7-27
Cisco ONS 15454 Installation and Operations Guide
November 2001
Chapter 7 Card Provisioning
Provisioning the Alarm Interface Controller
Figure 7-5
External alarms and controls using a virtual wire
When using AIC virtual wires, you can:
•
Assign different external devices to the same virtual wire.
•
Assign virtual wires as the trigger type for different external controls.
Procedure: Provision External Alarms
Step 1
Wire the external-device relays to the ENVIR ALARMS IN backplane pins. See the
“Alarm, Timing,
LAN, and Craft Pin Connections” section on page 1-32
for more information.
Step 2
Log into the node in CTC and display the AIC in card view.
Step 3
Click the Provisioning > External Alarms tabs (
Figure 7-6 on page 7-28
).
Step 4
Complete the following fields for each external device wired to the ONS 15454 backplane:
•
Enabled—Click to activate the fields for the alarm input number.
•
Alarm Type—Select an alarm type from the provided list.
ONS 15454
Node 1
Virtual Wire #1 is
external control
trigger
Virtual Wire #1
Smoke
detector
Bell
Smoke
detector
ONS 15454
Node 2
ONS 15454
Node 3
ONS 15454
Node 4
Virtual Wire #1
Virtual Wire #1
Virtual Wire #1
= External alarm
= External control
Smoke
detector
Smoke
detector
44743
Содержание 15454-TCC - Network Processor Card
Страница 22: ...Figures xxii Cisco ONS 15454 Installation and Operations Guide November 2001 ...
Страница 32: ...Procedures xxxii Cisco ONS 15454 Installation and Operations Guide November 2001 ...
Страница 158: ...3 20 Cisco ONS 15454 Installation and Operations Guide November 2001 Chapter 3 Node Setup Viewing CTC Software Versions ...
Страница 388: ...11 10 Cisco ONS 15454 Installation and Operations Guide November 2001 Chapter 11 SNMP SNMP Remote Network Monitoring ...