59
Technical Data
OPTIONAL DEVICES
Wireless Comunication
4G LTE /WiFi Hotspot/GPRS/GSM
Surge protection
Four pole transient surge protector IEC 61643-1 (class II)
Cable Length
5.5m (all cables)
Anti-vandal connector
protection
CHAdeMO, CCS (mechanical connector locking)
RFID Extension
Legic Advant / Legic Prime
ISO 15693/ISO 18092. Sony FeliCa
Low temperature Kit
- 30ºC to + 50ºC
POWER UNIT
AC power supply
3P + N + PE
AC Voltage
400 V AC +/- 10%
Maximum AC input
current
237 A
Required power supply
capacity
164 KVA
Power Factor (pu)
› 0,98
Efficiency (pu)
94 % at nominal output power
Frequency (pu)
50 / 60 Hz
Cooling system
Forced air
Operational noise level
‹ 55 dBA
Electrical input
protection
Main circuit disconnection
Overcurrent protections
(pu)
MCB curve C
Safety protection (pu)
RCD 30mA Type B
Dimensions (D x W x H)
800x1000x2100mm
Weight
420 kg
Содержание Raption 150 Series
Страница 1: ...Installation Manual Raption 150 Series ...
Страница 2: ......
Страница 4: ......
Страница 7: ...03 ...
Страница 20: ...16 Raption 150 Series Installation Manual Power Unit front door Power input supply ...
Страница 21: ...17 Power Unit rear door Output wiring to Dispenser ...
Страница 27: ...23 1 2 3 4 ...
Страница 34: ...30 Raption 150 Series Installation Manual E Dispenser template dimensions 435 300 70 ...
Страница 35: ...31 400 165 280 310 ...
Страница 37: ...33 0 1920 ...
Страница 40: ...36 Raption 150 Series Installation Manual H Power Unit template dimensions 250 350 50 50 850 714 ...
Страница 42: ...38 Raption 150 Series Installation Manual Concrete basement dimensions for Power Unit J 0 2100 ...
Страница 51: ...47 CCS CCS CHA CHA 3 ...
Страница 53: ...49 PE DC 2 L N PE ETHERNET CABLE 2 1 3 DC 1 2 2 Wiring connection for the Dispenser Scheme ...
Страница 55: ...51 L1 N PE ETHERNET 1 2 ...
Страница 56: ...52 Raption 150 Series Installation Manual CCS CCS 3 ...
Страница 57: ...53 CHA PE CHA 3 ...
Страница 59: ...55 ...
Страница 65: ...61 ...
Страница 66: ...62 Raption 150 Series Installation Manual 8 ...