background image

 

41000664 Iss 05 

1.2  General

 

All  installations  must  be  in  accordance  with  the 

regulations in force in the country of use. 

These instructions must be handed to the user on 

completion of the installation. 

Installers  and  service  engineers  must  be  able  to 

demonstrate competence and be suitably qualified 

in  accordance  with  the  regulations  in  force  in  the 

country of use. 

To  ensure  continued  and  safe  operation  it  is     

recommended  that  the  appliance  is  serviced    

annually. 

The  manufacturer  offers  a  maintenance  service. 

Details are available on request. 
The air curtain outlet grille and case air inlet slots 

must not be obstructed during use.

 

 

1.3  Electrical Supply 

For  full  electrical  loadings,  please  refer  to  the   

individual technical data sheets within this manual. 

 

It is recommended that the electrical supply to the 

base  unit  in  the  air  curtain  is  via  an  appropriate 

switched isolator in accordance with the         reg-

ulations in force in the country of use and must be 

via a fused isolator having a contact separation of 

greater than 3mm in all poles. 
BMS control, time switches, room thermostats and 

door  interlocks  can  be  installed  at  the  discretion 

and responsibility of the installer. 

 

All  units  must  be  wired  in  accordance  with  I.E.E 

regulations  for  the  Electrical  Equipment  of     

Buildings  and  the  installer  should  ensure  that  a 

suitable isolating switch is connected in the mains 

supply. 

 

Warning 

For safety reasons a good earth connection must 

ALWAYS be made to the heater and control box. 

 

1.3.1 Electronic Controller 

Electrically  heated  supply  is  415V  3  phase,     

Neutral and Earth. Max cable inlet size is 4mm² or 

6mm² (refer to individual technical specification). 

Remote  unit  is  wired  to  the  base  unit  via  a 

screened  twisted  pair  28AWG  (or  direct  equiva-

lent). 

1.4  Location 

 

All  units  should  be  installed  horizontally  directly 

over the door opening. It is recommended that the 

air curtain is installed on the inside of the building, 

within  the  open  room  space  against  a  wall  or   

ceiling.  

 

Care  must  be  taken  to  allow  complete  free  air 

movement into the inlet grilles of the unit to ensure 

correct  working  operation  of  the  air  curtain.  The 

discharge opening should be as close to the top of 

the door as possible and to cover the  entire door 

width. 

 

Units  can  be  mounted  adjacent  to  each  other  to 

cover  the  full  door  opening  across  wider           

entrances.  

 

These  units  are  designed  for  surface  mounting 

and  should  not  be  placed  into  a  ceiling  void,  due 

to  possible  obstruction  of  airflow  and  difficulty  in 

routine cleaning and maintenance. 

 

1.5  Clearance Distance 

It  is  recommended  that  a  minimum  clearance  of 

300mm is allowed around the top and front of the 

unit.  The  clearance  allows  for  cable  entry  and  

prevents combustible surfaces overheating.  
The  minimum  mounting  height  (floor  to  grille    

outlet)  is  1.8m.  The  recommended  maximum 

mounting  height  is  3m  for  standard  and  4m  for 

high capacity models. 
 

1.6  Health and Safety 

Sole liability rests  with the  installer to ensure that 

all  site  safety  procedures  are  adhered  to  during 

installation. 

Sole liability rests  with the  installer to ensure that 

protective safety wear such as hand, eye, ear and 

head  protection  is  used  during  installation  of  the 

product. 

Do not rest anything especially ladders against the 

product. 

 

1.7  Standards 

Units conform to the European electrical standard 

BS EN 60335-2-30 and to the following European 

CE directives- 

73/23/EEC - amended 98/68/EEC low voltage; 

89/336/EEC electromagnetic  compatibility. 

 

 

WARNING: 

 

THIS AIR CURTAIN SHOULD NOT BE 

INSTALLED WHERE THERE IS A 

CORROSIVE ATMOSPHERE. 

Содержание ScreenZone HE8360

Страница 1: ...inding 9 Parts Replacement 10 User Instructions 11 WARNINGS 1 This appliance must only be installed by a competent person in accordance with the requirements of the Codes of Practice or the rules in f...

Страница 2: ...Motor Replacement 10 2 Electrical Element Replacement 11 User Instructions 11 1 Keypad Buttons 11 2 Manual Operation 11 3 Automatic Control 11 3 1 Auto Mode 11 3 2 Auto Mode Settings 11 3 3 Door Switc...

Страница 3: ...is wired to the base unit via a screened twisted pair 28AWG or direct equiva lent 1 4 Location All units should be installed horizontally directly over the door opening It is recommended that the air...

Страница 4: ...TLET D see table OVERALL WIDTH mm 1500 2000 A 1562 2062 B 1492 1992 C 1553 2053 D 1638 2138 2 Dimensions 2 1 Air Curtain Cable Entries 13 35 43 5 SELECT 87 0 60 3crs 60 3crs Cable Entries 7 35 60 3crs...

Страница 5: ...nit terminals 12V DATA GND Air Data Air volume Low speed m h 2900 1600 2900 Medium speed m h 4100 2400 4100 High speed m h 5000 3300 5000 Air velocity Low 0M m s 6 0 Medium 0M m s 8 5 High 0M m s 11 0...

Страница 6: ...Screw terminals 4 for supply 6 for heater output 4 for fan output 2 for BMS time control 2 for sensor input 2 for external thermal trip 2 for external door switch Supply 415 3Ph Dimensions Program pan...

Страница 7: ...ow F2 T3 15A slow blow Protection External circuit breaker with the appropriate rating should be installed for the protection of the installation 4 1 Installer Wiring Electrically Heated 18 24kW THREE...

Страница 8: ...HREE PHASE ONLY The element outputs are connected to contactors AC1 and AC2 on terminals T1 T2 and T3 The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connect...

Страница 9: ...ked air curtains maximum 6 air curtains per control panel For mains wiring refer to section 4 of this manual installer wiring details The program panel is connected to the base unit in the first air c...

Страница 10: ...e around the sensor falls below the selected t2 temperature the heater will be working on 100 heat output If the tempera ture is above the selected t2 temperature but be low t1 selected temperature th...

Страница 11: ...t separation of greater than 3mm Test for correct operation and refit the cover For connection to the mains supply it will be necessary to remove the outer cover from the unit After removing the cover...

Страница 12: ...the wall at the desired mounting height and mark through the holes in the back box brackets to enable the wall to be drilled for the appropriate fixings Step 5 Drill the wall then fix the backbox in...

Страница 13: ...plate and connected to a surface mounted back box in a suitable location Please see Figure 5 Alternatively the program panel can be flush wall mounted with the addition of a suitable conduit box MK pa...

Страница 14: ...plied to the motor bearing from time to time The product should be serviced annually Servicing shall be undertaken by a competent person Step 1 Undo screws securing the grille Step 2 Adjust the grille...

Страница 15: ...cut out x 2 8 1 General Rating 18kW 3Ph 24kW 3Ph SE 100842 Length 2 0m HE 100527 100528 Length 1 5m 2 0m Element assembly AC ACR PANEL Program Keypad AC ACR PCB Base Unit SC OS Outside Air Sensor Due...

Страница 16: ...may help to identify the nature of the fault however we do not recommend re set without a thorough investigation into why the cut out operated 9 3 Electronic Controller If the air curtain goes into th...

Страница 17: ...te with bearing housing from rotor bear ing Step 2 Slacken the grub screw secur ing rotors to the motor shaft remove rotor Step 3 Repeat steps 1 2 for opposite rotor Step 4 Disconnect the wires from t...

Страница 18: ...1 to 4 above Step 1 Carefully remove connections to element noting wiring configuration Step 2 Remove two bolts securing elements Step 3 Lift out element cartridge replace as required Refit in revers...

Страница 19: ...rs Prefix F denotes the FAN SPEED This can be either 1 slow 2 medium or 3 fast speed 0 setting denotes the unit is OFF To alter the current speed press the button The value will start flashing Press t...

Страница 20: ...d in manual mode how ever you will not be able to benefit from the energy saving features which are available in auto mode 11 3 Automatic Control 11 3 1 Auto Mode The controller can be set to automati...

Страница 21: ...e around the temperature sensor falls below the t2 value the heater is working on 100 heat output If the temperature is above this value but is below set point t1 then the heater is working on 50 heat...

Страница 22: ...the b button for 5 seconds Setting d will appear The air curtain operates as normal under the program of the Fan and Heat settings As the door opens the air curtain changes state to the settings prese...

Отзывы: