Figure 1 - Control board

3.2 - Electrical supply to boards

All boards are supplied from a common 24 V a.c. supply referred 
to earth.

CAUTION: Maintain the correct polarity of the power 
supply connection of the boards, to ensure that  
they are not damaged.

In the event of a power supply interrupt, the unit restarts auto-

matically without the need for an external command. However, 

any faults active when the supply is interrupted are saved and 
may in certain cases prevent a circuit or unit from restarting.

3.3 - Light emitting diodes on boards

All boards continuously check and indicate the proper opera-
tion of their electronic circuits. A light emitting diode (LED) lights 
on each board when it is operating properly.

•   The red LED that flashes for a two-second period - one 

second on, one second off - indicates correct operation. 
A different rate indicates a board or a software failure.

• 

The green LED flashes continuously on all boards to 

show that the board is communicating correctly over its 

internal bus. If the LED is not flashing, this indicates a 

LEN bus wiring problem.

• 

The orange LED of the master board flashes during any 

communication via the proprietary protocol communica-
tion bus.

3.4 - The sensors

Pressure sensors

Two types of electronic (high and low-pressure) sensors are 
used to measure the suction and discharge pressure in each 
circuit.

Thermistors

The heat exchanger water sensors are installed in the entering 

and leaving side. The outdoor temperature sensor is mounted 
under a metal plate. An optional water system temperature sen-
sor can be used for master/slave assembly control (in the case 
of leaving water control).

In heat pump units a sensor placed on an air heat exchanger 

pipe ensures defrost operation.

3.5 - The controls

Water circulation pump

The  controller  can  regulate  one  or  two  water  heat  exchanger 

pumps and takes care of automatic change-over between pumps.

Heaters

They protect the heat exchanger (and the piping for units without 

pump) against frost, if the unit has stopped and is left energised.

Boiler

This output authorises start/stop of a boiler.

Contrast control 

wheel

Back to the previous 

screen

On/off key

- Unit stopped

- List of available operating 

modes (only in local mode) 

Green  LED

Unit has stopped

Unit starts up

Unit in operation

Red LED

No alarm

Warning

Circuit or complete unit error

Up/Down key

- Navigation

- Modification

Enter key

- Validation

- Selection access

3 - HARDWARE DESCRIPTION

3.1 - General

The control system consists of an NRCP2-BASE board for sin-
gle-circuit units (up to two compressors) and two NRCP2-BASE 
boards (one master and one slave board) for units with three or 
four compressors. The heat pump units that are equipped with 
the additional electric heater stage option uses an additional PD-
AUX board.

All boards communicate via an internal LEN bus. The NRCP2-
BASE boards continuously manage the information received 
from the various pressure and temperature probes. The NRCP2-
BASE master board contains the program that controls the unit. 
The user interface includes an alphanumeric eight-line display, 

two LEDs with five navigation keys as well as a contrast control 

wheel. 

 

 

EN - 3 

EREBA ACCESS

Содержание PRO-DIALOG+

Страница 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Страница 2: ......

Страница 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Страница 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Страница 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Страница 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Страница 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Страница 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Страница 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Страница 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Страница 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Страница 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Страница 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Страница 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Страница 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Страница 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Страница 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Страница 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Страница 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Страница 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Страница 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Страница 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Страница 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Страница 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Страница 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Страница 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Страница 27: ......

Страница 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: