Total Solution for Industrial Automation
62
Hybrid Xpanel User’s Manual
(2)
Touch Problem
First, check if the protective film is removed. Protective film is only there for temporary
protection of product. It must be removed before operating the product. If there seems
to be a problem even when the protective film is removed, please refer to the following
steps.
1)
Intended and actual touch points are different.
The device might require additional calibration. Calibration methods are described
below.
I.
Calibrating Hybrid Xpanel using long-touch
The way can be only used when preset below is applied.
Preset
a)
Select [Configure] in the Ethernet loader dialog box.
b)
Check the box [Hold time for Touch Calibration] and set touch time in range of 30
seconds to 32767 seconds. Select [Save and Quit].