SM-P00077-A/3
2. INSTALLATION
54
2020-04-15
2.5.8
Flat cable connector (T51/T52/T53)
◼
Precautions on wiring the flat cable connector (T51/T52/T53)
• Signal arrays of the PLC output unit must match signal arrays on the valve side.
• Only 24 VDC or 12 VDC power can be used.
• The T51/T52/T53 types are driven with a general output unit.
• Connecting this manifold to the input unit may cause damage not only to the manifold itself but also to
peripheral devices. Do not connect this manifold to the input unit.
• Manifold stations are numbered in order from left to right with the piping port towards the user (refer to
the figure below).
• Voltage drop occurs when energizing solenoids at the same time or depending on the cable length.
Make sure that the voltage drop on the solenoid does not exceed 10% of the rated voltage.
◼
Internal wiring
-
T51
-
T52
-
T53
1st station
2nd station
3rd station
nth station
Manifold
station no.