Chapter 3 Turn Up a Node
NTP-G31 Install the DWDM Dispersion Compensating Units
Note
The DWDM node type is determined by the cards that are installed. For example, if two
32DMX-O and two 32MUX-O cards are installed but no AD-xC-xx.x or AD-xB-xx.x cards are
installed, CTC considers the node a hub node. However, if one 32DMX-O and one 32MUX-O
card are installed with no AD-xC-xx.x or AD-xB-xx.x cards, CTC considers the node a terminal
node. For more information, refer to
Step 8
Repeat Steps
through
until all the DWDM cards are installed in the node.
Step 9
If OPT-PRE cards are installed, complete one of the following steps for each OPT-PRE card based upon
the Cisco MetroPlanner shelf layout. If OPT-PRE cards are not installed, you have completed this
procedure.
•
If the Cisco MetroPlanner shelf layout does not include DCUs, install a 4-dB attenuator with a
tolerance of +/–1 dB between the OPT-PRE DC TX and RX ports for each OPT-PRE installed in the
shelf.
•
If the shelf layout includes DCUs, complete the
“NTP-G31 Install the DWDM Dispersion
Compensating Units” procedure on page 3-41
for each side of the shelf that requires a DCU.
Stop. You have completed this procedure.
NTP-G31 Install the DWDM Dispersion Compensating Units
Warning
Class I (CDRH) and Class 1M (IEC) laser products.
Statement 1055
Warning
Invisible laser radiation may be emitted from the end of the unterminated fiber cable or connector. Do
not view directly with optical instruments. Viewing the laser output with certain optical instruments
(for example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm may pose an eye
hazard.
Statement 1056
Caution
Always use the supplied ESD wristband when working with a powered ONS 15454. Plug the wristband
cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
Purpose
This procedure describes how to install the dispersion compensating units
(DCU-xx.x) for DWDM shelves.
Tools/Equipment
DCU-xx.x cards
Prerequisite Procedures
NTP-G15 Install the Common Control Cards, page 1-71
NTP-G14 Install DWDM Equipment, page 1-66
NTP-G30 Install the DWDM Cards, page 3-39
NTP-G139 Verify Cisco MetroPlanner Reports and Files, page 3-3
Required/As Needed
As needed
Onsite/Remote
Onsite
Security Level
Provisioning or higher