8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.6
Control point
The control point represents the water temperature that the
unit must produce. The required capacity can be decreased
depending on the unit load operating conditions.
Control point = Active se Reset
The control point is based on the active setpoint and the reset
calculation. The forced value can be used instead of any
other setpoint calculation only when the unit is in the Network
operating type.
8.6.1 Active setpoint
Two heating setpoints and three cooling setpoints can be
selected. The third cooling setpoint is used for ice storage
during unoccupied periods.
Depending on the current operation type, the active setpoint
can be selected using one of the following methods:
●
Manually
Via the Main menu (GENUNIT - General Parameters)
With the volt-free user contacts
Network commands
●
Automatically
Setpoint Time Schedule is used (schedule 2)
The following tables provide the overview of possible setpoint
selections, where the selected setpoint depends on the
following parameters:
Control operating type:
Local, Remote, Network
Mode:
Cooling or Heating
Setpoint select parameter:
The Setpoint Select parameter
in the General Parameters menu allows the user to select
the active setpoint when operating in the Local control
operating type [hc_sel in GENUNIT menu]
Ice configuration:
Ice production mode configuration
[ice_cnfg in GENCONF menu]
Ice done contact status:
Available on EMM SIOB board
Setpoint switch status:
Remote Setpoint switch parameter
in the Inputs menu
Schedule 2 status:
Schedule configuration
LOCAL OPERATING TYPE
Mode
Setpoint selection Ice configuration
Ice done contact
Setpoint switch
Schedule 2 status Active setpoint
cooling
sp-1
-
*
*
-
Cooling setpoint 1
cooling
sp-2
-
*
*
-
Cooling setpoint 2
cooling
(*)
enable
open
closed
-
Ice setpoint
cooling
(*)
enable
closed
closed
-
Cooling setpoint 2
cooling
auto
-
*
*
occupied
Cooling setpoint 1
cooling
auto
-
*
*
unoccupied
Cooling setpoint 2
cooling
auto
enable
open
*
unoccupied
Ice setpoint
cooling
auto
enable
closed
*
unoccupied
Cooling setpoint 2
heating
sp-1
-
*
*
-
Heating setpoint 1
heating
sp-2
-
*
*
-
Heating setpoint 2
heating
auto
-
*
*
occupied
Heating setpoint 1
heating
auto
-
*
*
unoccupied
Heating setpoint 2
REMOTE OPERATING TYPE
Mode
Setpoint selection Ice configuration
Ice done contact
Setpoint switch
Schedule 2 status Active setpoint
cooling
-
-
*
open
-
Cooling setpoint 1
cooling
-
-
*
closed
-
Cooling setpoint 2
cooling
-
enable
open
closed
-
Ice setpoint
cooling
-
enable
closed
closed
-
Cooling setpoint 2
heating
-
-
*
open
-
Heating setpoint 1
heating
-
-
*
closed
-
Heating setpoint 2
NETWORK OPERATING TYPE
Mode
Setpoint selection Ice configuration
Ice done contact
Setpoint switch
Schedule 2 status Active setpoint
cooling
-
-
*
*
occupied
Cooling setpoint 1
cooling
-
-
*
*
unoccupied
Cooling setpoint 2
heating
-
-
*
*
occupied
Heating setpoint 1
heating
-
-
*
*
unoccupied
Heating setpoint 2
* any configuration
- default configuration
AQUACIAT
POWER
EN-42