5.1 - Start/stop control
The table below summarises the unit control type and stop or
go status with regard to the following parameters.
•
Operating type: this is selected using the start/stop button
on the front of the user interface.
LOFF: local off, L-C: local on, L-SC: local schedule, REM:
remote, Net.: network, MAST: Master
•
Remote start/stop contacts: these contacts are used
when the unit is in remote operating type (Remote). See
sections 3.6.2 and 3.6.3.
•
CHIL_S_S: this network command relates to the unit
start/stop when the unit is in network mode.
•
Command set to Stop: the unit is halted.
•
Command set to Start: the unit runs in accordance with
schedule 1.
•
Start/Stop schedule: occupied or unoccupied status of
the unit as determined by the chiller start/stop program
(Schedule 1).
•
Master control type. This parameter is used when the unit
is the master unit in a two chiller lead/lag arrangement.
The master control type determines whether the unit is to
be controlled locally, remotely or through Network (this
parameter is a Service configuration).
•
Network emergency shutdown: if this network command
is activated, it shuts the unit down whatever the active
operating type.
•
General alarm: the unit is totally stopped due to failure.
5.2 - Heating/cooling/standby operation
5.2.1 - General
The heating / cooling / standby selection applies to all units. But
only liquid chillers, controlling a boiler can change over to heating
mode. Heating/cooling control can be automatic or manual.
In automatic mode the outdoor temperature determines the
heating/cooling/standby changeover based on the two threshold
values configured by the user (see RESETCFG menu for cooling
and heating mode changeover thresholds).
If the unit is in standby it does not cool or heat, and no com-
pressor can be activated. The diagram below summarises the
operating principle in automatic mode.
HEATING
STANDBY
COOLING
Outdoor
temperature
Heating
threshold*
Cooling
threshold
* This threshold does not apply to cooling only units that do not control a
boiler.
ACTIVE OPERATING TYPE
STATUS OF PARAMETERS
CONTROL
TYPE
UNIT
MODE
LOFF
L-ON
L-SC
rEM
Net.
MASt
CHIL_S_S
REMOTE
START/
STOP
CONTACT
MASTER
CONTROL
TYPE
START/STOP
SCHEDULE
MODE
NETWORK
EMERGENCY
SHUTDOWN
GENERAL
ALARM
-
-
-
-
-
-
-
-
-
-
Enable
-
-
Off
-
-
-
-
-
-
-
-
-
-
-
Yes
-
Off
Active
-
-
-
-
-
-
-
-
-
-
-
Local
Off
-
-
Active
-
-
-
-
-
-
Unoccupied
-
-
Local
Off
-
-
-
Active
-
-
-
Off
-
-
-
-
Remote
Off
-
-
-
Active
-
-
-
-
-
Unoccupied
-
-
Remote
Off
-
-
-
-
Active
-
Disable
-
-
-
-
-
Network
Off
-
-
-
-
Active
-
-
-
-
Unoccupied
-
-
Network
Off
-
-
-
-
-
Active
-
-
Local
Unoccupied
-
-
Local
Off
-
-
-
-
-
Active
-
Off
Remote
-
-
-
Remote
Off
-
-
-
-
-
Active
-
-
Remote
Unoccupied
-
-
Remote
Off
-
-
-
-
-
Active
Disable
-
Network
-
-
-
Network
Off
-
-
-
-
-
Active
-
-
Network
Unoccupied
-
-
Network
Off
-
Active
-
-
-
-
-
-
-
-
Disable
No
Local
On
-
-
Active
-
-
-
-
-
-
Occupied
Disable
No
Local
On
-
-
-
Active
-
-
-
On cooling
-
Occupied
Disable
No
Remote
On
-
-
-
Active
-
-
-
On heating
-
Occupied
Disable
No
Remote
On
-
-
-
Active
-
-
-
On auto
-
Occupied
Disable
No
Remote
On
-
-
-
-
Active
-
Enable
-
-
Occupied
Disable
No
Network
On
-
-
-
-
-
Active
-
-
Local
Occupied
Disable
No
Local
On
-
-
-
-
-
Active
-
On cooling
Remote
Occupied
Disable
No
Remote
On
-
-
-
-
-
Active
-
On heating
Remote
Occupied
Disable
No
Remote
On
-
-
-
-
-
Active
-
On auto
Remote
Occupied
Disable
No
Remote
On
-
-
-
-
-
Active
Enable
-
Network
Occupied
Disable
No
Network
On
5 - PRO- CONTROL OPERATION