24
GETEST
Instructions Manual
Table 6 (Continued): Warning and error messages
Message
Cause
Solution
Error: Unable to reach
required current, there is a
drop in the device's supply
voltage� The installation to
which it is connected is un-
able to supply the required
current� At least 20 kVA is
required� Do you wish to
continue extrapolating the
data?
GETEST
being asked to supply more
power than the electricity grid is capable of
supplying. Power is equal to the resistance
of earth by the square of the current to be
injected. If allowed, the
GETEST
application
will extrapolate the values by applying a
current less than the desired one.
Connect the
GETEST
to a mains socket con-
nected to an installation with less imped-
ance, or to a generator with more power.
Warning: a short circuit has
been found in the output�
The current has been limit-
ed to 35 A� Check the con-
nections�
Measured resistance less than 0.7 Ω.
Check the connections. It is possible there is
a metallic plane in the ground.
Notice: resistance found
greater than 120
Ω
� Check
connections�
Do you wish to continue?
There is a risk of electroshock.
Resistance encountered too high.
Check the connections, make sure that no
one is touching the connectors / electrodes
/ auxiliary ground; remove rust from con-
nectors / electrodes / auxiliary ground.
Содержание GETEST MPC-5
Страница 1: ...INSTRUCTIONS MANUAL Step and contact voltage meter GETEST M98224701 03 20A...
Страница 2: ...2 GETEST Instructions Manual...
Страница 29: ...29 Instructions Manual GETEST 8 CE CERTIFICATE...
Страница 30: ...30 GETEST Instructions Manual...
Страница 31: ...31 Instructions Manual GETEST...