Chapter 1 Install the Shelf and Common Control Cards
NTP-G8 Install the Fan-Tray Assembly
•
If you are using a 100-A fuse panel, insert a 30-A fuse into the fuse position according to site
practice.
Step 3
Using a voltmeter, verify the ONS 15454 shelf for –48 VDC battery and ground:
a.
To verify the A-side of the shelf, place the black lead of the voltmeter to the frame ground. Place the
red test lead to the BAT1 (A-side battery connection) red cable. Verify that it reads between
–40.5 VDC and –57 VDC. Then place the red test lead of the voltmeter to the RET1 (A-side return
ground) black cable and verify that no voltage is present.
Note
The voltages –40.5 VDC and –57 VDC are, respectively, the minimum and maximum
voltages required to power the chassis.
b.
To verify the B-side of the shelf, place the black test lead of the voltmeter to the frame ground. Place
the red test lead to the BAT2 (B-side battery connection) red cable. Verify that it reads between
–40.5 VDC and –57 VDC. Then place the red test lead of the voltmeter to the RET2 (B-side return
ground) black cable and verify that no voltage is present.
Step 4
Return to your originating procedure (NTP).
NTP-G8 Install the Fan-Tray Assembly
Caution
Do not operate an ONS 15454 without a fan-tray air filter. A fan-tray air filter is mandatory, except for
ONS 15454 ANSI applications in an outside plant cabinet.
Note
Error messages appear on the TCC2/TCC2P card, the fan-tray LED, and in Cisco Transport Controller
(CTC) when the fan-tray assembly is removed from the shelf or when one fan is not working.
Note
If you are installing the ONS 15454 in an outside plant cabinet, remove the air filter to provide maximum
cooling capabilities and to comply with Telcordia GR-487-CORE.
Purpose
This procedure installs the fan-tray assembly.
Tools/Equipment
#2 Phillips screwdriver
Medium slot-head screwdriver
Small slot-head screwdriver
Prerequisite Procedures
NTP-G3 Open and Remove the Front Door, page 1-20
NTP-G7 Install the Power and Ground, page 1-30
Required/As Needed
Required
Onsite/Remote
Onsite
Security Level
None