14
GETEST
Instructions Manual
MPC 5-50/Getest
0...40ºC
IP20-Class I
CAT II-300V
230±20%Vac
50/60Hz
30kW/20ms
CIRCUTOR SA - Vial Sant Jordi, s/n
08232 Viladecavalls (Barcelona) Spain
Main Module S/N
Bluetooth S/N
Date
Made in EU (Spain)
Figure 5: Getest label�
5�-
Once the device is linked, open the
Getest
application.
Select the linked device in the
Device Identifier 1
tab and press the
wireless connection button
2
.
6�-
Put the safety key in the
TEST ENABLED
setting.
7�-
Select the
Mains frequency
and the value of the
Test current to be injected
.
8�-
Select the type of test in the
Mode
tab.
The device features 3 types of tests:
Step Voltage, Contact Voltage
and
Ground Resistance
.
9�-
For standard testing on
Step Voltage and Contact Voltage
it is necessary to select the test
resistance and the maximum defect current.
In the
Resistance
tab, select according to ITC-RAT-13:
1 k
, for “barefoot” measurement.
2 k
, for “shod foot” measurement.
Once the Resistance has been selected in the application, it is also necessary to select it
in the device, pressing the resistance selection switch.
The switch will turn on indicating the selection of
2kΩ
, by default it is
1kΩ
.
In the
Max defect current
section, it is necessary to program the maximum defect current, according
1
2