background image

5.9 - Capacity control

This function adjusts the number of active compressors to keep 

the heat exchanger water temperature at its setpoint. The preci

-

sion with which this is achieved depends on the capacity of the 

water loop, the flow rate, the load, and the number of stages avail

-

able on the unit. The control system continuously takes account 
of the temperature error with respect to the setpoint, as well as 
the rate of change in this error and the difference between en-
tering and leaving water temperatures, in order to determine the 
optimum moment at which to add or withdraw a capacity stage.

If the same compressor undergoes too many starts (per hour) 
or runs below one minute each time it is started this automati-
cally brings about reduction of compressor starts, which makes 
leaving water temperature control less precise.

The high pressure, low pressure or defrost unloading functions 
can also affect temperature control accuracy. Compressors are 
started and stopped in a sequence designed to equalise the 
number of start-ups (value weighted by their operating time).

5.10 - Head pressure control

The head pressure is independently controlled for each circuit, 
based on the saturated condensing temperature value.

5.11 - Defrost function

This function only applies to heat pumps. Defrost is activated, 
when the unit is in heating mode to reduce frost build-up on the 

air  heat  exchanger.  The  defrost  cycle  can  only  be  applied  to 

one circuit at a time. During the defrost cycle the fans of that cir-
cuit are stopped, and the four-way refrigerant valve is reversed, 
forcing the circuit to cooling mode. The fan can temporarily be 
restarted during the defrost cycle. The defrost cycle is fully auto-
matic and does not require any setting.

5.12 - Desuperheater option

In units with desuperheater it is possible to reclaim the hot wa-
ter. To optimise this option, the condensing setpoint should be 

increased (chapter 4.9.4 setpoint menu, sct_min) while the des

-

uperheater heat exchanger is used. Optimising desuperheater 
condensation is activated via dry contact DSHTR_SW 

(see chapter 3.6.1).

5.13 - Additional electric heater stage control

The heat pump units can control up to four additional electric 
heating stages (accessory).

The electric heating stages are activated to complement the 

heating capacity when the following conditions are satisfied:

• 

The unit uses 100% of the available heating capacity, or 
the unit is limited in its operation by a protection mode 
(low suction temperature, hot gas or defrost sequence in 
progress protection), and in all cases cannot satisfy the 
heating load.

• 

The outdoor temperature is below a configured threshold 

(see HCCONFIG configuration).

• 

The unit demand limit is not active.

The user may configure the last available electric heating stages 

as a safety stage. In this case, the safety stage is only activated 
in addition to the other stages if there is a machine fault, prevent-
ing the use of the heating capacity. The other electric heating 
stages will continue to operate as described above.

5.14 - Control of a boiler

NOTE: The control of the electric heating stages or of a 
boiler is not authorised for slave units.

The unit can control the start-up of a boiler, if it is in heating mode. 
When the boiler is operating, the unit water pump is stopped.

A heat pump unit and a boiler cannot operate together. In this 
case the boiler output is activated in the following conditions:

• 

The unit is in heating mode, but a fault prevents the use 
of the heat pump capacity.

• 

The unit is in heating mode, but works at a very low 
outdoor temperature, making the heat pump capacity 

insufficient. The outdoor air temperature threshold for use 

of the boiler is fixed at -10°C, but this value can be 

adjusted in the HCCONFIG menu.

5.15 - Master/slave assembly

Two Pro- units can be linked to produce a master/slave 
assembly. The two machines are interconnected over the pro-
prietary protocol communication bus. All parameters required for 

the master/slave function must be configured through the Service 
configuration menu.

Master/slave operation requires the connection of a tempe-rature 

probe at the common manifold on each machine, if the heat ex

-

changer leaving water temperature is controlled. It is not required, 
if the entering water temperature is controlled.

The master/slave assembly can operate with constant or varia-

ble flow. In the case of variable flow each machine must control 

its own water pump and automatically shut down the pump, if 
the cooling capacity is zero.

For constant flow operation the pumps for each unit are continu

-

ously operating, if the system is operating. The master unit can 
control a common pump that will be activated, when the system 
is started. In this case the slave unit pump is not used.

All control commands to the master/slave assembly (start/stop, 
setpoint, heating/cooling operation, load shedding, etc.) are 

handled by the unit which is configured as the master, and must 

therefore only be applied to the master unit. They will be trans-
mitted automatically to the slave unit.

The master unit can be controlled locally, remotely or by Network 
commands. Therefore to start up the assembly, simply validate 
the Master operating type (Master) on the master unit. If the Mas-

ter has been configured for remote control then use the remote 

volt-free contacts for unit start/stop.

The slave unit must stay in Network operating type continuously. 
To stop the master/slave assembly, select Local Off on the mas-
ter unit or use the remote volt-free contacts if the unit has been 

configured for remote control.

One of the functions of the master unit (depending on its configu

-

ration) may be the designation, whether the master or slave is to 
be the lead machine or the follower. The roles of lead machine 
and follower will be reversed when the difference in running hours 

between the two units exceeds a configurable value, ensuring that 

the running times of the two units are automatically equalised.

5 - PRO- CONTROL OPERATION

 

EREBA ACCESS 

 EN - 20 

Содержание PRO-DIALOG+

Страница 1: ...Instruction manual EREBA ACCESS 8 40 kW 11 2016 10183 PRO DIALOG...

Страница 2: ......

Страница 3: ...3 Password screens 6 4 4 Menu screen characteristics 6 4 5 Data screen or configurable parameter characteristics 6 4 6 Parameter modification 7 4 7 Operating mode screen 7 4 8 Menu tree structure 8 4...

Страница 4: ...ty to the unit be shut off before any work is begun Shut off the main power supply at the main circuit breaker or isolator IMPORTANT This equipment conforms to all applicable codes regarding electroma...

Страница 5: ...mounted under a metal plate An optional water system temperature sen sor can be used for master slave assembly control in the case of leaving water control In heat pump units a sensor placed on an air...

Страница 6: ...24 30A 31A NRCP2 BASE Unit operation relay output J3 CH 25 37 38 NRCP2 BASE Network connection J12 NRCP2 BASE RS 485 series connection Pin 1 signal Pin 2 ground Pin 3 signal Setpoint selection J4 CH 8...

Страница 7: ...g cooling contact Open Closed With multiplexing Off On cooling On heating On auto On off contact Open Closed Closed Open Heating cooling contact Open Open Closed Closed NOTE The automatic changeover f...

Страница 8: ...cs There are four default screens Each screen shows The unit status its screen number Three displayed parameters LOCAL OFF 1 On the left the unit status on the right the screen number Entering water t...

Страница 9: ...on hps1 40 0 C hps2 40 0 C hramp_sp 27 4 C Cooling Setpoint 2 Description of the item framed by the selection cursor The following screen allows modification of a parameter Modify value Screen descrip...

Страница 10: ...OLIDY16S HOLIDY02S OCC1P01S OCC1P02S NAVIGATION Password 0 ACCESS ALL USER DEFAULT SCREENS PASSWORD General parameters Temperatures Pressures Setpoint Inputs Outputs Pump status Operating time Unit st...

Страница 11: ...emperature OAT nnn n C Outside air temperature CHWSTEMP nnn n C Common master slave temperature SCT_A nnn n C Saturated condensing temperature A SST_A nnn n C Saturated suction temperature A SCT_B nnn...

Страница 12: ...B HD_POS_B 0 100 Position variable fan speed controller B RV_B On Off Four way refrigerant valve C_HEATER On Off Heat exchanger and lower coil heater BOILER On Off Boiler output EHS_STEP 0 4 Electric...

Страница 13: ...urs Operating hours pump 1 hr_cpum2 nnnnn hours Operating hours pump 2 nb_def_a nnnnn Number of defrost cycles circuit B nb_def_b nnnnn Number of defrost cycles circuit A 4 9 9 MODES menu NAME FORMAT...

Страница 14: ...t alarm 2 alarm_3c nnnnn Current alarm 3 alarm_4c nnnnn Current alarm 4 alarm_5c nnnnn Current alarm 5 alarm_1 nnnnn Current JBus alarm 1 alarm_2 nnnnn Current JBus alarm 2 alarm_3 nnnnn Current JBus...

Страница 15: ...tartdow 1 to 7 7 Day of the week 1 Monday startwom 1 to 5 5 Week of the month Winter time stopmon 1 to 12 10 Month stoptdow 1 to 7 7 Day of the week 1 Monday stopwom 1 to 5 5 Week of the month 4 9 18...

Страница 16: ...r_deg 16 7 to 16 7 0 C Cooling reset value HEATING RESET oathr_no 10 to 51 7 10 C Outside temperature for no reset oathr_fu 10 to 51 7 10 C Outside temperature for maximum reset dt_hr_no 0 to 13 9 0 C...

Страница 17: ...onday Tuesday P3 period 3 7h00 21h00 Wednesday P4 period 4 7h00 17h00 Thursday Friday P5 period 5 7h00 12h00 Saturday P6 period 6 20h00 21h00 Holidays P7 period 7 Not used in this example P8 period 8...

Страница 18: ...ending on the programmed periods validated for public holidays Each of these public holiday periods can be displayed and changed with the aid of a sub menu ATTENTION The broadcast function must be act...

Страница 19: ...utomatic mode the outdoor temperature determines the heating cooling standby changeover based on the two threshold values configured by the user see RESETCFG menu for cooling and heating mode changeov...

Страница 20: ...ents the unit from starting if it is open when the delay at start up has expired This open contact leads to an alarm shut down if the unit is running 5 5 Heat exchanger frost protection The heater for...

Страница 21: ...Heating sp 2 closed Heating setpoint 2 5 6 2 Reset Reset means that the active setpoint is modified so that less machine capacity is required in cooling mode the setpoint is increased in heating mode...

Страница 22: ...lt prevent ing the use of the heating capacity The other electric heating stages will continue to operate as described above 5 14 Control of a boiler NOTE The control of the electric heating stages or...

Страница 23: ...The follower will automatically use the master unit active setpoint The lead machine will be held at its full available capacity for as long as the active capacity on the follower is not zero When th...

Страница 24: ...t are active on the unit 6 3 Resetting alarms When the cause of the alarm has been corrected the alarm can be reset depending on the type either automatically on return to normal or manually when acti...

Страница 25: ...unication is re established Installation bus fault or defective slave board Depending on the configuration compressor A3 is shut down or circuit B is shut down 16 Co ht Communication loss with the add...

Страница 26: ...too low less than 10 C prevents unit start up Automatic when the temperature detected returns to normal or when the mode returns to cooling Operating compressor protection out of range or pressure se...

Страница 27: ......

Страница 28: ...ompagnie Industrielle d Applications Thermiques S A au capital de 26 728 480 R C S Bourg en Bresse B 545 620 114 Non contractual document With the thought of material improvement always in mind CIAT r...

Отзывы: