![CIAT CIATControl OPC Server Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/ciat/ciatcontrol-opc-server/ciatcontrol-opc-server_installation-and-operating-instructions-manual_2606705027.webp)
NA 12.46 A
©2012
CIAT
NA 12.46 A
installation instructions
[27]
V05.2012
88
Load shedding, stage 1, circuit 2
1=load shedding
Read-only
89
Load shedding, stage 2, circuit 1
1=load shedding
Read-only
90
Load shedding, stage 2, circuit 2
1=load shedding
Read-only
91
Load shedding via Modbus, stage 1, circuit 1 (different from 0 x 140)
1=Shed
Read/Write
92
Load shedding via Modbus, stage 1, circuit 2
1=Shed
Read/Write
93
Load shedding via Modbus, stage 2, circuit 1
1=Shed
Read/Write
94
Load shedding via Modbus, stage 2, circuit 2
1=Shed
Read/Write
95
State of auxiliary electric heater 1 or boiler
1=on
Read-only
96
State of auxiliary electric heater 2
1=on
Read-only
97
State of auxiliary electric heater 3
1=on
Read-only
98
State of auxiliary electric heater 4
1=on
Read-only
99
Stage 1, circuit 1 output status
1=on
Read-only
100
Stage 1, circuit 2 output status
1=on
Read-only
101
Stage 2, circuit 1 output status
1=on
Read-only
102
Stage 2, circuit 2 output status
1=on
Read-only
103
State of pump 1 output
1=on
Read-only
104
State of pump 2 output
1=on
Read-only
105
Heating or cooling operation
1=heating
Read/Write
106
On/Off
1=On
Read/Write
107
Actual operating mode
0= Off; 1=cooling; 2=heating
Read-only
108
Controller name
33=Connect2
Read-only
109
P06 Number of evaporators
-
Do not change/
Manufacturer only