Channel Master
57
BuildingMode
Building occupancy provided by supervisor
0 = Bldg occupied/1=Bldg unoccupied/2 =
Bldg frost prot.
Write only
58
OccMode
Space occupancy (provided by supervisor)
0 = Occupied/1 = Standby/2 = Unoccupied
Write only
59
HVACMode
Mode (comfort, standby, economy, frost protection) provided
by a clock
1=Comfort/2=Stdby/3=Eco/4=Frost prot.
Write only
60
HVACModeOptim
Override mode (comfort, standby, economy, frost protection)
provided by supervisor
0=Auto/1=Comfort/2=Stdby/3=Eco/4=Frost
prot.
Write only
61
ContrMode
Special functions (provided by supervisor)
0=Auto/1=Heating/3=Cooling/9=Ventilation/
10=Free cooling
Write only
62
EnableHeat
Heating authorisation
0 = Disabled/1= Enabled
Write only
63
EnableCool
Air conditioning authorisation
0 = Disabled/1= Enabled
Write only
64
ChangeOverStatusWater
Central changeover
0 = Cooling/1 = Heating
Write only
65
TempOutside
Outdoor temperature
Temp. value in °C
Write only
66
TempRoomSetpSetHeat
Base heating setpoints (comfort, standby, economy)
Three temp. values in °C
Write only
67
TempRoomSetpSetCool
Base air conditioning setpoints (comfort, standby, economy)
Three temp. values in °C
Write only
68
TempRoomSetpSetHeatSh
ift
Drift of base heating setpoints (comfort, standby, economy)
Three temp. values in K
Write only
69
TempRoomSetpSetCoolShi
ft
Drift of base air conditioning setpoints (comfort, standby,
economy)
Three temp. values in K
Write only
70
TempRoomSetpUserAbs
User comfort setpoint, set via a KNX terminal
Temp. value in °C
Write only
71
TempRoomSetpUserOffset User comfort setpoint override set via a KNX terminal
Temperature shift value in K
Write only
72
ComfortPushButton
On/Off control via a KNX user terminal
0 = Reduced (Stdby/Eco/Frost
protection)/1=Comfort
Write only
73
HVACModeUser
User mode (comfort, standby, economy, frost protection) set
via a KNX terminal
0=Auto/1=Comfort/2=Stdby/3=Eco/4=Frost
prot.
Write only
74
FanSpeedUser
Manual speed set via a KNX terminal
Values of 0 to 100% LS 33% MS 66% GS
100%
Write only
75
FanManual
Auto/Man. speed selection via a KNX terminal
0=Auto/1=Man.
Write only
76
AQSetpUser
Air quality setpoint
CO2 value in ppm
Write only
77
HumRelSetpUser
Dehumidification setpoint
Relative humidity value in %
Write only
78
TempRoom
Ambient temperature provided by a terminal or KNX sensor
Temp. value in °C
Write only
79
AQRoom
Air quality in ppm
CO2 value in ppm
Write only
80
HumRelRoom
Relative humidity level in %
Relative humidity value in %
Write only
81
PresenceStatus
KNX presence detector
0 = Unoccupied/1 = Occupied
Write only
82
WindowSwitch
Synchronisation input for master/slave window switches
0 = Closed/1 = Open
Write only
83
WindowStatus
State of KNX window switch
0 = Closed/1 = Open
Write only
84
OnOff
On/Off control for synchronised output
0 = OFF/1 = ON
Write only
85
EnableAlarmInfo
Enable sending of AlarmInfo
0 = Disabled/1= Enabled
Write only
86
EnableAlarmText
Enable sending of AlarmText
0 = Disabled/1= Enabled
Write only