![CIAT AQUACIATPOWER ILD-HE Series Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/ciat/aquaciatpower-ild-he-series/aquaciatpower-ild-he-series_instruction-manual_2606702054.webp)
Drive alerts
Code
Alarm/Alert
Description
Action to be taken
VFD alerts
1
Alert
10 V low
Contact Manufacturer Agency
2
Alert
Live zero error
Contact Manufacturer Agency
3
Alert
No motor
Check the motor connections
4
Alert
Mains phase loss
Check the VFD supply voltage and the phase balance (±3%)
5
Alert
DC link voltage high
Check the VFD supply voltage and the phase balance (±3%)
6
Alert
DC link voltage low
Check the VFD supply voltage and the phase balance (±3%)
7
Alert
DC overvoltage
Contact Manufacturer Agency
8
Alert
DC undervoltage
Contact Manufacturer Agency
9
Alert
Inverter overloaded
Check the VFD output current
10
Alert
Motor overtemperature
Check the motor temperature
11
Alert
Motor thermistor
Contact Manufacturer Agency
12
Alert
Torque limit exceeded
Check the VFD output current
13
Alert
Overcurrent
Check the VFD output current
14
Alert
Earth fault
Check if an earth fault exists
17
Alert
Control word timeout
Check the connections and the shielding of the serial communication cable
23*
Alert
Internal fan fault
Check the internal fan rotation
25
Alert
Brake resistor short-circuited
Contact Manufacturer Agency
26
Alert
Brake resistor Power limit
Contact Manufacturer Agency
28
Alert
Brake verification
Contact Manufacturer Agency
34
Alert
Fieldbus communication fault
Check the connections and the shielding of the serial communication cable
36
Alert
Mains failure
Check the VFD supply voltage and the phase balance (±3%)
47
Alert
24 V supply low
Contact Manufacturer Agency
49
Alert
Motor speed limit exceeded
Contact Manufacturer Agency
59
Alert
Current limit exceeded
Check the VFD output current
62
Alert
Output frequency at maximum limit
Check the VFD output current
64
Alert
Voltage limit
Supply voltage too low
65
Alert
Control board over temperature
Check the space temperature and the VFD fan
66
Alert
Heat sink temperature low
Space temperature too low
71
Alert
PTC1 emergency stop
Contact Manufacturer Agency
72
Alert
Emergency stop
Contact Manufacturer Agency
90†
Alert
Encoder loss
Contact Manufacturer Agency
94
Alert
End of curve
Contact Manufacturer Agency
95
Alert
Torque loss
Contact Manufacturer Agency
96
Alert
Start delayed
Contact Manufacturer Agency
97
Alert
Stop delayed
Contact Manufacturer Agency
98
Alert
Clock fault
Contact Manufacturer Agency
243
Alert
IGBT defective
Contact Manufacturer Agency
247
Alert
Capacity board temperature
Contact Manufacturer Agency
* Error 24 and 104 possible
† Not applicable to VFD size 102
9 - DIAGNOSTICS
AQUACIAT
POWER
EN-54
Содержание AQUACIATPOWER ILD-HE Series
Страница 1: ...Instruction manual 05 2021 10536 CONNECT TOUCH AQUACIAT POWER I LD ST HE 602 2000...