installation instructions
[24]
V05.2012
21
EEPROM fault
1=Fault
Read-only
22
Stage 1, circuit 1 fault
1=Fault
Read-only
23
Stage 1, circuit 2 fault
1=Fault
Read-only
24
Stage 2, circuit 1 fault
1=Fault
Read-only
25
Stage 2, circuit 2 fault
1=Fault
Read-only
26
Circuit 1 exchanger frosting fault
1=Fault
Read-only
27
Circuit 2 exchanger frosting fault
1=Fault
Read-only
28
Circuit 1 refrigerant frosting fault
1=Fault
Read-only
29
Circuit 2 refrigerant frosting fault
1=Fault
Read-only
30
Circuit 1 water frosting fault
1=Fault
Read-only
31
Circuit 2 water frosting fault
1=Fault
Read-only
32
Circuit 1 manual HP fault
1=Fault
Read-only
33
Circuit 2 manual HP fault
1=Fault
Read-only
34
HP fault, circuit 1 pressure sensor
1=Fault
Read-only
35
HP fault, circuit 2 pressure sensor
1=Fault
Read-only
36
Aeroconnect link fault
1=Fault
Read-only
37
Link fault, additional board for reversible
1=Fault
Read-only
38
Circuit 1 expansion valve board link fault
1=Fault
Read-only
39
Circuit 2 expansion valve board link fault
1=Fault
Read-only
40
Mechanical fault, Inverter compressor
1=Fault
Read-only
41
VCM module fault, expansion valve 1
1=Fault
Read-only
42
VCM module fault, expansion valve 2
1=Fault
Read-only