  should  be 

called to identify the nature of the fault. 

 

Note  The  manufacturer  operates  a  service      

function  from  the  address  provided  in  these      

instructions.

 

 

All Air Curtains are fitted with fuse protection and 

motor thermal protection. 

 

Other  faults  in  relation  to  the  element, motor  and 

wiring should be identified using conventional fault 

finding techniques. 

 

In  the  event  that  electrical  components  are       

replaced,  please  ensure  that  electrical  safety 

checks in accordance with the regulations in force 

in the country of use are undertaken. 

 

9.2  Electrical Heated Units 

For the service engineer, please note that there is 

a  thermal  cut-out  incorporated  in  the  air  curtain 

which  needs  to  be  manually  reset.  The  cut-out  is 

located near to the mains terminal block. 
 

Re-setting the thermal cut-out may help to identify 

the  nature  of  the  fault  however  we  do  not         

recommend 

re-set 

without 

thorough                

investigation into why the cut-out operated.

 

9.3  Electronic Controller

 

If  the  air  curtain  goes  into  thermal  trip  (overheat) 

the  Electronic  panel  keypad  displays  an  ‘ERR’ 

code. Refer to air curtain instructions to remedy. 

The electronic control base unit  is protected from 

any  short  circuit  on  the  air  sensor  or  heatsink  

sensor  as  the  short  circuit  will  cause  the          

temperature  to  go  high  and  trigger  over           

temperature alarm.

 

1: 

Polarity:  Use  a  multimeter  to  check  correct   

polarity  between  all  three  cores  i.e.  that  +12V 

goes to +12V, DATA goes to DATA, and GND to 

GND. 

 

2:

 Continuity: Use a multimeter to check continuity 

between each end of all three cores. 

 

3: 

Short  circuit:  Use  a  multimeter  to  check  that 

there  are  no  short  circuits  between  any  of  the 

three cores.  

N.B.

 

This  test  should  be  done  with  both  ends  of 

the cable disconnected to avoid false readings.

 

 

4: 

Plugs: 

a) 

Check that the correct length of insulation has 

been stripped from each core.  

 

b) 

Check the tightness of the cables in the plugs. 

9. Fault Finding 

Figure 6. Thermal cut-out 

 

Figure 7. Electronic controller 

Содержание ScreenZone HE8360

Страница 1: ...inding 9 Parts Replacement 10 User Instructions 11 WARNINGS 1 This appliance must only be installed by a competent person in accordance with the requirements of the Codes of Practice or the rules in f...

Страница 2: ...Motor Replacement 10 2 Electrical Element Replacement 11 User Instructions 11 1 Keypad Buttons 11 2 Manual Operation 11 3 Automatic Control 11 3 1 Auto Mode 11 3 2 Auto Mode Settings 11 3 3 Door Switc...

Страница 3: ...is wired to the base unit via a screened twisted pair 28AWG or direct equiva lent 1 4 Location All units should be installed horizontally directly over the door opening It is recommended that the air...

Страница 4: ...TLET D see table OVERALL WIDTH mm 1500 2000 A 1562 2062 B 1492 1992 C 1553 2053 D 1638 2138 2 Dimensions 2 1 Air Curtain Cable Entries 13 35 43 5 SELECT 87 0 60 3crs 60 3crs Cable Entries 7 35 60 3crs...

Страница 5: ...nit terminals 12V DATA GND Air Data Air volume Low speed m h 2900 1600 2900 Medium speed m h 4100 2400 4100 High speed m h 5000 3300 5000 Air velocity Low 0M m s 6 0 Medium 0M m s 8 5 High 0M m s 11 0...

Страница 6: ...Screw terminals 4 for supply 6 for heater output 4 for fan output 2 for BMS time control 2 for sensor input 2 for external thermal trip 2 for external door switch Supply 415 3Ph Dimensions Program pan...

Страница 7: ...ow F2 T3 15A slow blow Protection External circuit breaker with the appropriate rating should be installed for the protection of the installation 4 1 Installer Wiring Electrically Heated 18 24kW THREE...

Страница 8: ...HREE PHASE ONLY The element outputs are connected to contactors AC1 and AC2 on terminals T1 T2 and T3 The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connect...

Страница 9: ...ked air curtains maximum 6 air curtains per control panel For mains wiring refer to section 4 of this manual installer wiring details The program panel is connected to the base unit in the first air c...

Страница 10: ...e around the sensor falls below the selected t2 temperature the heater will be working on 100 heat output If the tempera ture is above the selected t2 temperature but be low t1 selected temperature th...

Страница 11: ...t separation of greater than 3mm Test for correct operation and refit the cover For connection to the mains supply it will be necessary to remove the outer cover from the unit After removing the cover...

Страница 12: ...the wall at the desired mounting height and mark through the holes in the back box brackets to enable the wall to be drilled for the appropriate fixings Step 5 Drill the wall then fix the backbox in...

Страница 13: ...plate and connected to a surface mounted back box in a suitable location Please see Figure 5 Alternatively the program panel can be flush wall mounted with the addition of a suitable conduit box MK pa...

Страница 14: ...plied to the motor bearing from time to time The product should be serviced annually Servicing shall be undertaken by a competent person Step 1 Undo screws securing the grille Step 2 Adjust the grille...

Страница 15: ...cut out x 2 8 1 General Rating 18kW 3Ph 24kW 3Ph SE 100842 Length 2 0m HE 100527 100528 Length 1 5m 2 0m Element assembly AC ACR PANEL Program Keypad AC ACR PCB Base Unit SC OS Outside Air Sensor Due...

Страница 16: ...may help to identify the nature of the fault however we do not recommend re set without a thorough investigation into why the cut out operated 9 3 Electronic Controller If the air curtain goes into th...

Страница 17: ...te with bearing housing from rotor bear ing Step 2 Slacken the grub screw secur ing rotors to the motor shaft remove rotor Step 3 Repeat steps 1 2 for opposite rotor Step 4 Disconnect the wires from t...

Страница 18: ...1 to 4 above Step 1 Carefully remove connections to element noting wiring configuration Step 2 Remove two bolts securing elements Step 3 Lift out element cartridge replace as required Refit in revers...

Страница 19: ...rs Prefix F denotes the FAN SPEED This can be either 1 slow 2 medium or 3 fast speed 0 setting denotes the unit is OFF To alter the current speed press the button The value will start flashing Press t...

Страница 20: ...d in manual mode how ever you will not be able to benefit from the energy saving features which are available in auto mode 11 3 Automatic Control 11 3 1 Auto Mode The controller can be set to automati...

Страница 21: ...e around the temperature sensor falls below the t2 value the heater is working on 100 heat output If the temperature is above this value but is below set point t1 then the heater is working on 50 heat...

Страница 22: ...the b button for 5 seconds Setting d will appear The air curtain operates as normal under the program of the Fan and Heat settings As the door opens the air curtain changes state to the settings prese...

Отзывы: