NA 12.46 A
©2012
CIAT
NA 12.46 A
installation instructions
[17]
V05.2012
P76
Polling period for the
ambient temperature and
the return air temperature
over the bus:
Frequency at which the controller sends the ambient
temperature over the Konnex bus:
0 = No transmission
1…30 = period of time (minutes) distribution processes,
according to KNX constraints
0…30
Do not change/
Manufacturer only
P77
Application type
1 = Recycled air sequence
2 = Fresh air sequence
01:02
Do not change/
Manufacturer only
P78
Blown air temperature
limiting function
1 = Room control without supply air limiting
2 = Room control with supply air limiting
3 = Control at constant supply air temperature
01:02:03
Do not change/
Manufacturer only
P79
Number of fan speeds
1 = 1 auto and manual speed
2 = 2 auto and manual speeds
3 = 3 auto and manual speeds
4 = 1 manual speed only
5 = 2 manual speeds only
6 = 3 manual speeds only
1…6
Do not change/
Manufacturer only
P80
Fan speed 1 on
Low fan speed cut-in point
0…100
Do not change/
Manufacturer only
P81
Fan speed 2 on
Medium fan speed cut-in point
0…100
Do not change/
Manufacturer only
P82
Fan speed 3 on
High fan speed cut-in point
0…100
Do not change/
Manufacturer only
P83
Fan speed 1 off
Low fan speed cut-out point
0…100
Do not change/
Manufacturer only
P84
Fan speed 2 off
Medium fan speed cut-out point
0…100
Do not change/
Manufacturer only
P85
Fan speed 3 off
High fan speed cut-out point
0…100
Do not change/
Manufacturer only
P86
0/10 V brushless motor -
Man. LS
Fan setpoint at manual low speed
0…100
Do not change/
Manufacturer only
P87
0/10 V brushless motor -
Man. MS
Fan setpoint at manual medium speed
0…100
Do not change/
Manufacturer only
P88
0/10 V brushless motor -
Man. HS
Fan setpoint at manual high speed
0…100
Do not change/
Manufacturer only
P89
0/10 V brushless motor -
auto speed algo
Extra-low fan speed in deadband
0…100
Do not change/
Manufacturer only
P90
0/10 V brushless motor -
auto speed algo
Speed setpoint at fan start-up
0…100
Do not change/
Manufacturer only
P91
0/10 V brushless motor -
auto speed algo
Speed setpoint for a need corresponding to P85 (change in
control slope)
0…100
Do not change/
Manufacturer only
P92
Use of 0/10 V output
0 = Not used or 0/10 V valve
1 = Ventilation
2 = Current PID value
0 : 1 : 2
Do not change/
Manufacturer only
P93
Period for filter
maintenance
The maintenance pictogram appears onscreen at the end of this
ventilation period to indicate that the filter needs to be changed.
This pictogram does not stop control:
0 = Inactive
1…200 = time in days (in HS equivalent)
0…200
Read/Write
P94
Temperature displayed in
°C or °F
1 = Temperature displayed in °C
2 = Temperature displayed in °F
01:02
Read/Write
P95
Temperature displayed on
terminal
Actual temperature display on the indoor environment device
LCD:
1 = Setpoint
2 = Measurement
01:02
Read/Write
P96
Setpoint offset value
display
Display of actual temperature offset value:
1 = Not displayed (bar graph)
2 = Display bar graph
3 = Display se bar graph
01:02:03 Read/Write
P97
Application code
1 = 2-Wire
2 = 2-pipe
21 = 2-Pipe/2-Wire
22 = 2 Cold pipes + radiator
23 = 2-pipe + elec. convector
4 = 4-pipe
41 = 4-Pipe/2-Wire
1:2:21:22:23: 4:41
Do not change/
Manufacturer only