1 three-pole electromechanical contactor
, appropriate for connecting capacitive loads
(application category AC-6), with a pre-inserted impedance block to limit the capacitor's con-
nection current and fast discharging resistors to ensure a minimal residual voltage in the ca-
pacitor when it is connected.
The contactors have 1 x 230 V / 50-60 Hz (± 10 %) operation coils.
1 three-phase capacitor
, in a cylindrical aluminium housing, with a rated voltage of 440 V.
1 three-pole circuit breaker
with a calibre suitable for the stage power, with a C Curve and
Ics = 6 kA (400 V).
For more detailed information, see section
2.1.5. MAINS CONNECTION TERMINALS
The mains connection terminals of a
OPTIM HYB
unit consist of the input terminals of the quad-
rupole isolating switch, which comes standard with the capacitor bank.
For more detailed information, see section
14
OPTIM HYB Series
Instruction Manual