P40  

Ventilation in comfort 

mode deadband  

In the comfort mode deadband, the fan may be on 
continuously, be off, or turn on periodically for a set number of 

seconds: 
0 = ventilation off  
1 = permanent ventilation, any season  
2 = permanent ventilation in summer  

3 = ventilation periodically restarted 

0:1:2:3  

Read/Write 

P41  

Ventilation in standby 
mode deadband  

In the standby mode deadband, the fan may be on 
continuously, be off, or turn on periodically for a set number of 
seconds:  

0 = ventilation off  
1 = permanent ventilation, any season  
2 = permanent ventilation in summer  

3 = ventilation periodically restarted  

0:1:2:3  

Read/Write 

P42  

Ventilation in economy 
mode deadband  

In the economy mode deadband, the fan may be on 

continuously, be off, or turn on periodically for a set number of 
seconds:  
0 = ventilation off  

1 = permanent ventilation, any season  
2 = permanent ventilation in summer  
3 = ventilation periodically restarted  

0:1:2:3  

Do not change/ 

Manufacturer only 

P43  

Ventilation in frost 
protection mode 
deadband  

In the frost protection mode deadband, the fan may be on 

continuously, be off, or turn on periodically for a set number of 
seconds:  
0 = ventilation off  
1 = permanent ventilation, any season  

2 = permanent ventilation in summer  
3 = ventilation periodically restarted  

0:1:2:3  

Do not change/ 

Manufacturer only 

P44  

Time between two 

periodic restarts  

The time set in this parameter is that during which the fan is off 

if it must run periodically in the deadband zone  

10…120 (resolution of 10)  

Do not change/ 

Manufacturer only 

P45  

Restart time  

Restart time if the periodic restart function is enabled on the 
above parameters  

30…180 (resolution of 30 s)  

Do not change/ 

Manufacturer only 

P46  

Time delay between fan 

speeds (in Auto mode)  

The fan does not shift directly to speed 3 without first 
remaining at speed 1 or 2 for a minimum period (in minutes). 
This also prevents oscillation of the fan speed during hysteresis  

0…10  

Do not change/ 

Manufacturer only 

P47  

Operating mode selected 

by the sleep button on the 
user terminal (former P79)  

The time set in this parameter is that during which the fan is off 
if it must run periodically in the deadband zone  

1 = Comfort --> Frost protection  
2 = Comfort --> Economy  
3 = Comfort --> Standby  

01:02:03 Read/Write 

P48  

Comfort override delay  

Override to remain in comfort mode after comfort mode 

activation from the user terminal. May be set to remain on at all 
times, to turn on for a specific period, or be disabled.  
0 = Override prohibited  

0.5...24 = Override time in h  
24.5 = Infinite override time  

0.0…24.5 (increments of 0.5 h)  

Read/Write 

P49  

Action direction of 

auxiliary contact on input 
D1  

The auxiliary contact on input DI1 may be normally closed or 
normally open:  
0 = Normally open  

1 = Normally closed  

00:01 

Do not change/

Manufacturer only/or ensure 

wiring is in place for the 

selected function  

P50  

Action direction of 

auxiliary contact on input 
D2  

The auxiliary contact on input DI2 may be normally closed or 
normally open:  
0 = Normally open  

1 = Normally closed  

00:01 

Do not change/

Manufacturer only/or ensure 

wiring is in place for the 

selected function  

P51  

Input D1 function  

Operating mode with window switch: 

0 = Inactive  
1 = Window switch (Comfort --> Frost protection)  
2 = Presence contact (Comfort --> Eco)  

3 = Presence contact (Comfort --> Standby)  
4 = Condensate drain pump  
5 = Fan unit motor alarm  

6 = General alarm  
7 = CO2 sensor  

0…7  

Do not change/ 

Manufacturer only/or ensure 

wiring is in place for the 

selected function  

P52  

Input D2 function  

This parameter allows the input to have several functions: 
0 = Inactive  
1 = Window switch (Comfort --> Frost protection)  

2 = Presence contact (Comfort --> Eco)  
3 = Presence contact (Comfort --> Standby)  
4 = Condensate drain pump  

5 = Fan unit motor alarm  
6 = General alarm  
7 = CO2 sensor  
8 = Frost protection for "Fresh air"  

9 = Condensation-free AC function  

0…9  

Do not change/ 

Manufacturer only/or ensure 

wiring is in place for the 

selected function  

 

Содержание CIATControl OPC Server

Страница 1: ...tion of the system s various CIATControls on an OPC compatible BMS Large range of licences for monitoring o 1 CIATControl o 2 to 5 CIATControls o Over 5 CIATControls Quick intuitive installation Includes Installation CD Dongle licence Installation and operating instructions To be carried out by the integrator Installation of the OPC server on the BMS CIATControl IP configuration CIATControl declar...

Страница 2: ...P 7 Server 2008 compatible Processor 1 6 Ghz RAM 1 Gb Disk space 1 Gb CD player 1 USB port available Net Framework version 2 0 2 Dongle licence 1 To be connected to the USB port 3 Installation and operating instructions 1 2 INSTALLING THE SOFTWARE Insert the installation CD in the CD player Double click on the icon to launch the installation The following window appears ...

Страница 3: ...ake sure you close all your open documents before clicking on Finish After restarting your computer the OPC server will be operational Connect the dongle to activate the licence 3 CONFIGURING THE STATIONS 1 Configuring the CIATControls Configure each CIATControl with a fixed IP address To do this identify yourself as a User click on Parameters and select the Ethernet configuration tab ...

Страница 4: ...nformation supplied by the network administrator or that assigned by the DHCP server IP address Subnet mask Gateway Click on Send to confirm the configuration Note if several CIATControls are present on the network please modify the computer name default name CIATCONTROL to a unique name to avoid conflicts The CIATControl will need to be restarted after the name has been modified Carry out the sam...

Страница 5: ...2 46 A 2012 CIAT NA 12 46 A installation instructions 5 V05 2012 2 Configuring the OPC server In Start Programs click on OPC Server Configurator The following window opens Click on NEW to add a CIATcontrol ...

Страница 6: ...fixed IP address then click on OK Click on PING to check the communication with the equipment Its status switches to Success Repeat the operation for each CIATControl When all the CIATControls have been configured close the application by clicking on the cross in the top right The OPC server is now configured ...

Страница 7: ... be monitored once all the items have been declared rather than updating the station each time an item is added deleted In particular this saves time when initialising the OPC server Disconnection time waiting time prior to disconnection of the link between the OPC server and the station for which no items are read by the OPC server Dataserver test frequency cyclical test to check for the presence...

Страница 8: ...y the OPC client The full address is indicated as well as the refresh time and value Bad addresses used to indicate incorrect addresses read written by the OPC client If these addresses do not exist they will be directly placed in this menu Group details gives a general overview of the OPC server as well as the value of the parameters set in the OPC server configurator Filter used to apply a filte...

Страница 9: ...00 restarts automatically It then loses the context in which it was switched to Auto mode It will not switch back to the mode requested by the time schedule when the mode next switches To prevent this the OPC client must send the command to the V3000 in order to make it switch back to the mode it was in before the restart The items available for each piece of equipment are displayed in French only...

Страница 10: ...tion instructions 10 V05 2012 In Configuration panel click on Program and Functions Win7 or Add Remove programs WinXP Win Server2003 2007 Select CIATControl OPC Server and click on uninstall The following window opens Follow the instructions ...

Страница 11: ...server Check that the OPCEnum service is activated Check that the firewall or antivirus software is not blocking access to the OPC server No stations are detected by the OPC server configurator or the OPC server itself Check that the different stations don t have the same IP address A conflict was detected on the network due to a similarity in the names of the panels on the network Please configur...

Страница 12: ...e event of a mains outage or a panel restart The OPC server attempts to reconnect periodically to the different stations Communication is thus restored automatically The project for a station must be modified adding deleting equipment Close the OPC server before making any modifications or delete the station from the OPC server configurator If equipment has been added deleted the OPC client must a...

Страница 13: ...Write P05 Cooling Standby setpoint Setpoint for cooling control in Standby mode 5 40 resolution of 0 5 Read Write P06 Economy heating setpoint Heating control setpoint in economy mode 5 40 resolution of 0 5 Read Write P07 Economy cooling setpoint Cooling control setpoint in economy mode 5 40 resolution of 0 5 Read Write P08 Frost protection setpoint Control setpoint during frost protection mode 5 ...

Страница 14: ...lection if recycled air application Control sensor selection 0 Return sensor priority 1 Indoor environment sensor priority 00 01 Read Write P25 Return air sensor calibration Correction factor for the return air sensor 9 9 9 9 resol of 0 1 Do not change Manufacturer only P26 Indoor environment sensor calibration Correction factor for the room sensor 9 9 9 9 resol of 0 1 Do not change Manufacturer o...

Страница 15: ... speed 1 or 2 for a minimum period in minutes This also prevents oscillation of the fan speed during hysteresis 0 10 Do not change Manufacturer only P47 Operating mode selected by the sleep button on the user terminal former P79 The time set in this parameter is that during which the fan is off if it must run periodically in the deadband zone 1 Comfort Frost protection 2 Comfort Economy 3 Comfort ...

Страница 16: ...300 resolution of 30 s Do not change Manufacturer only P62 Base outdoor temperature Lowest outdoor temperature for electric heater power limiting 35 5 Read Write P63 Excess capacity difference Temperature difference C between the real energy limitation curve and the theoretical energy limitation curve 0 5 resolution of 0 5 Do not change Manufacturer only P64 Setpoint drift as a function of the out...

Страница 17: ... setpoint at manual low speed 0 100 Do not change Manufacturer only P87 0 10 V brushless motor Man MS Fan setpoint at manual medium speed 0 100 Do not change Manufacturer only P88 0 10 V brushless motor Man HS Fan setpoint at manual high speed 0 100 Do not change Manufacturer only P89 0 10 V brushless motor auto speed algo Extra low fan speed in deadband 0 100 Do not change Manufacturer only P90 0...

Страница 18: ... Air quality setpoint provided by master device CO2 value in ppm Write only 12 HumRelSetpDehumEff Dehumidification setpoint provided by master device Relative humidity value in Write only 13 TempRoom Ambient temperature provided by user terminal CIAT or KNX Temp value in C Write only 14 TempReturnAir Return air temperature provided by master controller Temp value in C Write only 15 TempFlowWater W...

Страница 19: ...ation on state of heating valve position in Values of 0 to 100 Read only 40 ActPosHeatStageB Information on state of electric heater position in Values of 0 to 100 Read only 41 ActPosCoolStageA Information on state of air conditioning valve position in Values of 0 to 100 Read only 42 FanSpeed Information on state of fan speedin Values of 0 to 100 Read only 43 ActPosFreshAir Information on state of...

Страница 20: ...g setpoints comfort standby economy Three temp values in K Write only 70 TempRoomSetpUserAbs User comfort setpoint set via a KNX terminal Temp value in C Write only 71 TempRoomSetpUserOffset User comfort setpoint override set via a KNX terminal Temperature shift value in K Write only 72 ComfortPushButton On Off control via a KNX user terminal 0 Reduced Stdby Eco Frost protection 1 Comfort Write on...

Страница 21: ... Hot water coil consumption in kWh Read only 101 ElectricConsumption Electric heater consumption in kWh Electric heater consumption in kWh Read only 102 FanConsumption Fan motor consumption in kWh Ventilation consumption in kWh Read only 103 HVACModeEff Mode currently being used comfort standby economy frost protection 0 Auto 1 Comfort 2 Stdby 3 Eco 4 Frost prot Read only 104 TempRoomSetpSetHeatEf...

Страница 22: ... to slave by positioning of actuators Values of 0 to 100 Read only 125 FanSpeedSetp Ventilation control from master to slave by positioning of actuators Values of 0 to 100 Read only 126 ActPosSetpFreshAir Fresh air control from master to slave by positioning of actuators 0 or 100 Read only 127 InfoEnableHeat Enable heating from master to slave by enabling heating cooling mode 0 Disabled 1 Enabled ...

Страница 23: ...Circuit 1 LP fault 1 Fault Read only 9 Circuit 2 LP fault 1 Fault Read only 10 Circuit 1 LP sensor fault 1 Fault Read only 11 Circuit 2 LP sensor fault 1 Fault Read only 12 Circuit 1 HP sensor fault 1 Fault Read only 13 Circuit 2 HP sensor fault 1 Fault Read only 14 Change of operating mode fault 1 Fault Read only 15 Phase controller fault 1 Fault Read only 16 Water flow fault 1 Fault Read only 17...

Страница 24: ...0 Circuit 1 water frosting fault 1 Fault Read only 31 Circuit 2 water frosting fault 1 Fault Read only 32 Circuit 1 manual HP fault 1 Fault Read only 33 Circuit 2 manual HP fault 1 Fault Read only 34 HP fault circuit 1 pressure sensor 1 Fault Read only 35 HP fault circuit 2 pressure sensor 1 Fault Read only 36 Aeroconnect link fault 1 Fault Read only 37 Link fault additional board for reversible 1...

Страница 25: ...tage 2 circuit 2 discharge fault 1 Fault Read only 53 Tsat discharge fault Inverter compressor 1 Fault Read only 54 Exchanger ambient sensor fault 1 Fault Read only 55 Circuit 1 suction sensor fault 1 Fault Read only 56 Circuit 2 suction sensor fault 1 Fault Read only 57 Sensor fault coil A circuit 1 1 Fault Read only 58 Sensor fault coil A circuit 2 1 Fault Read only 59 Sensor fault coil B circui...

Страница 26: ...it 1 discharge sensor fault 1 Fault Read only 75 Stage 2 circuit 2 discharge sensor fault 1 Fault Read only 76 Loop outlet sensor fault Multiconnect 1 Fault Read only 77 Manifold outlet sensor fault 1 Fault Read only 78 Heat exchanger outlet sensor fault 1 Fault Read only 79 Circuit 1 exchanger outlet sensor fault 1 Fault Read only 80 Circuit 2 exchanger outlet sensor fault 1 Fault Read only 81 Ou...

Страница 27: ...iliary electric heater 1 or boiler 1 on Read only 96 State of auxiliary electric heater 2 1 on Read only 97 State of auxiliary electric heater 3 1 on Read only 98 State of auxiliary electric heater 4 1 on Read only 99 Stage 1 circuit 1 output status 1 on Read only 100 Stage 1 circuit 2 output status 1 on Read only 101 Stage 2 circuit 1 output status 1 on Read only 102 Stage 2 circuit 2 output stat...

Страница 28: ... for 4 mA in cooling mode step 0 5 Read Write 119 P125 2 Setpoint for 4 mA in heating mode step 0 5 Read Write 120 P126 1 Setpoint for 20 mA in cooling mode step 0 5 Read Write 121 P126 2 Setpoint for 20 mA in heating mode step 0 5 Read Write 122 P127 Cooling control according to the outside temperature 0 No 1 Yes Read Write 123 P128 Drift start in cooling mode Read Write 124 P129 Drift end in coo...

Страница 29: ... change Manufacturer only 139 P285 Heating mode runtime in hours Read only 140 P286 Cooling mode runtime in hours Read only 141 P287 Pump 1 runtime in hours Read only 142 P288 Pump 2 runtime in hours Read only 143 P310 Number of starts stage 1 circuit 1 Read only 144 P311 Stage 1 circuit 1 runtime Read only 145 P313 Number of starts stage 2 circuit 1 Read only 146 P314 Stage 2 circuit 1 runtime Re...

Страница 30: ...mmary 1 Fault Read only 156 Circuit 2 fault summary 1 Fault Read only 157 Operation summary on off and AB closed 1 on Read only 158 Condenser temperature Read only 159 Evaporator inlet temperature Read only 160 Outdoor temperature Read only 161 Outdoor temperature too high in cooling mode 1 Fault Read only 162 Evaporator outlet temperature Read only ...

Страница 31: ... Non critical fault output 0 On 1 Off Read only 10 Damper output frost protection or isolation 0 On 1 Off Read only 11 Plate heat exchanger bypass output 0 On 1 Off Read only 12 Intake filter fouling input 0 No 1 Yes Read only 13 Intake duct pressure input 0 No 1 Yes Read only 14 Intake temperature input C 10 Read only 15 Exhaust temperature input C 10 Read only 16 Exhaust duct pressure input Bar ...

Страница 32: ...tact closed Read only 2 On off input 2 0 Contact open 1 Contact closed Read only 3 On off input 3 0 Contact open 1 Contact closed Read only 4 On off input 4 0 Contact open 1 Contact closed Read only 5 On off output 1 0 Contact open 1 Contact closed Write only 6 On off output 2 0 Contact open 1 Contact closed Write only 7 On off output 3 0 Contact open 1 Contact closed Write only 8 On off output 4 ...

Отзывы: