![CIAT CIATControl OPC Server Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/ciat/ciatcontrol-opc-server/ciatcontrol-opc-server_installation-and-operating-instructions-manual_2606705028.webp)
NA 12.46 A
©2012
CIAT
NA 12.46 A
installation instructions
[28]
V05.2012
110
P10 Fan type
0=axial, 1=centrifugal, 2=pressure
Do not change/
Manufacturer only
111
P103 control type
0: local, 1:remote
Do not change/
Manufacturer only
112
P11 Coil type
0=overlapping coils, 1=separated coils,
2=mixed coils
Do not change/
Manufacturer only
113
P112 Number of electric stages
-
Do not change/
Manufacturer only
114
P121 Cooling setpoint 1
step 0.5
Read/Write
115
P122 Cooling setpoint 2
step 0.5
Read/Write
116
P123 Heating setpoint 1
step 0.5
Read/Write
117
P124 Heating setpoint 2
step 0.5
Read/Write
118
P125.1 Setpoint for 4 mA in cooling mode
step 0.5
Read/Write
119
P125.2 Setpoint for 4 mA in heating mode
step 0.5
Read/Write
120
P126.1 Setpoint for 20 mA in cooling mode
step 0.5
Read/Write
121
P126.2 Setpoint for 20 mA in heating mode
step 0.5
Read/Write
122
P127 Cooling control according to the outside temperature
0=No, 1=Yes
Read/Write
123
P128 Drift start in cooling mode
-
Read/Write
124
P129 Drift end in cooling mode
-
Read/Write
125
P130 Cooling setpoint at end of drift
-
Read/Write
126
P131 Heating control according to the outside temperature
0=No, 1=Yes
Read/Write
127
P132 Drift start in heating mode
-
Read/Write
128
P133 Drift end in heating mode
-
Read/Write
129
P134 Heating setpoint at end of drift
-
Read/Write
130
P191 Low Noise operation
0=No, 1=Yes
Read/Write
131
P20 All-season function
0=No, 1=Yes
Read/Write