CIAT PRO-DIALOG+ Скачать руководство пользователя страница 8

4.4 - Menu screen characteristics

\\MAINMENU

Current path in the menu structure

GENUNIT

PUMPSTAT

Selection cursor to the left of the 

first column

TEMP

RUNTIME

PRESSURE

MODES

Menu list

SETPOINT

LANGUAGE

INPUTS

LOGOUT

OUTPUTS

General Parameters Menu

Description of the menu framed by 

the selection cursor

Each menu item defines the access to categorised data. The 

Up and Down arrows position the cursor at the current item. 
The Enter key activates the display of the selected sub-menu.

The item LOGOUT permits exiting from the menu screen and 

protects access by a user password. The “Previous” key per-

mits  exiting  from  the  current  screen  without  deactivating  the 

password-protected access.

4.5 - Data screen or configurable parameter 

characteristics

The data screens display information parameters such as tem-

peratures or pressures. The configuration screens display unit 

control parameters such as the water temperature setpoints.

\\MAINMENU\TEMP

Current path in the menu structure

EWT        

 12.0°C 

List of items

LWT         

   7.0°C

Cursor position

OAT        

 35.0°C

CHWSTEMP      

-17.8°C

SCT_A

 57.0°C

Leaving Water Temperature

Description of the item framed by 

the selection cursor

The Up and Down arrow keys position the cursor on the current 

menu item. The Enter key activates the parameter modification 
(if possible). Any non-pertinent modification attempt is blocked 

by a refusal screen.

4 - SETTING UP PRO- CONTROL

4.1 - General features

The interface includes different screens that are listed below:

• 

Default screens with direct display of the main parameters,

• 

Menu screens for navigation,

• 

Data/configuration screens listing the parameters by type,

• 

Operating mode selection screen,

• 

Password entry screen,

• 

Parameter modification screen.

4.2 - Default screen characteristics

There are four default screens. Each screen shows:

• 

The unit status, its screen number,

• 

Three displayed parameters.

LOCAL OFF                               1

On the left the unit status, on the right 

the screen number

Entering water temp

Description of the first parameter

EWT      

17.2 °C

Abbreviation and value with unit of 

measurement of the first parameter

Leaving water temp

Description of the second parameter

LWT

17.2 °C

Abbreviation and value with unit of 

measurement of the second parameter

Outside air temperature

Description of the third parameter

OAT      

21.7 °C

Abbreviation and value with unit of 

measurement of the third parameter

Pressing the Up or Down key changes one default screen to 
another default screen. The screen number is updated.

4.3 - Password screens

Enter password

Description of the password entry 

screen

      0_**

Password value

(

0 = basic access)

Description

The password is entered digit by digit. The cursor is shown at the 

current digit that flashes. The arrow keys modify the digit value. 
The digit modification is validated with the Enter key and the cur

-

sor is moved to the next digit.

Enter password

      1_**

The first digit is 1, the cursor is 

positioned on the second digit

(0 = basic access)

Enter password

      11_**

(0 = basic access)

Pressing the Enter key at a digit without value validates the 
overall selection of the password. The screen is refreshed by 
the menu list, and the items displayed depend on the level of 
the activated password. The entry of an incorrect password 
keeps the password entry screen.

Password selection 0 (zero) can simply be made by pressing 

the Enter key twice in succession.

NOTE: If the interface is not used for a long period, it will go 
black. The control is always active, the operating mode 
remains unchanged. The interface screen is re-animated, 
when the user presses a key. Pressing the key once illumi-
nates the screen, pressing the key a second time leads to a 
screen that is related to the context and the key symbol.

 

EREBA ACCESS 

 EN - 6 

Содержание PRO-DIALOG+

Страница 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Страница 2: ......

Страница 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Страница 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Страница 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Страница 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Страница 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Страница 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Страница 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Страница 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Страница 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Страница 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Страница 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Страница 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Страница 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Страница 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Страница 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Страница 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Страница 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Страница 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Страница 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Страница 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Страница 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Страница 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Страница 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Страница 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...