The changeover between lead machine and follower may take 
place when the assembly is started up, or even whilst running. 
The running time balancing function is not active if it has not been 

configured: in this case the lead machine is always the master 

unit.

The lead machine will always be started first. When the lead ma

-

chine is at its full available capacity, start-up delay (configurable) 
is initialised on the follower. When this delay has expired, and if 
the error on the control point is greater than 1.7°C, the follower 

unit is authorised to start and the pump is activated. The follower 
will automatically use the master unit active setpoint. The lead 
machine will be held at its full available capacity for as long as the 
active capacity on the follower is not zero. When the follower unit 
receives a command to stop, its evaporator water pump is turned 
off with 20 seconds delay.

In the event of a communication fault between the two units, 
each shall return to an autonomous operating mode until the fault 
is cleared. If the master unit is halted due to an alarm, the slave 
unit is authorised to start without prior conditions.

ATTENTION: For heat pumps operating in master/slave mode 
and using an NRCP2 board or equipped with electric heater 
stages control must be on the entering water temperature.

5 - PRO- CONTROL OPERATION

 

 

EN - 21 

EREBA ACCESS

Содержание PRO-DIALOG+

Страница 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Страница 2: ......

Страница 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Страница 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Страница 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Страница 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Страница 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Страница 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Страница 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Страница 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Страница 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Страница 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Страница 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Страница 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Страница 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Страница 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Страница 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Страница 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Страница 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Страница 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Страница 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Страница 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Страница 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Страница 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Страница 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Страница 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Страница 27: ......

Страница 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: