background image

5.6 - Control point

The control point represents the water temperature that the unit 

must produce. The heat exchanger entering water temperature 
is controlled by default, but the heat exchanger leaving water 
temperature can also be controlled (requires a Service configu

-

ration modification).

Control point = active se reset

5.6.1 - Active setpoint

Two setpoints can be selected as active in cooling mode and 
two in heating mode. Usually, the second setpoint is used for 
unoccupied periods. 

Depending on the current operating type, the active setpoint 
can be selected:

• 

by choosing the item in the GENUNIT menu,

• 

via the user’s volt-free contacts,

• 

via network commands,

• 

via the setpoint timer program (schedule 2).

The following tables summarise the possible selections de-
pending on the control types (local, remote or network) and the 
following parameters:

• 

Setpoint select in local control: item LSP_SEL in the 

GENUNIT menu permits selection of the active set-point, if 
the unit is in local operating type.

• 

Heating/cooling operating mode.

• 

Setpoint selection contacts: setpoint selection contact status.

• 

Schedule 2 status: schedule for setpoint selection.

LOCAL OPERATING MODE

PARAMETER STATUS
Heating/cooling 
operating mode

Local setpoint 
selection

Time schedule 2 
status

Active 
setpoint

Cooling

sp 1

-

Cooling setpoint 1

Cooling

sp 2

-

Cooling setpoint 2

Cooling 

auto

occupied

Cooling setpoint 1

Cooling

auto

unoccupied

Cooling setpoint 2

Heating

sp1

-

Heating setpoint 1

Heating

sp 2 

-

Heating setpoint 2

Heating

auto

occupied

Heating setpoint 1

Heating

auto

unoccupied

Heating setpoint 2

REMOTE OPERATING MODE

PARAMETER STATUS
Heating/cooling 
operating mode

Setpoint selection 
contact

Active setpoint

Cooling 

sp 1 (open)

Cooling setpoint 1 

Cooling

sp 2 (closed)

Cooling setpoint 2

Heating

sp 1 (open)

Heating setpoint 1

Heating

sp 2 (closed)

Heating setpoint 2

5.6.2 - Reset

Reset  means  that  the  active  setpoint  is  modified  so  that  less 

machine capacity is required (in cooling mode, the setpoint is 

increased, in heating mode it is decreased). This modification 

is in general a reaction to a drop in the load. For the Pro-Dialog 

control system, the source of the reset can be configured in the 
HCCONFIG configuration: it can be provided either by the out

-

door temperature (that gives a measure of the load trends for 

the building) or by the return water temperature (heat exchanger 

delta T, gives an average building load). 

In response to a drop in the outdoor temperature or to a drop in 
delta T, the cooling setpoint is normally reset upwards in order 
to optimise unit performance: 

In both cases the reset parameters, i.e. slope, source and maximum 
value,  are  configurable  in  the  RESETCFG  menu  (see  section 

4.3.8). Reset is a linear function based on three parameters.

• 

A reference at which reset is zero (outdoor temperature 
or delta T - no reset value).

• 

A reference at which reset is maximum (outdoor 

temperature or delta T - full reset value).

• 

The maximum reset value.

Reset example in cooling mode based on the outside temperature

Legend

A  Maximum reset value

B  OAT or delta T for no reset

C  OAT or delta T for full reset

D  Building Load

5.7 - Demand limit

The demand limit is used to restrict the unit power consump-
tion. The Pro-Dialog control system allows limitation of the unit 
capacity, using user-controlled volt-free contacts. 

The unit capacity can never exceed the limit setpoint activated 
by  these  contacts. The  limit  setpoints  can  be  modified  in  the 

SETPOINT menu.

5.8 - Night mode

The night period is defined (see GENUNIT configuration) by a 

start time and an end time that are the same for each day of 
the week. During the night period, the number of fans operating 
can be reduced, and the unit capacity may be limited.

Reset v

alue

Outdoor temperature (OAT)

Heat exchanger delta T

% Building load

5 - PRO- CONTROL OPERATION

 

 

EN - 19 

EREBA ACCESS

Содержание PRO-DIALOG+

Страница 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Страница 2: ......

Страница 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Страница 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Страница 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Страница 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Страница 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Страница 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Страница 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Страница 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Страница 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Страница 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Страница 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Страница 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Страница 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Страница 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Страница 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Страница 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Страница 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Страница 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Страница 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Страница 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Страница 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Страница 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Страница 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Страница 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Страница 27: ......

Страница 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: