5.1  Introduction 

Shops, warehouses and factories are all subject to 

the  problems  caused  by  frequently  opened  doors. 

The open door not only causes a draft but greatly 

increases  energy  loss  and,  therefore,  the  running 

cost of the building. Screenzone units offer a cost-

effective,  energy  efficient  solution  to  these  prob-

lems  by  reducing  heat  loss.  The  installation  of  a 

Screenzone air curtain with energy saving controls 

provides a barrier of air that keeps the conditioned 

or warm air inside the building. The energy saving 

control  unit  when  run  under  automatic  control  re-

duces  both  the  power  consumption  and  energy 

cost.  The  key  benefits  of  the  energy  saving  con-

trols are:  

 

Simple installation — wiring connections are 

direct  to  the  controller,  no  intermediary  ter-

minal blocks are required. 

 

Easy programming — the user sets two tem-

peratures and three fan speeds enabling the 

air  curtain  to  vary  the  required  heat  output 

depending on the selected temperatures. 

 

In conjunction with a door switch the control-

ler can be set to change the fan speed when 

the door opens. 

 

Compatible  with  Building  Management  Sys-

tems 

 

The air temperature sensor can be mounted 

outside or inside to enable temperature con-

trol. 

 

No specialist commissioning required. 

 

Reduced payback period of your investment 

thanks to the energy saving generated. 

 

Cabling  from  the  air  curtain  to  the  program 

panel requires only 3 core cable. 

 

One control unit can control up to six air cur-

tains. 

 

A centralised control unit can be mounted up 

to 50m from the air curtain. 

5.2  Control with ‘outdoor’ temperature 

 

sensor 

This  type  of  temperature  control  is  suitable  for 

open  door  trade  or  frequently  used  doorways  in 

large areas  where  heat from the heater  would not 

affect the indoor ambient temperature. The control-

ler can be set to vary the heat output depending on 

the  outside  temperature.  This  type  of  control 

shouldn’t be used in small areas, between two sets 

of  doors  or  small  shops.  In  this  configuration  the 

heater  is  running  on  a  preset  speed  and  variable 

heat  output  depending  on  two  user  selected  tem-

peratures 

t1

  and 

t2. 

(range  0  to  30  degrees  C) 

If 

the  outside  temperature  around  the  sensor  falls 

below  the  selected 

t2

  temperature  the  heater  will 

be  working  on  100%  heat  output.  If  the  tempera-

ture  is  above  the  selected 

t2

  temperature  but  be-

low 

t1

  selected  temperature  the  heater  will  be 

working on 50% heat output. If the outside temper-

ature  is  above  the  user  selected 

t1

  temperature 

there is no heat output but the fan is running on a 

5. Energy Saving Configuration 

selected speed. For example: 

t1 

16 deg C 

t2 

 7 deg C 

Temperature below 7 - full heat 

Temperature above 7 but below 16 - half heat 

Temperature above 16 - no heat, cold blow only

 

5.3  Control  with  ‘indoor’  temperature 

 

sensor 

This  type  of  temperature  control  is  suitable  when 

the heater is used in small areas, between two sets 

of doors or in small shops where running the heater 

on full heat setting for a longer period will bring the 

room temperature to a very high level. With a tem-

perature  sensor  mounted  inside    the  building  the 

controller  can  be  set  to  vary  the  heat  output  de-

pending on the inside ambient temperature. In this 

configuration  the  heater  is  running  on  a  preset 

speed  and  variable  heat  output  depending  on  two 

user  selected  temperatures 

t1

  and 

t2. 

(range  0  to 

30  degrees  C) 

If  the  ambient  temperature  around 

the  sensor  falls  below  the  selected 

t2

  temperature 

the  heater  will  be  working  on  100%  heat  output.  If 

the temperature is  above the selected 

t2

 tempera-

ture  but  below  the 

t1

  selected  temperature  the 

heater  will  be  working  on  50%  heat  output.  If  the 

ambient  temperature  around  the  sensor  is  above 

the  user  selected 

t1

  temperature  there  is  no  heat 

output  but  the  fan  is  running  on  a  selected  speed. 

For example: 

t1

 

20 deg C 

t2

 

15 deg C 

Temperature below 15 - full heat 

Temperature above 15 but below 20 - half heat 

Temperature above 20 - no heat, cold blow only 

 

5.4  Optional Features  

Both  types  of  control  can  be  used  in  conjunction 

with a door switch which will change the fan speed 

as selected by the user. In the case where the door 

switch is  not  used  a standard one pole switch can 

be used to change the fan speed in auto mode. The 

heater  can  be  also  connected  to  a  Building  man-

agement system or 24h 7day timer to run the heat-

er in fully automatic mode. If the heater is not con-

nected to a  Building management system or timer 

the  available  terminals  can  be  connected  to  a 

standard  one  pole  switch 

(light  switch) 

to  turn  the 

heater off or on.  

Содержание ScreenZone HE8360

Страница 1: ...inding 9 Parts Replacement 10 User Instructions 11 WARNINGS 1 This appliance must only be installed by a competent person in accordance with the requirements of the Codes of Practice or the rules in f...

Страница 2: ...Motor Replacement 10 2 Electrical Element Replacement 11 User Instructions 11 1 Keypad Buttons 11 2 Manual Operation 11 3 Automatic Control 11 3 1 Auto Mode 11 3 2 Auto Mode Settings 11 3 3 Door Switc...

Страница 3: ...is wired to the base unit via a screened twisted pair 28AWG or direct equiva lent 1 4 Location All units should be installed horizontally directly over the door opening It is recommended that the air...

Страница 4: ...TLET D see table OVERALL WIDTH mm 1500 2000 A 1562 2062 B 1492 1992 C 1553 2053 D 1638 2138 2 Dimensions 2 1 Air Curtain Cable Entries 13 35 43 5 SELECT 87 0 60 3crs 60 3crs Cable Entries 7 35 60 3crs...

Страница 5: ...nit terminals 12V DATA GND Air Data Air volume Low speed m h 2900 1600 2900 Medium speed m h 4100 2400 4100 High speed m h 5000 3300 5000 Air velocity Low 0M m s 6 0 Medium 0M m s 8 5 High 0M m s 11 0...

Страница 6: ...Screw terminals 4 for supply 6 for heater output 4 for fan output 2 for BMS time control 2 for sensor input 2 for external thermal trip 2 for external door switch Supply 415 3Ph Dimensions Program pan...

Страница 7: ...ow F2 T3 15A slow blow Protection External circuit breaker with the appropriate rating should be installed for the protection of the installation 4 1 Installer Wiring Electrically Heated 18 24kW THREE...

Страница 8: ...HREE PHASE ONLY The element outputs are connected to contactors AC1 and AC2 on terminals T1 T2 and T3 The fan output is connected to a 4 way connector marked N F1 F2 and F3 The thermal trip is connect...

Страница 9: ...ked air curtains maximum 6 air curtains per control panel For mains wiring refer to section 4 of this manual installer wiring details The program panel is connected to the base unit in the first air c...

Страница 10: ...e around the sensor falls below the selected t2 temperature the heater will be working on 100 heat output If the tempera ture is above the selected t2 temperature but be low t1 selected temperature th...

Страница 11: ...t separation of greater than 3mm Test for correct operation and refit the cover For connection to the mains supply it will be necessary to remove the outer cover from the unit After removing the cover...

Страница 12: ...the wall at the desired mounting height and mark through the holes in the back box brackets to enable the wall to be drilled for the appropriate fixings Step 5 Drill the wall then fix the backbox in...

Страница 13: ...plate and connected to a surface mounted back box in a suitable location Please see Figure 5 Alternatively the program panel can be flush wall mounted with the addition of a suitable conduit box MK pa...

Страница 14: ...plied to the motor bearing from time to time The product should be serviced annually Servicing shall be undertaken by a competent person Step 1 Undo screws securing the grille Step 2 Adjust the grille...

Страница 15: ...cut out x 2 8 1 General Rating 18kW 3Ph 24kW 3Ph SE 100842 Length 2 0m HE 100527 100528 Length 1 5m 2 0m Element assembly AC ACR PANEL Program Keypad AC ACR PCB Base Unit SC OS Outside Air Sensor Due...

Страница 16: ...may help to identify the nature of the fault however we do not recommend re set without a thorough investigation into why the cut out operated 9 3 Electronic Controller If the air curtain goes into th...

Страница 17: ...te with bearing housing from rotor bear ing Step 2 Slacken the grub screw secur ing rotors to the motor shaft remove rotor Step 3 Repeat steps 1 2 for opposite rotor Step 4 Disconnect the wires from t...

Страница 18: ...1 to 4 above Step 1 Carefully remove connections to element noting wiring configuration Step 2 Remove two bolts securing elements Step 3 Lift out element cartridge replace as required Refit in revers...

Страница 19: ...rs Prefix F denotes the FAN SPEED This can be either 1 slow 2 medium or 3 fast speed 0 setting denotes the unit is OFF To alter the current speed press the button The value will start flashing Press t...

Страница 20: ...d in manual mode how ever you will not be able to benefit from the energy saving features which are available in auto mode 11 3 Automatic Control 11 3 1 Auto Mode The controller can be set to automati...

Страница 21: ...e around the temperature sensor falls below the t2 value the heater is working on 100 heat output If the temperature is above this value but is below set point t1 then the heater is working on 50 heat...

Страница 22: ...the b button for 5 seconds Setting d will appear The air curtain operates as normal under the program of the Fan and Heat settings As the door opens the air curtain changes state to the settings prese...

Отзывы: